Installation and servicing instructions for wall-mounted condensing gas boiler Buderus 600 - 11R/19R/24R • 02/2006
21
Subject to modifications resulting from technical improvements!
Buderus • http://www.buderus-domestic.co.uk
Installation
1
1.7
Flue Installation
1.7.1 Siting the flue terminal
z
The flue must be installed in accordance with the
recommendations of
BS. 5440-1:2000
.
Pluming will occur at the terminal so terminal positions
where this could cause a nuisance should be avoided.
The air supply and the flue gas exhaust must meet the
applicable general regulations. Please consult the
instructions provided with the flue terminal kits prior to
installation.
The boiler MUST be installed so that the terminal is
exposed to external air.
It is important that the position of the terminal allows the
free passage of air at all times.
Minimum acceptable spacing from the terminal to
obstructions and ventilation openings are specified in
table 1.
If the lowest part of the terminal is less than 2 metres
above the level of the ground, balcony, flat roof or place
to which any person has access, the terminal must be
protected by a guard.
Ensure that the guard is fitted centrally.
The flue assembly shall be so placed or shielded as to
prevent ignition or damage to any part of the building.
Terminal Position
Minimum
Spacing
A. Directly below, above or alongside
an opening window, air vent or
other ventilation opening
300 mm
B. Below guttering, drain pipes or soil
pipes
200 mm
C. Below eaves
200 mm
D. Below balconies or a car port roof
Not recommended!
200 mm
E. From vertical drain pipes or soil
pipes
150 mm
F. From internal or external corners
300 mm
G. Above adjacent ground, roof or
balcony level
300 mm
H. From a surface facing the terminal
600 mm
I.
From a terminal facing a terminal
1200 mm
J. From an opening in a car port (e.g.
door or window) into dwelling.
Not recommended
!
1200 mm
K. Vertically from a terminal on the
same wall
1500 mm
L. Horizontally from a terminal on the
wall
300 mm
M. Adjacent to opening
300 mm
N. Above intersection with roof
300 mm
O. From a vertical structure on the roof
500 mm
Fig. 10 Flue terminal position
table 1 Balanced flue terminal position
A
F
M
G
M
B,C
F
F
B,C
K
G
K
K
G
C
L
L
A
N
N
O
E
F
J
K
G
D
H, I