DUCT SIZING WORKSHEET-EXAMPLE 2
Step 1:Calculate Block Load
Heating Load:__________90,000_____ Btuh
Cooling Load:_________52,000_____ Btuh
Step 2:Room by Room Load
Room
Heating Load (Btuh)
Cooling Load (Btuh)
Airflow (CFM)*
Zone Number
Living Room_
___________
____________
______150___
_______3_____
Dining Room/Foyer
___________
____________
______150___
_______3_____
Kitchen/Dinette
___________
____________
______200___
_______4_____
Family Room_
___________
____________
______200___
_______4_____
Laundry Room
___________
____________
______300___
_______4_____
Master Bedroom/Bathroom
___________
____________
______400___
_______1_____
Bedrooms 2-4/Bathroom
___________
____________
______500___
_______2_____
____________
___________
____________
____________
_____________
____________
___________
____________
____________
_____________
____________
___________
____________
____________
_____________
____________
___________
____________
____________
_____________
____________
___________
____________
____________
_____________
____________
___________
____________
____________
_____________
____________
___________
____________
____________
_____________
____________
___________
____________
____________
_____________
____________
___________
____________
____________
_____________
*Highest CFM determined from Heat/Cool Btuh
Step 3: Zone CFM totals
Zone 1 _____400____ CFM
Zone 5 _____________CFM
Zone 2 _____500____ CFM
Zone 6 _____________CFM
Zone 3 _____300____ CFM
Zone 7 _____________CFM
Zone 4 _____700____ CFM
Zone 8 _____________CFM
Step 4: Equipment Selection
Indoor Section
____355MAV06100__
Outdoor Section
_________598B060__
Heating Capacity/CFM
____95,000/62,000__
__________1320/860__
Cooling Capacity/CFM
____53,000/34,000__
_______2,000/1,200__
Design CFM
_____1,200 (low speed A/C)
Step 5: Bypass Determination
System Design CFM *
___1,200____
X 0.60 =
_______720____
(Value MUST be less than smallest zone CFM; otherwise Bypass Damper may be required)
* Design CFM can be: Step 1C from above OR if Two Speed/Variable Speed equipment is selected, select low speed CFM value...used 2-speed A/C unit/low CFM=1200CFM
—16—