background image

Motor-driven blocking device EasyLock 

8360.0 

Installation instruction 

 

 

Page 8 

Version  

8360Err_en.doc

 

3.2  Connection  

To  connect  the  blocking  device  you  can  use  the  armed  or  not  armed  output  of  a  burglary  alarm 
center or a timely limited release signal for the entrance control applications. 
When  activating  the  input,  the  blocking  device  will  close,  when  deactivating,  the  blocking  device 
will open. 

A) 

Signal behavior and example for switching on with “0 V-activated“-“armed“signal

 

 

 

 

8360ES1.png 

8360ES2.png 

 

Illustration 3.3 – Input voltage behavior 

Illustration 3.4 - Ext. armed 0 V-active 

 
The  input  of  the  blocking  device  requires  very  little 
current – on average 3...4 µA. If the used control output 
to  activated  the  Input  voltage  may  have  a  residual 
current  of  a  view  µA  (e.g.  due  to  the  corresponding 
burglary  alarm  center  protective  circuit  –  varistors, 
transildiods,  etc)  it  may  occur  that  the  blocking  device 
will  not  correctly  react  when  changing  over  the  output 
from  “active“  to  "inactive“.  In  order  to  work  properly,  a 
pull-up  resistance  can  be  put  between  the  input  and 
+12 V. The amount of resistance shall not exceed 1 M

8360ES2a.png 

Illustration 3.5 - Ext. armed 0 V- Pull-up 

Attention:  When  using  a  pull-up  resistance  the  quiescent  current  consumption  of  the  status 

“closed”  will  increase  according  to  the  distribution  voltage  and  to  the  used  amount  of 
resistance!  
Calculation example: U = 12V, R = 100K 

 I

R

 = 120µA 

B) 

Example of switching on with “+12 V-activated”-“not armed“-signal

When  activating  the  input  via  a  p-n-p  transistor  a 
resistance  needs  to  be  put  between  the  input  and  0 V
The amount of resistance must not exceed 33 k

 
 
 
 
 

8360ES3.png 

Illustration 3.6 - Ext. fuzzy +12 V-active 

 

 

 

Summary of Contents for 108360.0

Page 1: ...8360Err_en doc Version Page 1 Installation instruction Motor driven blocking device EasyLock 108360 VdS Class C G 107 102 ...

Page 2: ... and communication of its contents is not allowed if it is not expressively allowed Any infringement obliged to compensation All rights reserved We have checked if the content of the printout complies with the described components Nonetheless we cannot exclude any deviations so that we do not take any liability for the complete compliance The information in this printout are regularly checked and ...

Page 3: ...2 Installation 5 2 1 Assembly of the blocking device 5 2 2 Assembly of the counterpart 6 2 3 Emergency opening 6 3 Switching on 7 3 1 Connection to the test device 8322 0 7 3 2 Connection 8 3 2 1 Connection of several blocking devices 9 3 3 Commissioning 9 4 Trouble shooting 9 4 1 Electrical emergency opening 10 4 2 Mechanic emergency opening 10 4 3 Sluggish bolt 10 4 4 Replacing the bolt 11 4 5 P...

Page 4: ... connection is performed using a 4 pin connecting cable Distribution voltage 12 V Distribution voltage 0 V Entry opened closed 0 V Bolt extends door locked open or 12 V Bolt moved in Exit status opened closed active 0 V with blocking bolt moved out Drive with statistic signal several blocking devices are connectable Feedback signal of the bolt position Easy installation in the door frame Only the ...

Page 5: ...ce for a cable loop behind the hole for the blocking device or in the further cable duct so that sufficient cable reserves are available to extend the blocking device for service purposes The installation direction of the flange should be selected preferably in a way that the power on the bolt will come from the fixing screws of the blocking device also refer to figure 4 1 The exact installation d...

Page 6: ...d position 5 Open the locking device by using the test device 6 Open the door 7 On the door leaf you can recognize a color circle which shows the exact position of the counterpart 8 Mark the center using a center punch and drill the hole according to the counterpart For the installation dimensions of the counterparts please refer to the technical data sheet also see chapter 6 9 Assemble the counte...

Page 7: ... extended 8360Ans png Illustration 3 1 Connection plan blocking device Inputs and outputs of the blocking device Signal Lead color Description 12 V white Tension distribution 12 V 0 V brown Tension distribution 0 V Input green Input Closed 0 V Closed open or 12 V Opened Output yellow Open drain exit active 0 V Display of the status closed 3 1 Connection to the test device 8322 0 During the commiss...

Page 8: ...esidual current of a view µA e g due to the corresponding burglary alarm center protective circuit varistors transildiods etc it may occur that the blocking device will not correctly react when changing over the output from active to inactive In order to work properly a pull up resistance can be put between the input and 12 V The amount of resistance shall not exceed 1 MΩ 8360ES2a png Illustration...

Page 9: ...must neither contact nor interlock on the counterpart The locking bolt extends without several locking trials The locking bolt can extend at full length since otherwise it would open up again after several locking trials If the functionality is incorrect then check the wiring on the basis of the signal descriptions and the examples for switching on described in chapter 3 2 4 Trouble shooting In ca...

Page 10: ...emergency opening If the electrical emergency opening options is not successful you can apply the mechanic emergency opening options Predetermine breaking point at the locking bolt The locking bolt of the blocking device possesses a predetermine breaking point which responds at a force of more than 1 kN about 100 kg at max 3 mm distance from the fixing flange Spare Locking bolts are available unde...

Page 11: ... the blocking device refer to the drawing on the right The two guiding noses on the bolt need to fit exactly to the guiding grooves of the housing After a few seconds the bolt will be moved in If you put the bolt the other way around by mistake it will automatically be ejected after a few seconds When the bolt is correctly inserted turn in a new screw cap up to the stop 8360BA2 eps Illustration 4 ...

Page 12: ...ad for min 5 sec Bolt path 12 mm Maximum distance housing flange to counterpart 8 mm for VdS Applications 3 mm Closing Opening time 0 3 s at 14 V DC operating voltage Locking force 5 N at 14 V DC operating voltage Admissible shearing force 1 0 kN at max 3 mm distance from the flange 0 5 kN at 8 mm distance from the flange Operating temperature Storage temperature range 25 C 60 C 40 C 70 C Ecologic...

Reviews: