CRX Modes:
The XT Panel operates in two modes: the main operation mode and a secondary mode. De-
pending on the setup of the alarms, it is possible to continue running in an alarm mode.
For example, for a cell pump failure, the secondary mode would indicate a cell pump failure, send out the alarm,
indicate an alarm (a blinking red light) but continue to run in Cooling or Refrigeration. Wetbulb calculation would
be shut off.
3.0
CRX Modes of Operation
Main Operation Modes:
Shutdown:
Shutdown is activated by the Stop/Start switch set to the Stop position.
Standby:
Standby can only be activated with the time clock set to standby or
with no outside cooling available during Cooling mode.
Cooling:
Cooling mode can only be activated with outside cooling air available
and time clock set to either Cooling or Refrigeration mode.
Refrig:
Refrigeration mode will be activated when cooling air is not available
and the time clock is set for Run or Ref Only.
Recirc
Recirc will be activated when the time clock is set to Recirc, there
is no outside cooling air available and the refrigeration switch is set to
Off.
Remote Stop:
Remote stop is activated with the Stop button from either the HMI
touch screen or web interface.
Low Temp:
The low temp alarm is triggered by the backup low temp safety
thermostat. It can only be reset with the Start/Stop switch.
Parameter Fail:
The Parameter fail is triggered by an out-of-range setting on one of the
critical parameters. If setpoint is < 32.0 or > 76.7, the alarm is trig-
gered. If target is < 32.0 or > 76.7, the alarm is triggered. If pile diff
selection > 8, the alarm is triggered. If Start differential > 50 or < -50,
the alarm is triggered.
Remote Standby:
Remote Standby is activated by a contact closure across input IN4.
Typically used for off-peak power, ripple control or refrig defrost.
Alarm Standby:
Any alarm condition that was set to shut down the system.
Fan Fail:
The fan input IN1 did not get a closed contact within the fan fail timer
period. There is a programmable timer associated with this alarm.
Cooling / Purge:
The system is in Cooling and the return air heaters are being used to
force the fresh air doors open. This cycle has been triggered by time
and not the CO2 sensor.
Refrig / Purge:
The system is in Refrigeration and the fresh air doors are open to the
max door setting. This cycle has been triggered by time and not the