TABLE 1–ZONE CFM
MAIN & BRANCH DUCT AREA (SQ. IN.)
Equipment Capacity
2
2.5
3
3.5
4
5
6
7.5
8
8.5
10
12.5
200
Main
57**
57
57
64
64
64
Branch
66***
66
66
75
75
75
300
Main
79
79
79
79
79
87
87
Branch
99
99
99
99
99
110
110
400
Main
86
86
86
86
86
86
104
104
104
Branch
132
132
132
132
132
132
140
140
140
500
Main
113
113
113
113
113
113
113
123
123
123
123
Branch
165
165
165
165
165
165
165
179
179
179
179
600
Main
123
123
123
123
123
123
123
123
133
133
133
133
Branch
198
198
198
198
198
198
198
198
208
208
208
208
700
Main
143
143
143
143
143
143
143
143
154
154
154
Branch
231
231
231
231
231
231
231
231
246
246
246
800
Main
154
154
154
154
154
154
154
154
154
154
165
Branch
264
264
264
264
264
264
264
264
264
264
273
900
Main
165
165
165
165
165
165
165
165
165
177
Branch
297
297
297
297
297
297
297
297
297
311
1000
Main
189
189
189
189
189
189
189
189
189
201
Branch
330
330
330
330
330
330
330
330
330
330
1100
Main
201
201
201
201
201
201
201
201
201
Branch
363
363
363
363
363
363
363
363
363
1200
Main
214
214
214
214
214
214
214
214
214
Branch
396
396
396
396
396
396
396
396
396
1300
Main
227
227
227
227
227
227
227
227
Branch
429
429
429
429
429
429
429
429
1400
Main
241
241
241
241
241
241
241
241
Branch
462
462
462
462
462
462
462
462
1500
Main
254
254
254
254
254
254
254
Branch
495
495
495
495
495
495
495
1600
Main
269
269
269
269
269
269
269
Branch
528
528
528
528
528
528
528
1700
Main
284
284
284
284
284
284
Branch
561
561
561
561
561
561
1800
Main
299
299
299
299
299
299
Branch
594
594
594
594
594
594
1900
Main
314
314
314
314
314
Branch
627
627
627
627
627
2000
Main
314
314
314
314
314
Branch
660
660
660
660
660
2100
Main
330
330
330
330
Branch
693
693
693
693
2200
Main
346
346
346
346
Branch
726
726
726
726
2300
Main
363
363
Branch
759
759
2400
Main
363
363
Branch
792
792
2500
Main
380
380
Branch
825
825
Shaded areas represent less than 20 percent of total CFM, increased by one size.
*Main Duct sq in. are determined by multiplying CFM by 1.3 (200x1.3=260). Then size duct based on square inches of round pipe. Example: 260CFM.1 in. wc = 8.5” round
pipe = 57 sq in.
**Branch duct sq in. are based on 6” pipe delivering 100 CFM .1 in. wc X 1.3 = 130 CFM. Take 130 CFM .1 in. wc =6.5”pipe = 33 sq in. Example: 33 sq in. /100 CFM X
2 = 66 CFM
—21—