Instrucciones de montaje
AM10 - Reservado el derecho de introducir modificaciones como consecuencia de mejoras técnicas
30
1
1.4
Single Boiler Control
To equip a single GB142 boiler with outdoor reset control:
Required items:
– ON/OFF thermostat for every heating zone with individual zone pump or zone valve
– Pump relay
– Wiring
If there are multiple zones, wire all thermostats in parallel for calls for heat from any thermostat
to produce a heat demand.
Fig. 7
Wiring detail
Outdoor
sensor
N
Pump Relay
H
C1
C2
X
X
T
T
Dedicated
120 Vac
15 Amp Circuit
Neutral
Zone
valve
Line
120 Vac
Field wiring
Low Voltage
Field wiring
AM10 Module
EV
1
2
FW
1
2
1
2
WA
1
2
FA
1
2
RC
DHW Tank
Sensor
Factory
Installed
Jumper
RC 10/20
Outdoor
sensor
T T
Connection
DHW
Sensor
Safety
Limit
Orange
Blue
Lt Green
Lt Gray
Red
GB142 wire terminal strip
Terminals FA and WA
not used in this
application
1
2
1
2
On / Off
1
2
Do not install RC10 module when
using this configuration.