Megabreak®
113
Installation of Terminal Adaptor available as an accessory.
"X" max
(mm)
"X" max (mm)
Termination support must be
made of isolating material and
sized according to the bars in
order to avoid performances
during short circuit conditions
Megabreak 2500 = 25 Nm
Megabreak 4000 = 36 Nm
Megabreak 6300 = 36 Nm
Icc (kA)
≤ 42
≤ 50
≤ 65
≤ 100
“X” max (mm)
350
300
250
150