8
HOT AIR DUCT INSTALLATION
The BuckMaster Fireplace can be used to heat a single room or an entire house. The diagrams on this and the
following three pages show approved duct configuration.
1) SAME
ROOM
WITH
DUCT OPTION
United States and
Canada (WIRING
OPTION A)
2) SAME ROOM AND
SECOND ROOM United
States and Canada (WIRING
OPTION A)
3) CENTRAL HEATING
United States and Canada (See
complete layout on following
page.)
(WIRING OPTION B,C or D)
4) TWO ADJACENT ROOMS
United States Only (WIRING
OPTION B or D)
5) BASEMENT, SAME
ROOM AND SECOND
ROOM
United States Only
(WIRING OPTION B)
NOTES:
A. In installations where ductwork is run downward, one
standard hot air vent must also open into the fireplace
room.
B. Booster fans must not be enclosed with a chase.
C. Booster fans on upward ductwork must be equipped
with snap disk, heat sensitive switches. Booster fans
on downward ductwork may be equipped with snap
disk, heat sensitive switches or an on/off switch.
D. All hot air ductwork must be 8" diameter B-Vent
through the initial wall or ceiling penetration. Single
wall pipe may then be used providing booster fans and
self closing dampers are installed on upward ducting.
E. See wiring section for detailed electrical requirements.
F. B-Vent will retain heat much better than single wall
pipe for longer runs.
G. Cut hole in outer skin of B-Vent to install snap disk.