Megabreak®
85
SWITCH DISCONNECTORS
According to IEC 60947-3 Megabreak®
Megabreak®
I 2500
Megabreak®
I 4000
Megabreak®
I 6300
Poles number
3P-4P
3P-4P
3P-4P
Rated uninterrupted current (In) [A]
1250÷2500 3200-4000
6300
Isolation voltage (Ui) [V]
1000
1000
1000
Rated impulsive voltage (Uimp) [kV]
12
12
12
Service voltage at 50÷60Hz (Ue) [V]
690
690
690
Utilization category
AC23
AC23
AC23
Rated short circuit making
capacity (kA)
220V÷500Va.c.
143
220
220
600Va.c.
132
165
165
690Va.c.
121
143
143
Rated short-time withstand
current Icw (kA) t=1s
220V÷500Va.c.
65
85
100
600Va.c.
60
75
75
690Va.c.
55
65
65
Rated short-time withstand current
Icw (kA) t=3s
220V÷500Va.c.
45
65
85
600Va.c.
45
65
75
690Va.c
45
65
65
Isolation capability
yes
yes
yes
Endurance
(cycles)
mechanical
without
maintenance
10000
10000
5000
with
maintenance
20000
20000
10000
electrical
without
maintenance
10000
10000
5000
Opening time
15 ms
15 ms
15 ms
Closing time
30 ms
30 ms
30 ms
Visualization of contacts position
S
S
S
Visualization of charged/
discharged springs
S
S
S
Auxiliary contacts
S*/O
S*/O
S*/O
Shunt trip
O
O
O
Closing coil
O
O
O
Undervoltage release
O
O
O
Undervoltage release with time delay
O
O
O
Motor operator
O
O
O
Mechanical counter
O
O
O
Mechanical interlock
O
O
O
* Standard version with n° 4 NO/NC (max n° 6 optional contacts M8AGG).
S=Standard O=Optional
Summary of Contents for Megabreak 2500
Page 1: ...Megabreak Manuale installatore Installation manual Y3142G 01GF 16W39...
Page 2: ...2 Megabreak IT UK ITALIAN 3 ENGLISH 69...
Page 32: ...32 Megabreak 6300 3 poli 68 130 130 130 130 130 68 90 30 85 30 354 100...
Page 34: ...34 Megabreak 6300 4 poli 68 130 130 130 130 130 130 130 68 90 30 85 30 354 100...
Page 68: ......
Page 69: ...Megabreak Manuale installatore Installation manual Y3142G 01GF 16W39...
Page 70: ...70...
Page 100: ...100 Megabreak 6300 3 poles 68 130 130 130 130 130 68 90 30 85 30 354 100...
Page 102: ...102 Megabreak 6300 4 poles 68 130 130 130 130 130 130 130 68 90 30 85 30 354 100...