background image

Take a minute to study the LAT Limit table. Note that the limits
are the final shutdown temperatures, but actions begin earlier.
First, at levels 1 and 2, closed dampers begin to open gradually,
followed at level 3 by staging down of multi stage equipment, if it
exists. Under most limit challenges, the system will stabilize
between 1 and 3 due to opening of closed dampers.

CAUTION:

UNIT DAMAGE HAZARD

Failure to follow this caution could result in unit damage.
Setting LAT limit too high can shorten the life of the
HVAC equipment.

Automatic Checkout

An automatic checkout procedure is provided which will exercise
dampers, heating, and cooling in that order. It is described under
the Understanding System Operation section in Installer Test
Mode
. This may be used or the system may be checked out
manually by creating thermostat calls. When using thermostats,
remember that only the calling zoning dampers will be open. This
provides the means to select which dampers are open for any
heating or cooling call. It is advisable that the initial checkout be
made with all dampers open before the bypass is set. This can be
done by temporarily setting Switch 5 to ON (disable zoning) and
controlling the equipment from the Zone 1 thermostat. When the
equipment is operating satisfactorily, return Switch 5 to OFF and
proceed to the next section.

Bypass Adjustment

The bypass should be set to the highest possible pressure setting
consistent with an acceptable air noise level. To set, operate the
system with a call from the smallest zone at its highest airflow
(highest may be either heating or cooling). This condition forces
the largest amount of air through the smallest duct, creating the
highest static pressure at the bypass. Adjust the bypass pressure
setting so that the bypass stays closed. Then check to determine if
the level of noise and

blow

in that zone is acceptable. If it is

unacceptable, reduce the bypass pressure setting (see bypass
instructions for how to adjust) until it just begins to crack open.
Check again, continuing the process until an acceptable noise and

blow

level is reached.

If, under this condition, the LAT approaches its limit, the system
will open the other closed dampers until the LAT reaches an
acceptable level. This operation is acceptable. The system will
automatically open dampers enough to keep the LAT at a safe
value, and will do it only when the zone demands require it. You
may observe the limit level on the status LED (if it is above zero).
If it stabilizes at a value of higher than 2, an overly small duct
system is indicated and it would be desirable to raise the bypass
pressure setting, if possible.

Error Codes

The status LED indicates normal operation, problems, and
LAT/HPT limit status according to a two digit code. The first digit
flashes its number, followed by a 2 second pause, followed by the
second digit, followed by a 4 second pause. The cycle the repeats.
The codes are:

TABLE 6—ERROR CODES

ON CONTINUOUSLY

NO PROBLEMS

11 - 17

LAT limit level 1 - 7

21 - 27

HPT limit level 1 - 7

31

LAT shorted

32

LAT open

33

HPT open

34

HPT shorted

41

Invalid: Sw 9=ON; Sw 10=OFF

—8—

Summary of Contents for ZONEBB3Z

Page 1: ...and location of zones This affects duct and damper selections This instruction covers the physical installation and start up of the Bryant 3 Zone system Use this instruction to guide the actual instal...

Page 2: ...he routing of wiring early to avoid possible problems later on Remember all wires converge at the Bryant 3 Zone system so its location is important III INSTALL COMPONENTS A Install Bryant 3 Zone Syste...

Page 3: ...4 Insulate damper using 1 1 2 in to 2 in insulation Check your local codes See Fig 5 NOTE All zone dampers and duct work must be properly supported according to local codes or SMACNA standards D Recta...

Page 4: ...2S Control may be used in 1 stage cooling and 1 or 2 stage heating applications For 2 stage heating the stat may be a 2 stage heat AC stat or a HP stat converted to AC Bryant HP stats can be field co...

Page 5: ...d When dampers are to move all opening is done first followed by all closing Stages In multi stage systems the equipment stage is set by the greatest thermostat call but may be delayed by the control...

Page 6: ...am of the coil but ahead of the electric heater This sensor measures the temperature of the air leaving the coil during HP heating It is not included with the control but may be ordered separately as...

Page 7: ...he changeover time effective if switch 1 is OFF ON sets 30 minutes OFF sets 20 minutes Default is OFF Dipswitch 3 This is a multiplier modifying the time set on switch 2 ON multiplies the set time by...

Page 8: ...air noise level To set operate the system with a call from the smallest zone at its highest airflow highest may be either heating or cooling This condition forces the largest amount of air through th...

Page 9: ...N COIL AIR CONDITIONER COOL LO HEAT FAN R C Y Y2 G Rz C HI HEAT R C Y1 G W1 Y2 W2 O SWITCH 9 ON SWITCH 10 ON R C Y1 G W1 Y2 W2 O R C Y G W2 C Y Fig 11 HP 2S 3 Zone Control AC Stat 1 Stg AC with 1 or 2...

Page 10: ...AN COIL LO COOL LO HEAT FAN R C G Rz C HI HEAT R C Y1 G W1 Y2 W2 O SWITCH 9 ON SWITCH 10 ON Rh Y1 G W1 Y2 W2 O R C Y1 G C Y1 Rc R Y Y2 HI COOL Y2 W2 Y2 2 SPEED AIR CONDITIONER Fig 14 HP 2S 3 Zone Cont...

Page 11: ...11...

Page 12: ...d formats and materials All include video and or slides plus companion book Classroom ServiceTraining plus hands on the products in our labs can mean increased confidence that really pays dividends in...

Reviews: