![BTECH S5 BATTERY VALIDATION SYSTEM SCM-600 Operating Manual Download Page 34](http://html.mh-extra.com/html/btech/s5-battery-validation-system-scm-600/s5-battery-validation-system-scm-600_operating-manual_2824997034.webp)
34
S5 Battery Validation System
8
Check the
impedance
multipliers.
a. From the Communications window, click
System Configuration.
b. In the System Configuration window, click the
Impedance Multipliers tab.
c. In the Impedance Multipliers tab, click the
Auto Multiplier Setup button. The system will
measure the impedance across all the battery
units in all the strings.
If you get an error message after clicking the
Auto Multiplier Setup button, you will need to
generate the multipliers manually. Call BTECH
Tech Support for assistance.
d. Wait for the process to finish. Depending upon
how many battery strings you have, and how
many units per string, it could take anywhere
from 1 or 2 minutes to much longer than that. (It
takes about 15 seconds per unit.)
d. When the impedance readings are finished,
multiplier values will appear. Click OK to accept
them.
Action
How to do it
Picture