The bypass should be installed according to local codes and
SMACNA standards. Be sure bypass is properly supported.
For proper installation, refer to Installation Instructions packaged
with barometric bypass.

VI.

INSTALL LEAVING AIR TEMPERATURE (LAT) SEN-

SOR

NOTE:

The supplied LAT sensor must be installed for normal

operation. Heat pump systems may use an optional HPT (heat
pump temperature) sensor for added protection. These sensors
protect the equipment when leaving air temperatures approach
excessive levels.
Locate LAT sensor in main supply trunk after heating and cooling
coil and before bypass damper and first branch. The LAT sensor is
radiant shielded to prevent heat from affecting correct air tempera-
ture.

1. Drill a 1/4-in. hole at location in supply trunk where sensor

will be installed.

2. Insert sensor in hole and use as a template to mark the 2

mounting holes.

3. Drill two 1/16-in. holes to accept No. 6 screws through

pre-drilled holes in duct temperature sensor back plate.

4. Use 2 No. 6 sheet metal screws to mount duct temperature

sensor to unit.

5. Connect sensor to 2-conductor wire using provided wire

nuts. (See Fig. 9, 10, or 11 for connection to Bryant 3-Zone
System.)

VII.

INSTALL HEAT PUMP TEMPERATURE (HPT) SEN-

SOR

The optional HPT sensor is recommended in all heat pump/fan coil
installations. If an optional HPT sensor is not used, the 10K ohm
resistor attached to the two HPT terminals on the board must be
left in place. The HPT sensor measures the temperature of the air
leaving the indoor coil. The sensor is to be installed downstream of
the indoor coil but before the electric heaters. It can be installed
through the wall of the fan coil or may be located entirely inside
the fan coil near the blower inlet. Anchor firmly in place with cable
ties so that it cannot interfere with the blower wheel.

SYSTEM WIRING

Wiring the system is best done in four steps. Thermostats,
Equipment, Dampers, and Remainder. The descriptions below and
Table 1 will help you choose the correct wiring diagram for your

system. Table 1 also shows the proper setting of dipswitches 9 and
10 for each diagram. Based on the equipment, 3-zone control, and
thermostat type, select the appropriate wiring diagram. Terminal
designations on all the thermostats are those of Bryant thermostats.
Other brands may vary somewhat. Wiring diagrams and 3-Zone
Control board layouts are located at the end of this Installation
Instruction.

Fig. 8 - Shows the board layout for the AC Control.
Fig. 9 - Shows the board layout for the HP/2S Control.
Fig. 10 - Shows the 3-Zone AC Control wiring. It supports only 1
stage cooling and 1 stage heating.
Fig. 11 - Shows that the 3-Zone HP/2S Control may be used in 1
stage cooling and 1 or 2 stage heating applications. For 2 stage
heating, the stat may be a 2 stage heat AC stat or a HP stat
converted to AC. (Bryant HP stats can be field converted to 2 stage
heat AC stats.)
Fig. 12 - Shows the conventional HP system, using a HP stat. Only
single stage auxiliary heat is supported for heat pump systems.
Using the HP stat allows control of emergency heat directly from
the stat.
Fig. 13 - Is also a HP system, but uses an AC stat with 2 stage
heating instead of a HP stat. (Bryant HP stats can be field
converted to 2 stage heat AC stats.) Here, emergency heat can only
be selected by a switch on the 3-Zone Control.
Fig. 14 - Is a 2 speed AC system and may have 1 or 2 stages of
heat. An HP/2S Control and a 2S stat set for AC operation must be
used.
Fig. 15 - Is for a 2 speed HP. It requires an HP/2S Control and a
2S stat set for HP operation. Only single stage auxiliary heat is
supported for heat pump systems.

I.

WIRE THERMOSTATS

All zone thermostats are wired identically, so only the Zone 1
thermostat is shown on the wiring diagrams. For physical location
of connections on 3-Zone Control refer to Fig. 8 (AC Control) or
9 (HP Control).
Battery or power stealing thermostats may not require the C
connection. Refer to thermostat Installation Instructions. Be care-
ful not to cross zone numbers.

II.

WIRE EQUIPMENT

Again, from the selected Fig. 10 through 15, make each connection
as shown at the indoor and outdoor units and the 3-zone Control.
Connect the equipment R to both Rz and either Rh or Rc. A jumper
will be needed. Rc and Rh are internally connected but may be
separated by breaking a twist-off (see step 4 below).

III.

WIRE DAMPERS

Each damper has three connections: Close, Open, and Common.
Find the connection points along the lower left side of the 3-Zone
Control. Suggested colors are Close = red; Open = green; Common
= white. Field label and make the connections at the dampers and
at the 3-Zone Control. Be careful not to cross zone numbers.

IV.

WIRE REMAINDER

Connect the LAT sensor to the LAT and LATC terminals. Polarity
does not matter. If used, connect the HPT sensor to the HPT and
HPTC terminals. If the HPT sensor is not used, you must leave the
10K ohm resistor connected in its place.

Fig. 6—Rectangular Fibrous Glass Duct Work

A92480

ZONE
DAMPER

2

 TO 3

FIBROUS
GLASS
DUCTWORK

FIELD
SUPPLIED
SCREWS

Fig. 7—Insulated Rectangular Fibrous Glass

Duct Work

A95134

1  /  

 TO 2

INSULATION

1 2

TABLE 1—WIRING DIAGRAM SELECTION CHART

WIRING

DIAGRAM

EQUIPMENT

3-ZONE

TYPE

STAT
TYPE

SWITCH 9 SWITCH 10

Fig. 10

1-spd. AC,

1-Stg. heat

AC

AC

not present not present

Fig. 11

1-spd. AC,

1 or 2-stg. heat

HP/2S

AC

ON

ON

Fig. 12

1-spd. HP,

1-stg. aux heat

HP/2S

HP

OFF

OFF

Fig. 13

1-spd. HP,

1-stg. aux heat

HP/2S

AC (2 ht)

OFF

ON

Fig. 14

2-spd. AC,

1 or 2-stg. heat

HP/2S

2S (AC)

ON

ON

Fig. 15

2-spd. HP,

1-stg. aux heat

HP/2S

2S (HP)

OFF

OFF

—4—

Summary of Contents for ZONEBB3Z

Page 1: ...and location of zones This affects duct and damper selections This instruction covers the physical installation and start up of the Bryant 3 Zone system Use this instruction to guide the actual instal...

Page 2: ...he routing of wiring early to avoid possible problems later on Remember all wires converge at the Bryant 3 Zone system so its location is important III INSTALL COMPONENTS A Install Bryant 3 Zone Syste...

Page 3: ...4 Insulate damper using 1 1 2 in to 2 in insulation Check your local codes See Fig 5 NOTE All zone dampers and duct work must be properly supported according to local codes or SMACNA standards D Recta...

Page 4: ...2S Control may be used in 1 stage cooling and 1 or 2 stage heating applications For 2 stage heating the stat may be a 2 stage heat AC stat or a HP stat converted to AC Bryant HP stats can be field co...

Page 5: ...d When dampers are to move all opening is done first followed by all closing Stages In multi stage systems the equipment stage is set by the greatest thermostat call but may be delayed by the control...

Page 6: ...am of the coil but ahead of the electric heater This sensor measures the temperature of the air leaving the coil during HP heating It is not included with the control but may be ordered separately as...

Page 7: ...he changeover time effective if switch 1 is OFF ON sets 30 minutes OFF sets 20 minutes Default is OFF Dipswitch 3 This is a multiplier modifying the time set on switch 2 ON multiplies the set time by...

Page 8: ...air noise level To set operate the system with a call from the smallest zone at its highest airflow highest may be either heating or cooling This condition forces the largest amount of air through th...

Page 9: ...N COIL AIR CONDITIONER COOL LO HEAT FAN R C Y Y2 G Rz C HI HEAT R C Y1 G W1 Y2 W2 O SWITCH 9 ON SWITCH 10 ON R C Y1 G W1 Y2 W2 O R C Y G W2 C Y Fig 11 HP 2S 3 Zone Control AC Stat 1 Stg AC with 1 or 2...

Page 10: ...AN COIL LO COOL LO HEAT FAN R C G Rz C HI HEAT R C Y1 G W1 Y2 W2 O SWITCH 9 ON SWITCH 10 ON Rh Y1 G W1 Y2 W2 O R C Y1 G C Y1 Rc R Y Y2 HI COOL Y2 W2 Y2 2 SPEED AIR CONDITIONER Fig 14 HP 2S 3 Zone Cont...

Page 11: ...11...

Page 12: ...d formats and materials All include video and or slides plus companion book Classroom ServiceTraining plus hands on the products in our labs can mean increased confidence that really pays dividends in...

Reviews: