NetAgent 

BT UPS Enterprise SNMP Agent 
User Manual 

Version 6.1  
 

Issue Date March 2019 

 
 

 

 

Summary of Contents for BP505

Page 1: ...NetAgent BT UPS Enterprise SNMP Agent User Manual Version 6 1 Issue Date March 2019 ...

Page 2: ...ll the NetAgent II with UPS and Network 19 3 2 Install the NetAgent Mini with UPS and Network 20 4 Using Netility Setup IP Update Firmware 21 4 1 Install Netility 21 4 2 Using Netility 21 5 UPS Web management by NetAgent 26 5 1 Introduction 26 5 2 NetAgent UPS Web Interface 27 5 3 Log Information 58 5 4 Help 62 6 Telnet Remote Configuration 65 6 1 Introduction 65 6 2 Telnet Configuration 65 6 3 Te...

Page 3: ...indows Based UPS Management System 75 8 1 Introduction 75 8 2 System Requirements 75 8 3 Install SNMPView 75 8 4 Using SNMPView 76 8 5 SNMPView Buttons 77 9 Appendix A Update the firmware of NetAgent UPS 93 10 Appendix B 3 Ports NetAgent II with SMS Modem 96 11 Appendix C SMS Server with SMS Modme 99 ...

Page 4: ...nstallation procedure CD provides along with NetAgent offers several softwares to allow the user to configure IP address central monitoring and multi shutdown on different operating systems Other advance configurations could be accomplished in the Webbrowser Features Provide SNMP MIB to monitor control UPS Auto sense 10M 100M Fast Ethernet Manage and configure via Telnet Web Browser or NMS Support...

Page 5: ...NetFeeler II to get the temperature humidity smoke fire signals These informations could also be revealed on the NetAgent Web page When there is an abnormal condition happened it could also be sent as a trap to the system manager 1 2 4 When we need the NetAgent When we need to remote monitoring and controls the UPS conditions For example the system manager could use the Internet to control all the...

Page 6: ...nternal External 1 3 Ports 1 3 phases CP504 CT504 1Port Internal card NetAgent Utility CD User Manual Internal CP503 CT503 1Port External card NetAgent Utility CD User Manual Adaptor External 1 Port 1 3 phases BP505 3 Port External Agent NetAgent Utility CD User Manual M2501 Cable for Contact Closure UPS M2502 or M2505 Cable for RS232 UPS M2506 Cable for Modem 9V DC adapter External 3 Ports 1 3 ph...

Page 7: ...tAgent Utility CD User Manual Internal DP802 DT802 Internal NetAgent Mini NetAgent Utility CD User Manual Internal DP522 DT522 Enternal NetAgent Mini NetAgent Utility CD User Manual 5 3V DC adapter External DP523 DT523 Enternal NetAgent Mini Dry Contact NetAgent Utility CD User Manual 5 3V DC adapter External DP532 DT532 Enternal NetAgent Mini with LCD Display NetAgent Utility CD User Manual 5 3V ...

Page 8: ...BT UPS Enterprise SNMP Agent Issued by BT Version no 6 1 Date March 2019 Page 8 of 103 CP504 CP503 BP506 BP505 NetAgent Mini DP Series DP520 DP522 DP532 ...

Page 9: ... managementsoftware o SMS Server SMSNotification o UPS MIB MIB file for the Network ManagementSystem o Time Server Timeadjustmentutility o And NetAgentinstallation usersmanual M2501 Cable For external NetAgent II connection to contact closure UPS M2502 or M2505 Cable For external NetAgent II connection to RS 232 UPS M2506 Cable For connection 3Port NetAgent and Modem 9V DC Adapter For External Net...

Page 10: ...rch 2019 Page 10 of 103 o Ports NetAgent Internal External LED Table Yellow Red Green Status Solid Off Solid Off Solid ON Power ON Flashing Solid ON Solid ON System initial Solid ON Solid Off Solid ON Normal operation Solid ON Flashing Solid ON No connection to UPS ...

Page 11: ...r Red Connection state with UPS Flash no connection with UPS Orange Correspondence state Light flashes when Netagent transmits command to UPS Light signal application of NetAgent Mini LAN Port LED Light color Condition description Green On Internet correspond speed is 100M Flash Data transmmiting Yellow On Internet correspond speed is 10M Flash Data transmmiting Fig 3 NetAgent Mini Out looking 1 4...

Page 12: ...rnal card BX506 NetAgent Utility CD User Manual Internal 3Ports 3 M2506 Cable for Modem 1 1Port External card 2 NetAgent Utility CD 1 3 Phase CX503 User Manual M2501 Cable for Contact Closure UPS External 1Port 5 M2502 or M2505 Cable for RS232 UPS 6 Adaptor 1 1Port Internal card CX504 2 NetAgent Utility CD Internal 3 User Manual 1Port 1 Internal NetAgent Mini DX520 NetAgent Utility CD User Manual ...

Page 13: ...BT UPS Enterprise SNMP Agent Issued by BT Version no 6 1 Date March 2019 Page 13 of 103 CX504 CX503 BX506 BX505 NetAgent 9 Mini DX Series DX520 DX801 ...

Page 14: ...platformmultipleNetAgent UPS managementsoftware o SMS Server SMSNotification o UPS MIB MIB file for the Network ManagementSystem o Time Server Timeadjustmentutility o And NetAgentinstallation usersmanual M2501 Cable For external NetAgent II connection to contact closure UPS M2502 or M2505 Cable For external NetAgent II connection to RS 232 UPS M2506 Cable For connection 3Port NetAgent and Modem 9V...

Page 15: ...BT UPS Enterprise SNMP Agent Issued by BT Version no 6 1 Date March 2019 Page 15 of 103 1 4 4 NetAgent 9 Outlook Port NetAgent Internal External 3 Ports NetAgent Internal External ...

Page 16: ...ON Normal operation Solid ON Flashing Solid ON No connection to UPS Flashing Flashing Solid ON Writing data to flash memory Green light Power state Red light Connection state with UPS 1 5 NetAgent 9 Mini Outlook NetAgent 9 DX520 NetAgent 9 DX801 To UPS To UPS Status LED Status LED To LAN LAN Port LED To LAN LAN Port LED Light signal application of NetAgent 9 Mini Status LED Light color Signal defi...

Page 17: ... with UPS Flash no connection with UPS Orange Correspondence state Light flashes when Netagent transmits command to UPS Light signal application of NetAgent 9 Mini LAN Port LED Light color Condition description Green On Internet correspond speed is 100M Flash Data transmmiting Yellow On Internet correspond speed is 10M Flash Data transmmiting ...

Page 18: ...Mate to protect your Windows operating system And also could use the UPS management software SNMPView to control and management multiple UPS on the network Fig 4 NetAgent UPS installation flowchart Setup the NetAgent IP address or update firmware by using Netility Chapter 4 The NetAgent management utility SNMPView could be used to manage multiple NetAgent Chapter 8 Using the shutdown utility Clien...

Page 19: ... 3 1 Install the NetAgent II with UPS and Network Fig 5 NetAgent II Installation 3 1 1 For External NetAgent II Connect the NetAgent II Adapter to LAN using the appropriate UTP port Connect the specified serial cable M2501 M2502 M2505 from NetAgent II Adapter to the serial port of UPS Plug supplied AC adapter to the wall socket the other side connection with NetAgent Adapter UPS with AC 3 1 2 For ...

Page 20: ... adapter to UPS outlet the DC plug connected with NetAgent Mini 3 2 2 For Internal NetAgent Mini Please make sure the connector direction of the cable is correct before connecting to the NetAgent Connect the NetAgent module to LAN using the UTP port Warning Please make sure the input Voltage and Frequency of the DC power adapter NetAgent II DC 9V NetAgent Mini DC 6V or 5 3V is correct before plug ...

Page 21: ... Netility exe After complete installation there will be a Netility group in Windows Start Program Group Fig 6 Netility Group Click Netility could initiate the Netility and enter the mail window for configuration 4 2 Using Netility The main window of Netility is here below left table is to show you all of NetAgent be searched in LAN right side is function selection menu Fig 7 Netility Main Window L...

Page 22: ...nfigure would shows the following setting page IP Address Set IP address for Netagent UPS When use at the first time please set IP address subnet mask and gateway After setting enter IP address from Telnet or Browser to connect to NetAgent s website Fig 8 Netility Configure When using DHCP or BOOTTP to set up IP address IP address Subnet Mask and Gateway would receive directly by the system Fig 8 ...

Page 23: ...o functionswere set asactivated by using port number 80 and 23 for Http and Telnet As for Https and SSH are 443 and22 2 Untick means not using the function 1 When set to the other port value full IP Address must be entered in order to login to the website or Telnet For example Set 81 as HTTP port number then http 192 168 0 177 81 must be typed at the web address to proceed to Netagent UPS s websit...

Page 24: ...etAgent Setup menu click Browser select new firmware file bin and press Start Thus Net Agent s Red LED and Yellow LED flashing alternative means the firmware is upgrading After upgrade completed Net Agent will auto reboot To upgrade multi NetAgent with same firmware hold on shift or Ctrl and choose the NetAgent device from Netility list Please connect to the http www megatec com tw for the latest ...

Page 25: ...Fig 11 Netility Update NetAgent UPS firmware About Netility version examined Fig 12 Netility version examined Refresh List Search Lan s NetagentUPS manually Netility would search all the available NetAgent from Lan automatically orthe user could search manually by click on Search NetAgent ...

Page 26: ... setting you are now able to go to NetAgent web site to monitor and control UPS by inputting NetAgent IP address in Browser Starting the Web Brower Netscape or Internet Explore Enter the NetAgent IP Address Which is setting on Netility e g 192 168 0 156 Fig 13 Input NetAgent UPS IP address On the first screen enter the current password If no password has been set just press ENTER Fig 14 NetAgent U...

Page 27: ... items in the first Web page Information Configuration Log Information Help Enter the main function item the sub menu items will be shown on the left side of the page When using this NetAgent for the first time please enter the Config menu item to set all the configuration items Then the UPS status could be correctly revealed by other pages Fig 15 NetAgent UPS single port ...

Page 28: ...erprise SNMP Agent Issued by BT Version no 6 1 Date March 2019 Page 28 of 103 Fig 16 NetAgent UPS 3 ports Fig 17 NetAgent 9 5 2 1 Information Sub Menu System Status Basic Information Current Status Remote Control ...

Page 29: ...gs from the Configuration pages System Information This section is to show NetAgent system information Values in Hardware Version Firmware Version Serial Number System Time are provided by NetAgent itself Other values are user settings from the Configuration pages Network Status This section is to show NetAgent Network settings The MAC address is provided by NetAgent All other values in this secti...

Page 30: ...us This section is to show the UPS power status The abnormal status will be displayed in red when there is a power event Input Status This section is to show the UPS input status including AC Status Input Voltage Input Frequency Values here will be shown in red when an abnormal status condition occurs Output Status This section is to show the UPS output status including Output Voltage Output Statu...

Page 31: ... Deep Battery Test This function is to execute XX minute deep battery test Test Until Battery Low When execute UPS will test Battery until battery low Cancel Test This function is to abort a test when it is executing Turn off UPS when AC failed Reboot UPS Selecting Turn off UPS when AC failed will turn off the UPS You can reboot the UPS by selecting Reboot UPS Put UPS in Sleep mode for minutes Wak...

Page 32: ... of 103 UPS Buzzer On Off This is to trigger UPS buzzer On If its ON already execute such command will set it OFF Fig 21 Remote Control 5 2 1 5 Meter Chart This page displays temperature capacity load voltage etc of the UPS by appearing with meters chart diagram Fig 22 Meter Chart ...

Page 33: ...age 33 of 103 Fig 23 NetAgent 9 Meter Chart Fig 24 NetAgent 9 Meter Chart 5 2 1 6 ModemStatus For3PortsNetAgentIIonly Modem Information This section displays the modem information GSM Modem Operating Status This section displays the operating status between NetAgent and Modem ...

Page 34: ...e set in the Configuration NetFeeler II page The status will be displayed in red when NetFeeler II detects an abnormal status condition In addition NetFeeler II will also set off an alarm for notification NetFeeler II Status This section is to show current temperature which is detected by NetFeeler II Environment Humidity This section is to show current humidity which is detected by NetFeeler II s...

Page 35: ...ity Sensors Fig 26 Environment Sensors NetFeeler II 5 2 2 Configuration Sub Menu UPS Configuration UPS On Off Schedule Network SNMP Email SMS Modem Port NetFeeler II NetSwitch Action Apply on BT Model WEB Telnet System Time Language Please set each parameter correctly so that NetAgent would operates properly Note This page s selection would differ according to the differrent interface of the UPS ...

Page 36: ...he value Date of last battery replacement yyyy mm dd This section is to record the date when the UPS battery was last replaced 5 2 3 2 UPS Recorded UPS Data Log This section is to set how often the UPS data should be logged 5 2 3 3 Test UPS Test UPS for every This section is to schedule the UPS to test once a week or once every two weeks or not to test Test UPS on Weekday This section is to set th...

Page 37: ...g messages when UPS low battery occurs Fig 27 UPS Configuration 5 2 4 UPSOn OffSchedule This page is to schedule On Off time for the UPS and Wake On Lan 5 2 4 1 Weekly Schedule This section is to set the time to turn on off the UPS each day in the week 5 2 4 2 Date Schedule This section is to set the time to turn on off the UPS on particular days Eg holidays The settings here override the settings...

Page 38: ...the PC has such function supported and configure as Enabled under BIOS Enter the IP address of that PC and system would search its IP accordingly Fig 28 UPS On Off Schedule 5 2 5 Network This page is to set NetAgent Network settings 5 2 5 1 IP Address IP Address This section is to set NetAgent IP address Subnet Mask This section is to set NetAgent Subnet Mask Gateway ...

Page 39: ...ed between NetAgent and Network NetAgent will reboot after Connection Type is changed Stop UPS communication when Ethernet disconnected This section is to set if to stop UPS communication when NetAgent disconnects with Ethernet 5 2 5 4 Dynamic DNS This is a free service that allows the user to alias a dynamic IP address to a static hostname Sevices Provider NetAgent can be configured to register w...

Page 40: ...tly using your xDSL modem Once set up NetAgent will connect directly to the Internet without going through a router The LCD will display the current WAN Public IP instead of the LAN IP Address When Connection should be made This is to set if use PPPoE to connect with NetAgent UPS Disabled Default setting Connect always NetAgent will automatically dial up and maintain continuous connection Login Na...

Page 41: ...gle is optional NetAgent 9 BX models supports wireless encryption of Open system Shared Key WEP 64 128 bit WPA WPA2 TKIP AES Following is the wireless configuration Setup was done under Lan network Click on Configuration Wireless Search AP and select the wireless SSID station and click on Select Fig 30 NetAgent 9 Wireless Click on access Point enter the encryption configuration and password then c...

Page 42: ...nd on the NetAgent Utility CD 5 2 7 1 MIB System System Name This section is to give a name to a NetAgent System Contact This section is to give a name to the administrator System Location This section is to set NetAgent location 5 2 7 2 Access Control Manager IP Address This section is to set the IP address that the administrator can manage NetAgent from It is valid for up to 8 IP addresses To ma...

Page 43: ...n is to set the IP address that the administrator can manage NetAgent from It is valid for up to 8 IP addresses To manage NetAgent from any IP address enter into Manager IP address Version This is to select between SNMPv1 SNMPv2 or SNMPv3 SNMPv3 only applies to NetAgent 9 series Community This section is to set a Community name for NMS The community name has to be as the same as the setting in NMS...

Page 44: ...g to PPC MIB or RFC1628 Severity This section is to set Trap receiver levels There are three levels of Trap receiver Information To receive all traps Warning To receive only warning and severe traps Severe To receive only severe traps Please refer to NMS manual for Trap levels Accept This section is to set to receive a trop or not Description This section is for an administrator to make notes Even...

Page 45: ... Connected This section is to set the usage power and connection status of other devices which connects to the same UPS as NetAgent uses 5 2 7 6 SNMP UDP This is to configure the UDP port of the NetAgent and trap receiver SNMP default port is 161 and Trap MIB is UDP162 Fig 34 SNMP Fig 35 NetAgent 9 SNMP ...

Page 46: ...e This section is to set an Email account name when the email server requires authentication Password This section is to set a password when the email server requires authentication Sending test mail This is to send a test mail by clicking on Test Mail to the mail address configured 5 2 8 2 Recipient s Email Address for Event Log This section is to set Email Addresses to receive warning email sent...

Page 47: ...eport every day Send email when Event Log overflows 500 records Select YES to have NetAgent send a warning email stating Event Log has reached 500 The data will now be purged to make room for new data Send email when Data Log overflows 500 records Select YES to have NetAgent send a warning email stating Data Log has reached 500 The data will now be purged to make room for new data Fig 36 Email 5 2...

Page 48: ...er SMS Server Port This section is to set the IP address of the SMSAgent or PC if selected remote service e g 192 168 0 180 and Port Number default 80 Account Name Password This section is to enter SMSAgent s account and password if configured SMSAgent webpage Configuration Web Telnet Leave blank if no such setting Receiver cellular number for Event Log This section is to set the recipient s mobil...

Page 49: ...NetAgent connects with Megatec s GSM GPRS Modem PPP Dial in When NetAgent connects with dial in modem NetSwitch When NetAgent connects with BT NetAgent 5 2 11 2 SMS Setting SMS Communication Communication Type Suitable Condition GPRS To use with GSM 900 1800 or GPRS 900 1800 1900 frequency and make sure the local telecom supports such service CDMA To use with GSM 800 900 1800 frequency and make su...

Page 50: ... environmental sensor 1 Temperature Overrun Underrun 2 Humidity Overrun Underrun 3 Water 4 Smoke 5 Gas 6 Security Door Windows 1 7 5 2 11 5 NetSwitch Setting Select NetSwitch To select the NetSwitch Address Change RPM could be daisy chain up to 16 units to control a total of 128 devices Use this to assign a new number or change the currently assigned number for the RPM unit You have a choice of 00...

Page 51: ...delay time in seconds value from 0 to 9999 Fig 39 Modem Fig 40 Modem Port with NetSwitch NetSwitch Status When BT connects with NetAgent this will appear under Information option This section allows remote control over the RPM unit and its individual devices Click on the individual power input icon to either switch on off the device ...

Page 52: ...he action per setting as to turn on or turn off on the assigned outlet Click on New to select event and set action Fig 42 NetSwitch Action 5 2 12 WEB Telnet This page is to set up the User Account in NetAgent 5 2 12 1 User Account User Name This section is to set a user name for NetAgent web pages It is valid for up to 8 users Users have to input the user name to get access to NetAgent web pages f...

Page 53: ...S Server Settings This is to configure the parameter of the radius server Please refer to the appropriate radius server setting Only for NetAgent BT CT DT series and NetAgent 9 series of BX CX DX models Enable RADIUS in Web Telnet login To select between Yes or No RADIUS Server Address To enter the IP address of the radius server Authentication Port To enter the UDP communication port number Share...

Page 54: ...ion This is to upload the SSL certificate When both public key and certificate are uploaded to NetAgent web server the communication will be encrypted by SSL on the Internet by entering with Http on the browser To communicate via Https make sure to enable Https port 443 See page 19 Fig 43 WEB Telnet Fig 44 NetAgent 9 SSL ...

Page 55: ...of 30 Time Servers If to add new time server click on Edit and delete any time server from the list provided and add a new one Time Zone Relative to GMT This section is to set a different time zone for different countries Using Daylight Saving Time Choose between Yes or No 5 2 13 2 System Time yyyy mm dd hh mm ss This section is to set NetAgent system time manually Set this in the format yyyy mm d...

Page 56: ...m NetAgent restart in about 30 seconds 5 2 13 4 Backup Time This is to save the event log and data log automatically with the configured hour on external USB flash This only applies on BX NetAgent models and the USB flash disk must be with FAT FAT32 format Time Between Log Backup To configure the time in hour to save log file Fig 46 System Time Fig 47 NetAgent 9 SystemTime ...

Page 57: ...idity NetFeeler II will send a warning message when it detects temperature or humidity values above these settings 5 2 14 2 Security Label NetFeeler II may connect up to 7 security sensors This section is to set the location of searched sensor Fig 48 NetFeeler II 5 2 15 Language This page is to set the language interface for NetAgent Interface Language This section is to set the language for NetAg...

Page 58: ...an Turkish Russian NetAgent CT DT and BT supports the following languages English Traditional Chinese Simplified Chinese Korean Japanese Russian Thai German Portuguese Spanish French Italian Turkish Russian Polish NetAgent 9 CX DX and BX suports the following languages English Traditional Chinese Simplified Chinese Korean Japanese Russian Thai German Portuguese Spanish French Italian 5 3 Log Infor...

Page 59: ...T Version no 6 1 Date March 2019 Page 59 of 103 Date Time This is a record of the Date yyyy mm dd and Time hh mm ss that the event occurred Event This is a detailed description of the event Save This is to save the event log Fig 51 Event Log ...

Page 60: ...og Date Time This is a record of the Date yyyy mm dd and Time hh mm ss that the data was recorded The interval between every log can be set in Configuration UPS configuration UPS recorded UPS data Log Input Volt This section shows records of the UPS Input voltage readings Unit Volt Output Volt This section shows records of the UPS Output voltage readings Unit Volt Freq Hz This section shows record...

Page 61: ...61 of 103 Env Humidity This section shows environmental humidity which detected by NetFeeler II Fig 53 Date Log 5 3 4 Save Data Log This function is to record RS232 UPS s voltage frequency load capacity temperature etc to save as another file for the other purpose to the manager ...

Page 62: ...ble clicking on the highlighted unit to open the webpage of such device Fig 55 Browse NetAgent Refresh This will re search all the NetAgent in the network 5 4 2 Serial Port Debug This function is to know the immediate communication between NetAgent and UPS via serial port Port Information This is to configure the communication parameter between NetAgent and UPS Parameters are Debug Mode Port Speed...

Page 63: ...ig 56 Serial ports debug 5 4 3 Help This to help to illustrate the operation of NetAgent 5 4 4 About 5 4 4 1 About This to check Netagent s Firmware Hardware version and serial number 5 4 4 2 Save Restore Settings Click Save to save the configuration to your PC The text file will have a default format of YYYY_MMDD_ cfg Administrator permission required Restore previous configuration Use this funct...

Page 64: ...ver is set as ftp icv99 com with its username password Click on Update Now NetAgent will connects to the FTP server and upgrade to the latest firmware version accordingly Auto Update This is to configure the period of time to check if any updated firmware in FTP and upgrade automatically Firmware Update When click it links to http www megatec com tw Download htm NetAgent to download the available ...

Page 65: ...o choose any utilities that provided by NetAgent to monitor and control UPS Here are introduction for using Telnet 6 2 Telnet Configuration Select Start from Windows click Run to key in NetAgent IP Address Fig 58 Telnet startup Successfullink updisplay Fig 59 Telnet Connection Initial to setup please press Enter to enter telnet main screen If the User Name and Password had been set before please e...

Page 66: ...ss Permission 6 2 4 Set SNMP Trap Notification If you want to use a PC and perform the Trap function of SNMP manager to manage UPS through Net Agent the IP address of the PC must be added in this list of Net Agent 6 2 5 Set UPS Properties This allows you to setup the Communication Type of UPS UPS Device Name and Battery Replacement Date 6 2 6 Set UPS Devices Connected This allows you to setup the ...

Page 67: ...Reboot Save the current configuration data including any changes you have made and reboot the Net Agent c Exit Without Saving Exit all configuration changes will be lost 6 3 Telnet Configuration Use Putty software to configure SSH Telnet encryption on NetAgent 9 This only apply to NetAgent 9 models of CX DX and BX Refer to page 19 to enavle SSH port of 22 Following is the configuration of SSH Teln...

Page 68: ...BT UPS Enterprise SNMP Agent Issued by BT Version no 6 1 Date March 2019 Page 68 of 103 Main Menu ...

Page 69: ... on the network When the ClientMate detects the AC Fail Battery Low Schedule Shutdown signals from the NetAgent it will save the file and shutdown the system Please check the operation description here below 7 1 Install ClientMate Put the NetAgent Utility CD into the CD driver And execute the ClientMate program After complete installation there will be a ClientMate group in the Windows Start group...

Page 70: ...etAgent 9 or UPSilon RUPS 2000 SNMP V1 V2 This is default to connect with NetAgent or NetAgent 9 SNMP V3 This only use on NetAgent 9 NetAgent 9 uses SNMP V3 protocol to connect with ClientMate When select such communication it requires to enter username password and appropriate authentication and privacy SNMP V3 configuration may refer to SNMP of the NetAgent UPSilon RUPS To connect with UPSilon o...

Page 71: ...power failure When AC failed commence computer shutdown sequence in xx Min To configure the time delay between the AC failure and the system shutdown When Battery Low commence computer shutdown sequence in xx Min To configure the time delay between the Battery Low and system shutdown When Bettery capacity reaches to X To configure to shutdown when battery capacity meets at _ Auto save application ...

Page 72: ...2 Closed Files User could review all the files closed during previous shutdown process If the Auto save application files function has been turn on in the Setting dialog the details of the closed application and files could be reviewed here Fig 65 ClientMate Closed Files 7 2 3 About Press this button could review the version information of the ClientMate as here bellowed ...

Page 73: ...g 66 ClientMate About 7 2 4 Event log Press this button could review all the network status and UPS status happened Shown as below Fig 67 ClientMate About 7 2 5 IP address of connection Status ICON Description Connecting with NetAgent UPS at IP 192 168 0 162 Does not connect to any NetAgent ...

Page 74: ...ent UPS AC power is normal The connected NetAgent UPS AC power is failed 7 2 7 Battery Status Status ICON Description The connected NetAgent UPS battery is in normal condition The connected NetAgent UPS is in battery lowcondition 7 2 8 Status History On the main menu of ClientMate the Status History showing all the network status and UPS status happened ...

Page 75: ... II or NetAgent Mini connected to a network Capable of simultaneously monitoring up to 1 000 UPS Remotely control monitor and manage the networked UPS Turn On Off Self test etc Able to simultaneously support both RS 232 Interface 1 or 3 phase and Contact Closure Interface UPS UPSconditiondisplayedineitheragraphicoranalogbarchart Supports MegaTec s SNMP Agent and SNMP Internal Card Able to send ema...

Page 76: ...me the system will ask for input the user s name and password Please enter the default value as follows to start the SNMPView User Name Admin Password blank just press Enter After the SNMPView program start up the main windows will be displayed The left panel will list the available stations by area and the right panel will list the UPS Host Name Startup Time Manager and Location of UPS found in e...

Page 77: ... delete a host into the window Group Shows the Main group windows Settings If the host is a UPS just click on it to view and modify the UPS s general information Monitor If the host is a UPS just click on it to start monitoring UPS View Display in either Large icons small icons or details Event Log Records the UPS date time and description of an event Data Log Records data of all UPS listed Option...

Page 78: ...anagement 5 4 System S 5 4 1 Event Log 5 4 2 Data Log 5 4 3 SNMP Option 5 5 User U 5 5 1 Change Password 5 5 2 AccountManagement 5 6 Help H 5 6 1 Help 5 6 2About 8 5 1 Enumerate D Start SNMPView and press the Enumerate button SNMPView will start a search for all the NetAgent on network and list them in the main window 8 5 1 1 Enumerate When press SNMPView will start a search for all the NetAgent o...

Page 79: ...of NetAgent under network 8 5 1 3 Add UPS Click Add UPS to enter the IP address of the UPS manually Once entered the UPS will be shown on the main list 8 5 1 4 Delete UPS Highlight the unit to be deleted from main list and right click on it to choose Delete or use click on the Delete icon from main function list Hold On Shift to select multi NetAgent UPS ...

Page 80: ...to be browsed and click it to enter NetAgent s webpage 8 5 1 6 Export Configuration This is to save the NetAgent UPS s configuration 8 5 1 7 Import Configuration This is to import the configuration of NetAgent UPS that saved 8 5 1 8 Open archive Event Log Open up SnmpElog dat SNMPView would show the event log of all NetAgent UPS ...

Page 81: ...P Agent Issued by BT Version no 6 1 Date March 2019 Page 81 of 103 Open up SnmpElog dat event log would show as below 8 5 1 9 Open archive Data Log Open up SnmpDlog dat SNMPView would show the event log of all NetAgent UPS ...

Page 82: ...1 Date March 2019 Page 82 of 103 Open up SnmpDlog dat data log would show as below 8 5 1 10 Quit Exit SNMPView 8 5 2 View S This is to choose the presentation format of NetAgent UPS 8 5 2 1 Large Icons Large icon view to display IP address and its location ...

Page 83: ...te March 2019 Page 83 of 103 8 5 2 2 Small Icons Small icon view to display NetAgent UPS s IP address Name location etc 8 5 2 3 Details Detailed Information displays NetAgent UPS s IP address name input voltage output voltage battery capacity load frequency etc ...

Page 84: ...re 8 5 3 1 Settings General This to configure UPS information record UPS event enable trap alarm etc Email Send email notification when event occurs Sender Display name Please enter sender display name Sender email address Please enter sender email address SMTP server address Enter SMTP address IP address or domain name Server requires authentication Click Setting then enter your Account Name and ...

Page 85: ...BT UPS Enterprise SNMP Agent Issued by BT Version no 6 1 Date March 2019 Page 85 of 103 SMS Notification Send SMS when event occurs Trap List Double click on the trap that listed and configure ...

Page 86: ... on the device listed and configure 8 5 3 2 UPS Monitor Highlight NetAgent UPS device and configure Or right click on the highlighted device and click on monitor device Meter Display NetAgent UPS information such as input voltage output voltage temperature capacity etc in diagram Digital Display NetAgent UPS information such as input voltage output voltage temperature capacity etc in digital ...

Page 87: ...BT UPS Enterprise SNMP Agent Issued by BT Version no 6 1 Date March 2019 Page 87 of 103 Details Display NetAgent UPS s IP address location user manufacturer and all other detailed information ...

Page 88: ...ription Control Turn Off UPS To shutdown UPS Reboot UPS UPS shuts down in 12 seconds and reboot in 1 minute LED Enable LED flashes UPS must supports it Cancel Shutdown To cancel UPS shutdown UPS must supports it Simulate AC Fail Simulate AC failed to UPS UPS Sleep UPS enter sleep mode Economize UPS Battery Turn off UPS load to save UPS battery capacity ...

Page 89: ...lf Test Execute UPS Self Test UPS Calibration Test Execute UPS Calibration Test Turn Off Parameters Turn Off Delay To set the buffering time for UPS before shutdown Sleep Time To set UPS sleep time Test Period Unknown This defined by UPS configuration Two weeks Perform UPS test every two weeks Weekly Perform UPS test every week Disable Do not perform UPS test 8 5 3 3 UPS Management To configure SN...

Page 90: ...3 8 5 4 System S To view event log data log and configuration 8 5 4 1 Event Log Display event log date time and description of all NetAgent UPS 8 5 4 2 Data Log Display input voltage output voltage frequency load etc of all NetAgent UPS 8 5 4 3 SNMP Option To set NetAgent UPS s parameter ...

Page 91: ...reated to manage and control its NetAgent UPS 8 5 5 1 Change Password To change existing user s password to login 8 5 5 2 User Management This only for Admin user to add edit or remote other user s info 8 5 6 Help H Display the current SNMPView version and operation information 8 5 6 1 HTML Help This to check the operation of SNMPView ...

Page 92: ...BT UPS Enterprise SNMP Agent Issued by BT Version no 6 1 Date March 2019 Page 92 of 103 8 5 6 2 About Display the current SNMPView version Copyright information and product service contact ...

Page 93: ...to upload the latest firmware into the NetAgent Please follow the instruction below to update the firmware If there is other FTP client application on your computer that will also be fine to use it for updating the firmware For example if wish to update the latest firmware of the NetAgent UPS which IP address is 192 168 50 179 then please operate with the steps below 2 1 Enter Windows then type ft...

Page 94: ...erver point User may use this method to upload the latest firmware to the remote NetAgent quit This command is to allow the user to logout with the current username account as well as close the connection of FTP For example The picture below is to upload the latest NetAgent firmware file c work netagent prjs nag 2 32 DK520 bin which is in this computer to the NetAgent UPS with IP address of 192 16...

Page 95: ...d ftp admin 192 168 50 179 3 2 ftp 192 168 50 179 when using this method to enter the follow error message will be show At this moment select Enter Identity at the top left corner of file menu Then enter admin as account name and password to re enter again Once the connection been established the following window will be display Then the user may transfer the latest firmware to here for the replac...

Page 96: ...h 2019 Page 96 of 103 10 Appendix B 3 Ports NetAgent II with SMS Modem BP506 SMS MODEM Hardware Installation A GSM MODEM B GSM MODEM Adaptor C NetAgent BP506 D GSM MODEM Cable E RS232 to RJ45 Cable 1 2 How hardware should be connected 3 Before use GSM MODEM insert SIM ...

Page 97: ...inuously there is no signal been received OR SIM card has password invalid password If such conditions happens please unplug plug the power on Modem and it shall ready SIM again If Led doesn t flash continuously once every 8 seconds then Modem is working properly BP506 Modem Configuration BP506 Modem Modem communication Type Select SMS SMS Communication Select GPRS Enter SIM Card PIN leave blank i...

Page 98: ... Page 98 of 103 5 Under Modem status of BP506 webpage it indicates the status of Modem BP506 SMSConfiguration BP506 Configuration SMS Select Local Modem Enter BP506 s username and password leave none leave blank 1 Enter Mobile number 5 Select events to send 6 Click on Apply ...

Page 99: ...rch 2019 Page 99 of 103 11 Appendix C SMS Server with SMS Modme GPRS MODEM Installation 1 Insert Sim card 2 Connect DC adaptor to GPRS modem as well serial cable provided to PC com port 2 1 2 2 2 3 NOTE Please make sure there is no conflict port with the GPRS modem ...

Page 100: ...ed by BT Version no 6 1 Date March 2019 Page 100 of 103 SMS SERVER Software Installation 1 Click on exe for installation 2 Once installed the icon would appear on the tool bar 3 Right click on the SMS server icon and check modem status ...

Page 101: ...he SMS server s IP Service Port NetAgent SMS Server port that use for local connection Service account Account authentication for sending SMS Leave blank if no such setting Service password Password authentication for sending SMS Leave blank if no such setting To send SMS when event occurs YES OR NO 3 Enter mobile number to receive event by SMS 4 Select the event that needs to be send 5 Click Appl...

Page 102: ...BT UPS Enterprise SNMP Agent Issued by BT Version no 6 1 Date March 2019 Page 102 of 103 ...

Page 103: ...Offices worldwide British Telecommunications plc 2017 Registered office 81 Newgate Street London EC1A 7AJ Registered in England No 1800000 ...