RWA - Control Unit BCR

Indicator and Control Elements

 

i

nDiCator

 

anD

 C

ontrol

 e

lements

Push buttons:

Drive run direction  

A

 = OPEN / 

Z

 = CLOSE

2 x on   BCR 8A-0102 
              BCR 12A-0102

Reset / Emergency-CLOSE

resetting smoke detectors 
after Emergency-OPEN

Indicators

:

(GN) = Operation

(YE)  = Fault

(RD) = Alarm (Emergency-OPEN)

Drive run direction and position

A

 = OPEN (red)        

Duo-LED

Z

 = CLOSE (green)  

Duo-LED

2 x on   BCR 8A-0102 
              BCR 12A-0102

 

The 

Duo-LED

 only lights up for the duration of the drive run time  

(in red or in green light).

i

ndicator

 

and

 c

ontrol

 e

lements

Position in the Control Unit

Meaning of the Displays (overview)

The indicators and control elements (switches) are in the 
same position on all BCR versions. 
Only the number of ventilation lines varies. 
The versions BCR 8A-0102, BCR 12A-0102 have two sets 
of indicators and control elements for the drive control 
(LT 1 and LT 2). 

Basically, the green indicator „

B

“ signals that the Con-

trol Unit works properly. A yellow indicator „

S

“ lighting 

up signals a fault to be eliminated immediately.
Since the type of fault signal into the breakglass units 
may differ from the fault indicator „

S

“ in the Control 

Unit, always pay regard to the indicators in the Control 
Unit for exact troubleshooting.

reset

wind

T / SH ML

 - A

HSE 

- A

RM 

- A

NF 

- A

BF 

- A

Battery

GND

Battery

F2

F3

L1

open

L2

open

L1

close

L2

close

red: open

green: close

Wind-Speed (reshold) 

[m/s]

Drive 1

Drive 2 

07

Drive run direction

Drives

Drives

*) The 

Duo-LED

 only lights up for the duration of the drive run time.

off

on (red)

on (green)

off

1 2 3

1 2 3

A

Z

reset

A

S

B

red: 

green: 

open

close

red: open 

green: close 

A

A

Z

Z

Summary of Contents for BCR - 12 A

Page 1: ...RWA Control Unit BCR 2 A 4 A 8 A 12 A Installation and Commissioning Instructions Control Unit BCR ...

Page 2: ...ation step 1 Connection of drives and ventilation Installation step 2 Connection of automatic and manual smoke detectors Installation step 3 Connection of wind sensors and rain sensors Installation step 4 Connecting power supply Installation step 5 LED s and DIP switches Installation step 6 Enabling operation Completing installation Troublshooting and repair Fuses Indicator and Control elements Ma...

Page 3: ...reliminary Remark Useful note for an optimum installation Abbreviations Scale units C Degree Celsius A Amps Ah Amp hours kg Kilogram m Metres min Minutes mm Millimeters N Newtons s Seconds Pcs Pieces V Volts PU Packaging Units Vpp Residual ripple Voltage Peak Peak W Watts Ω k Ω Ohm kilo Ohm Figures AC Alternating current 50Hz 60Hz DC Direct current I Electric current L Length ME Module space unit ...

Page 4: ...ion Scope of application This control device is intended for power feeding and con trolling of electromotive operated windows in facade or roof areas The prime task of this product in combina tion with the electromotive window is to evacuate hot smoke and combustion gases in case of fire to save human lives and protect material assets Furthermore the electromotive operated window ensures fresh air...

Page 5: ...then installation 1 5 m inaccessible for public 7 12 1 Keep people away during closing Caution NRWA in accordance with EN12101 2 without dual purpose for ventilation Observe danger at NSK 2 5 m above floor Caution Keep people away during closing Caution In the environment with children people in need of protection Hazard analysis according to DIN EN 60335 2 103 Contact free anti trap protection 20...

Page 6: ...ce life of the products Risk of crushing and entrapment Electromotive operated windows can close automatically The compressive force is absolutely sufficient to crush fingers in case of carelessness 01 The planning and calculation of the wiring system is the responsibility of the builder or his agent or the authori zed constructor and must be performed according to the statutory provisions All rel...

Page 7: ... operati on It is recommended to perform an insulati on measurement of the system s line network and to document this Warning It is imperative that the information provided in the installation instructions of the controlled window drives are ob served and adhered to 01 Note Post warning signs During the proper assembly of drives with mounting elements at a window and the connection to an external ...

Page 8: ...e most recent state of country specific laws regulations provisions and standards must absolutely be observed du ring the installation and for electrical connections These are for instance State building code with special construction regulations such as Industrial construction guideline Venue regulations etc MLAR Sample Guideline on Conduits German desig nation Provisions of the fire protection a...

Page 9: ...ehind Prepared for 2 maintanance free backup accumulators 2x 12 V 2 3 Ah Part Nr 60 304 Control Unit BCR4A 0101 Article Application Compact Control Unit for smoke and heat exhaust ventilation systems operating with 24 V DC voltage suitable for staircases Technical Data Rated values Operating voltage Max power consumption Output voltage Output current Ambient temperature range Protection rating Hou...

Page 10: ...repared for 2 maintanance free backup accumulators 2x 12 V 7 Ah Part Nr 60 305 Control Unit BCR12A 0102 Article Application Compact Control Unit for smoke and heat exhaust ventilation systems operating with 24 V DC voltage suitable for staircases Technical Data Rated values Operating voltage Max power consumption Output voltage Output current Ambient temperature range Protection rating Housing Dim...

Page 11: ... 96 hours Mechanical Data Surface mounted housing Protection class Device type Housing dimensions W x H x D steel plate painted in RAL 7035 IP 30 Type D 316 x 305 x 112 mm all dimensions given without lock Preparing Assembly Preparing assembly Technical Data Warning Important instructions for safe assem bly Fully observe all instructions incorrect assembly may lead to serious injuries Before start...

Page 12: ...7 Input for smoke detectors max 10 8 Input for signal from external fire alarm system alternative connection to smoke detectors 9 Input for break glass units HSE max 10 10 Output for signal transduction 1 alarm release 11 Output for signal transduction 2 collective fault only available for BCR8A and BCR12A RAUCHABZUG O K RAUCHABZUG O K BMA 1 2 4 3 11 10 6 9 8 7 Operating voltage primary 195 253 V ...

Page 13: ...and ventilation BCR 2 A 0101 and BCR 4 A 0101 04 reset close close red open green close Drive 1 Drives 24V GND alarm operation fault GND GND O PEN C LOSE REL 6 REL 6 REL 6 REL 7 REL 7 REL 7 com n c n o com n c n o button L2 button L2 LED LED LED Alarm Fault inverted 1 s 1 2 Terminal M1 M2 2 1 BU BN BN BU BK BK OG BU BN Install drive line end module at the last drive in the line ...

Page 14: ...Drives 24V Drives 24V GND alarm operation fault GND GND O PEN C LOSE REL 6 REL 6 REL 6 REL 7 REL 7 REL 7 com n c n o com n c n o button L2 button L2 LED LED LED Alarm Fault inverted 1 s GND alarm reset GND smoke detector GND GND 24 V GND rain GND wind O PEN C LOSE button L1 button L1 HSE HSE 1 s 1 2 Terminal M1 M2 2 1 BU BN BN BU BK BK OG BU BN 1 2 Terminal M1 M2 2 1 BU BN BN BU Install drive line...

Page 15: ...n L2 LED LED LED GND alarm reset GND smoke detector GND GND 24 V GND rain GND wind O PEN C LOSE button L1 button L1 HSE HSE Alarm Fault inverted smoke detector OK 1 2 3 4 5 6 7 8 9 11 10 OK 1 2 3 4 5 6 7 8 9 11 10 RE 1 2 3 1 2 3 4 1 2 3 4 5 6 7 8 9 10 11 HSE Break glass unit Installation step 2 Connection Automatic and Manual Smoke Detectors 04 The fire detector connection is closed circuit moni t...

Page 16: ... s Drive 1 Drive 2 GND alarm reset GND smoke detector GND GND 24 V GND rain GND wind O PEN C LOSE button L1 button L1 HSE HSE 24 V 1 2 3 4 5 rain wind 04 In case of fire emergency OPEN or failure of power supply accumu lator operation the ventilation control via wind and rain sensors is deactivated Before mounting and positioning the wind sensors rain sensors carefully read the safety and assembly...

Page 17: ... red open green close Wind Speed reshold m s Drive 1 Ensure correct polarity when connecting blue red Operating voltage primary 195 253 V AC 05 Route line voltage supply via external fuse and switching component Only connect supply voltage and accumulator set when disconnected from the mains power supply Switch off power supply and secure against reconnection It is essential to ensure correct pola...

Page 18: ...ed open green close Wind Speed reshold m s Drive 1 Drive 2 Ensure correct polarity when connecting blue red Operating voltage primary 195 253 V AC Route line voltage supply via external fuse and switching component Only connect supply voltage and accumulator set when disconnected from the mains power supply Switch off power supply and secure against reconnection It is essential to ensure correct p...

Page 19: ...ergency OPEN alarm power supply operation ON OFF ON ON OFF ON Emergency OPEN alarm back up accumulators mode OFF flashes ON OFF flashes ON Power failure highest priority OFF flashes OFF OFF flashes OFF Fault breakglass unit lines OFF ON OFF OFF ON OFF Fault smoke detector lines OFF blinks slowly OFF OFF ON OFF Fault motor line 1 OFF blinks 4x OFF OFF blinks slowly OFF Fault motor line 2 OFF blinks...

Page 20: ...es to system components that do not come under our producer responsibility or whose installation had not been commissioned but are still components of the RWA system Upon completion of the installation all functions of the Control Unit must be checked for correct functionality with utmost care Even if there is no fault indication this does not mean that all components function faultlessly Warning ...

Page 21: ... x 20 mm RWA Control Unit BCR F1 5 A accumulators BCR 2A 0101 F2 3 15 AT drives F1 5 A accumulators BCR 4A 0101 F2 6 3 AT drives F1 10 A accumulators BCR 8A 0102 F2 10 AT drive 1 F3 10 AT drive 2 F1 20 A accumulators BCR 12A 0102 F2 10 AT drive 1 F3 10 AT drive 2 06 L1 open L1 close red open green close Drive 1 Drive 2 F1 F2 F3 Fuses ...

Page 22: ...he number of ventilation lines varies The versions BCR 8A 0102 BCR 12A 0102 have two sets of indicators and control elements for the drive control LT 1 and LT 2 Basically the green indicator B signals that the Con trol Unit works properly A yellow indicator S lighting up signals a fault to be eliminated immediately Since the type of fault signal into the breakglass units may differ from the fault ...

Page 23: ...intenance Maintenance Warranty 07 Important maintenance information While working in the Control Unit the workplace must be secured against unauthorized access The specialists performing the maintenance work are solely re sponsible for the maintenance For smoke and heat exhaust systems a log book must be kept in which the maintenance work must be documented Special attention must be paid to operat...

Page 24: ...In case the Control Unit is permanently decommissioned the statutory provisions for the destruction recycling and disposal shall be observed The control device contains plastic metal electrical components and ac cumulators Replaced accumulators contain highly toxic pollutants and may therefore only be disposed of at collection points prescribed by the legislator Keep the storage time of lead acid ...

Page 25: ...25 RWA Control Unit BCR Notes 08 ...

Page 26: ...26 RWA Control Unit BCR Notes 08 ...

Page 27: ...stration Basically the General Terms and Conditions of BTR GmbH apply to all offers supplies and services The publication of these assembly and commissioning instructions supersedes all previous editions Certificate and Declaration of Conformity We declare under our sole responsibility that the product described under Data sheet is in conformity with the following directives 2014 30 EU Directive r...

Page 28: ...9000032851_V0 3_KW16 21 www btr hamburg de BTR GmbH Gemeindewald 11 D 86672 Thierhaupten Telefon 49 8271 811 92 0 Fax 49 8271 811 92 55 ...

Reviews: