BT UPS Enterprise SNMP Agent
Issued by: BT
Version no: 6.1
Date: March 2019
Page 50 of 103
5.2.11.3
Receiver cellular number and message content
To send instant SMS, enter recipient’s mobile number and SMS text with configurable of
Unicode or Character format
5.2.11.4
NetSwitch (BT series only)
When BT NetAgent connects with NetSwitch on RPM, it able to perform action to the
specific outlet when following event or alarm triggers.
Events
1. UPS Load Overrun
2. UPS Communication Lost
3. AC Power Failed
4. UPS Battery Low
5. UPS Temperature Overun
6. When battery capacity
reaches to %
NetFeeler II (environmental sensor)
1. Temperature Overrun/
Underrun
2. Humidity
Overrun/Underrun
3. Water
4. Smoke
5. Gas
6. Security (Door/ Windows
1~7)
5.2.11.5
NetSwitch Setting
Select NetSwitch
:
To select the NetSwitch
Address Change
:
RPM could be daisy chain up to 16 units to control a total of
128 devices. Use this to assign a new number or change the
currently assigned number for the RPM unit. You have a choice
of 00 to 16.
Note
:
You cannot choose a number that is already assigned to another
RPM.
Identification
:
To give a unique name for the RPM.
Outlet
:
Indicate outlets A-H
Name
:
To set a unique name for the Outlets
Phone Controllable
:
Option of “Yes” or ”No”
Control type
:
Select between “Instant Shutdown”; Safe Reboot”; ”Safe
Shutdown”
Power off Delay
:
Sets the power off delay time in seconds (value from 0 to 9999)