—7—

 

ACCESSORY DESCRIPTION AND USAGE (Listed Alphabetically) Continued

 

13. Secondary Outdoor Thermostat 

 

An SPDT temperature actuated switch which turns on a third stage of supplemental electric heaters when outdoor air temperature drops below the second-
stage set point. 

SUGGESTED USE: Heat pump installations where 3-stage operation of supplemental heaters is desired.

 

14. Service Alarm 

 

A current-sensing lockout relay which provides immediate notification that compressor is not operating during a call for heating or cooling. Used with proper 
room thermostat, the thermostat light is turned on signifying service is required. This can minimize electrical cost increase due to operation of supplemental 
heaters only. 

SUGGESTED USE: As a feature to notify owner immediately when the system is not operating most efficiently.

 

15. Snow Stand

 

Coated wire rack which supports unit 18 in. above mounting pad to allow for drainage from unit base.

SUGGESTED USE: Heat pump installations in heavy snowfall areas.

Heat pump installations in snowdrift locations.
Heat pump installations in areas of prolonged subfreezing temperatures.
All commercial installations.

 

16. Sound Hood

 

Wraparound sound reducing cover for the compressor. Reduces unit sound level by about 2 dBA.

SUGGESTED USE: Unit installed closer than 15 ft to quiet areas—bedrooms, etc. 

Unit installed between 2 houses less than 10 ft apart.

 

17. Support Feet 

 

Four stick-on plastic feet which raise the unit 4 in. above the mounting pad. This allows sand, dirt, and other debris to be flushed from the unit base; minimizes 
corrosion.

SUGGESTED USE: Coastal installations.

Windy areas or where debris is normally circulating.
Rooftop installations.

 

18. Thermostatic Expansion Valve (TXV)—Bi-flow

 

A modulating flow control valve which meters refrigerant liquid flow rate into the evaporator in response to the superheat of the refrigerant gas leaving the evap-
orator. Kit includes valve, adapter tubes, and external equalizer tube. 

SUGGESTED USE: Required for improved system performance. (Refer to ARI Unitary Directory.)

Required for use on all zoning systems.

 

19. Time-Delay Relay

 

An SPST delay relay which briefly continues operation of the indoor blower motor to provide additional cooling after the compressor cycles off.

SUGGESTED USE: For improved efficiency ratings for certain combinations of indoor and outdoor units. (Refer to ARI Unitary Directory.)

Summary of Contents for SPLIT-SYSTEM 697C

Page 1: ...units include a suc tion tube accumulator that minimizes the amount of liquid re frigerant that reaches the compressor a high pressure switch for high pressure protection and a low pressure switch for loss of charge protection DEFROST CONTROL BOARD Incorporates a built in 5 minute compressor time delay relay defrost relay defrost timer and low voltage terminal board The defrost control is a time t...

Page 2: ...DIA KNOCKOUT 3 8 IN DIA 9 5 TIEDOWN KNOCKOUTS 2 PLACES IN BASEPAN 10 1 2 FIELD CONTROL SUPPLY CONN 1 9 16 L C F N G A B M K E D C L DIMENSIONS IN UNIT SIZE SERIES UNIT DIMENSIONS MINIMUM MOUNTING PAD DIMENSIONS A B C D E F G H K L M Support Feet Snow Stand 018 B 33 13 16 30 33 5 1 16 9 11 16 21 15 16 28 3 8 5 8 16 13 16 20 1 2 14 26 x 32 31 x 35 024 B 33 13 16 30 33 5 1 16 9 11 16 21 15 16 28 3 8 ...

Page 3: ...8 7 8 060 1 1 8 UNIT SIZE SERIES OUTDOOR PISTON INDOOR TXV 018 B 42 KHATX0901HSO 024 B 49 KHATX1001HSO 030 B 52 KHATX1101HSO 036 B 59 KHATX1201HSO 042 B 63 KHATX1201HSO 048 A 70 KHATX1301HSO 060 A 73 KHATX1401HSO M A N U F A C T U R E R CERTIFIED TO ARI AS C O M P L Y I N G W I T H A RI STANDARD 240 U N I T A R Y HE A T P U M P EQUIPMENT CERTIFICATION APPLIES ONLY WHEN THE COMPLETE SYSTEM IS LISTE...

Page 4: ...06MPK Time Delay Relay KAATD0101TDR Interface Control KHAIC0101AAA Service Alarm KHASA0101AAA Outdoor Thermostat KHAOT0301FST Secondary Outdoor Thermostat KHAOT0201SEC Cycle Protector Standard Crankcase Heater KAACH1201AAA Start Assist PTC KAACS0201PTC Start Capacitor and Relay KSAHS1501AAA Sound Hood Standard TXV Kits Hard Shutoff KHATX0901HSO KHATX1001HSO KHATX1101HSO KHATX1201HSO TXV Kits RPB N...

Page 5: ...t 91 56 116 66 Max Branch Circuit Fuse Size Amps 50 60 Compressor Rated Load Amps 26 5 34 9 Locked Rotor Amps 129 0 169 0 Fan Motor HP and RPM 1 8 and 820 1 5 and 820 Full Load Amps 1 0 1 4 COMPRESSOR AND REFRIGERANT Compressor Scroll Refrigerant Type and Amount Lb R 22 and 11 88 R 22 and 14 88 OUTDOOR COIL AND FAN Coil Face Area Sq Ft 18 18 24 89 Rated Airflow CFM 2900 3600 OPTIONAL EQUIPMENT Sup...

Page 6: ...at Item 12 to be adjusted for economic balance point temperature SUGGESTED USE For heat pump and gas or oil fired furnace combination systems 8 Isolation Relay An SPDT relay which switches the low ambient controller out of the outdoor fan motor circuit when the heat pump switches to heating mode SUGGESTED USE All heat pumps where low ambient controller has been added 9 Liquid Solenoid Valve LSV An...

Page 7: ...ed subfreezing temperatures All commercial installations 16 Sound Hood Wraparound sound reducing cover for the compressor Reduces unit sound level by about 2 dBA SUGGESTED USE Unit installed closer than 15 ft to quiet areas bedrooms etc Unit installed between 2 houses less than 10 ft apart 17 Support Feet Four stick on plastic feet which raise the unit 4 in above the mounting pad This allows sand ...

Page 8: ...A B A024 18 000 TDR 14 00 17 000 2 98 10 800 2 28 7 00 7 70 CE3AA024 18 000 TDR 13 50 17 000 2 98 11 000 2 26 7 00 7 70 COILS 355MAV042060 VARIABLE SPEED FURNACE CC5A CD5A CD5BA024 18 500 TDR 14 00 17 000 3 08 11 000 2 32 7 20 8 00 CC5A CD5A CD5BW024 18 500 TDR 14 00 17 000 3 08 11 000 2 32 7 20 8 00 CD3 A B A024 18 500 TDR 14 00 17 000 3 08 11 000 2 32 7 20 8 00 CJ5A CK5A CK5BW024 18 000 TDR 13 8...

Page 9: ... 000 3 38 15 100 2 42 7 80 8 40 CC5A CD5A CD5BW030 24 200 TDR 13 00 24 000 3 38 15 100 2 42 7 80 8 40 CD3 A B A030 24 200 TDR 13 00 24 000 3 38 15 100 2 42 7 80 8 40 CJ5A CK5A CK5BW030 24 400 TDR 12 80 24 200 3 52 15 200 2 50 8 00 CK3BA024 23 800 TDR 12 50 24 400 3 52 15 200 2 48 8 00 CK3BA030 24 400 TDR 12 80 24 200 3 52 15 200 2 50 8 00 COILS 355MAV042060 VARIABLE SPEED FURNACE CC5A CD5A CD5BA03...

Page 10: ...2 17 800 2 44 8 00 8 50 CD5A CD5BW036 29 000 TDR 14 00 29 000 3 32 17 800 2 44 8 00 8 50 CD3 A B A036 29 000 TDR 14 00 29 000 3 32 17 800 2 44 8 00 8 50 CE3AA036 28 600 TDR 13 70 29 000 3 26 17 800 2 40 8 00 8 50 COILS 333 B J AV060120 VARIABLE SPEED FURNACE CC5A CD5A CD5BA036 28 800 TDR 13 50 29 000 3 28 18 000 2 40 8 00 8 50 CD5A CD5BW036 28 800 TDR 13 50 29 000 3 28 18 000 2 40 8 00 8 50 CD3 A ...

Page 11: ...0 CJ5A CK5A CK5BN042 33 600 None 12 00 36 000 3 32 22 400 2 42 7 70 CJ5A CK5A CK5BW036 34 200 None 12 00 36 000 3 32 22 400 2 42 7 70 CK3BA036 33 600 None 12 00 36 000 3 36 22 800 2 44 7 80 CK3BA042 34 200 None 12 00 36 000 3 36 22 800 2 44 7 80 COILS 333 B J AV036060 VARIABLE SPEED FURNACE CC5A CD5A CD5BA042 34 000 TDR 12 70 35 400 3 36 22 000 2 46 7 80 8 20 CC5A CD5A CD5BW042 34 000 TDR 12 70 35...

Page 12: ...A B 4AN F B 048 39 500 TDR 12 50 41 000 3 46 25 600 2 46 7 70 7 90 FC4BNF038 40 500 TDR TXV 12 50 41 000 3 56 25 800 2 50 7 80 8 00 FC4BN F B 042 39 000 TDR TXV 12 00 41 000 3 32 25 600 2 40 7 50 7 70 FC4BN F B 048 39 500 TDR TXV 12 50 41 000 3 46 25 600 2 46 7 70 7 90 FG3AAA048 39 000 None 12 00 41 000 3 38 25 400 2 44 7 50 7 70 FK4BNB005 41 500 TDR TXV 13 50 41 000 3 74 25 400 2 62 8 20 8 40 FK4...

Page 13: ...000 TDR 12 50 42 000 3 40 25 800 2 44 7 50 CJ5A CK5A CK5BA048 40 500 TDR 12 50 42 000 3 50 25 800 2 48 7 50 CK3BA042 40 000 TDR 12 50 42 000 3 40 25 800 2 44 7 50 CK3BA048 40 500 TDR 12 50 42 000 3 50 25 800 2 48 7 50 COILS 355MAV060100 VARIABLE SPEED FURNACE CD5A CD5BA048 39 500 TDR 13 00 41 000 3 34 25 000 2 44 7 50 CD3 A B A048 39 500 TDR 13 00 41 000 3 34 25 000 2 44 7 50 CJ5A CK5A CK5BA042 40...

Page 14: ...LS 355MAV042040 VARIABLE SPEED FURNACE CC5A CD5A CD5BA060 45 000 TDR 11 50 48 500 2 94 30 400 2 26 7 00 7 20 CD3 A B A060 45 000 TDR 11 50 48 500 2 94 30 400 2 26 7 00 7 20 CC5A CD5A CD5BW060 46 000 TDR 11 80 49 000 3 16 30 400 2 36 7 30 7 50 COILS 355MAV042060 VARIABLE SPEED FURNACE CC5A CD5A CD5BA060 45 000 TDR 11 50 48 500 2 96 30 400 2 28 7 00 7 20 CD3 A B A060 45 000 TDR 11 50 48 500 2 96 30 ...

Page 15: ...DR 11 50 61 000 2 84 38 500 2 32 7 20 7 40 CD3 A B A060 55 500 TDR 11 50 61 000 2 84 38 500 2 32 7 20 7 40 CC5A CD5A CD5BW060 57 000 TDR 12 00 61 000 3 04 39 000 2 44 7 80 8 00 CE3AA060 57 500 TDR 12 00 61 000 3 02 39 000 2 42 7 80 8 00 CJ5A CK5A CK5BA060 57 500 TDR 12 00 61 000 2 94 38 500 2 40 7 50 CJ5A CK5A CK5BX060 58 500 TDR 12 20 61 000 3 12 38 500 2 48 7 80 CK3BA060 57 500 TDR 12 00 61 000 ...

Page 16: ...8 756 OUTDOOR TEMPERATURE F 10 0 10 20 30 40 50 60 70 80 2 9 5 9 8 8 11 7 14 7 17 6 20 5 70 60 50 40 30 20 10 KW BASED ON INDOOR ENT AIR AT 70 F AND AT RATED CFM 23 4 80 697CN024 A B FC4BNF030 697CN030 A B FC4BNF036 697CN036 A B FC4BN F B 042 697CN042 A B FK4CNF005 697CN048 A FK4CNF005 697CN060 A FK4CNB006 697CN018 B FC4BNF024 A95490 ...

Page 17: ... 51 18 1 14 2 1 68 17 3 13 9 1 8 16 3 13 5 2 08 15 4 13 1 2 31 63 18 5 14 4 1 35 17 7 14 0 1 50 16 9 13 7 1 68 16 0 13 3 1 8 15 2 13 0 2 08 14 3 12 6 2 31 62 18 4 18 0 1 35 17 6 17 6 1 51 16 9 16 9 1 68 16 3 16 3 1 8 15 5 15 5 2 08 14 8 14 8 2 31 57 18 2 18 2 1 35 17 6 17 6 1 51 16 9 16 9 1 68 16 3 16 3 1 8 15 5 15 5 2 08 14 8 14 8 2 31 Multipliers for Determining the Performance With Other Indoor...

Page 18: ...apacity Power Capacity Power FC4BNF 024 0 98 1 01 COILS 333 B J AV048080 VARIABLE SPEED FURNACE 030 1 00 1 00 CC5A CD5A CD5BA 030 0 99 0 92 033 1 02 1 01 CC5A CD5A CD5BW 030 0 99 0 92 F A B 4AN F C 024 0 98 1 01 CD3 A B A 030 0 99 0 92 030 1 00 1 00 CE3AA 030 1 00 0 93 FD3ANA 024 0 97 0 99 COILS 333 B J AV060100 VARIABLE SPEED FURNACE 030 1 00 1 02 CC5A CD5A CD5BA 030 0 99 0 91 FF1 A B NA 024 0 98...

Page 19: ... 0 91 F A B 4ANF 030 0 99 0 98 CJ5A CK5A CK5BW 030 0 99 0 92 036 1 00 1 00 CK3BA 030 0 99 0 92 FD3ANA 030 0 99 0 99 COILS 333 B J AV060100 VARIABLE SPEED FURNACE FF1 A B NA 030 0 99 0 99 CC5A CD5A CD5BA 036 1 02 0 90 FG3AAA 036 0 99 0 98 CD5A CD5BW 036 1 02 0 90 FK4BNF 001 1 02 0 94 CD3 A B A 036 1 02 0 90 002 1 03 0 94 CE3AA 036 1 01 0 90 003 1 04 0 92 COILS 333 B J AV060120 VARIABLE SPEED FURNAC...

Page 20: ... 20 3 2 91 25 6 19 7 3 17 63 27 7 20 7 2 43 26 4 20 2 2 65 25 2 19 7 2 89 23 8 19 1 3 15 62 27 3 25 9 2 43 26 2 25 3 2 64 25 1 24 7 2 89 23 8 23 8 3 15 57 26 8 26 8 2 43 25 9 25 9 2 64 24 9 24 9 2 89 23 8 23 8 3 15 1050 72 32 9 17 2 2 52 31 5 16 7 2 74 30 0 16 1 2 98 28 1 15 5 3 25 67 30 0 22 4 2 49 28 7 21 8 2 71 27 4 21 3 2 95 25 9 20 7 3 22 63 27 9 21 6 2 48 26 6 21 1 2 69 25 4 20 6 2 93 24 1 2...

Page 21: ...42 1 01 0 96 F A B 4AN F B 042 1 00 1 00 CJ5A CK5A CK5BW 036 1 00 0 93 FG3AAA 036 0 98 0 99 CK3BA 036 1 00 0 93 FK4BNF 001 0 99 0 97 042 1 01 0 96 002 0 99 0 98 COILS 333 B J AV060100 VARIABLE SPEED FURNACE 003 1 02 0 94 CC5A CD5A CD5BA 042 1 00 0 91 004 1 01 0 96 CC5A CD5A CD5BW 042 1 00 0 91 FK4CNF 001 0 98 0 94 CD3 A B A 042 1 00 0 91 002 0 98 0 94 CC5A CD5A CD5BC 048 0 99 0 90 003 1 01 0 91 CE...

Page 22: ...3 04 31 8 31 6 3 33 30 4 30 4 3 64 29 0 29 0 4 00 57 32 9 32 9 3 03 31 8 31 8 3 33 30 4 30 4 3 64 28 9 28 9 3 99 1300 72 39 1 21 0 3 13 37 5 20 4 3 43 35 5 19 7 3 75 33 5 19 0 4 10 67 36 1 27 7 3 10 34 4 27 1 3 39 32 8 26 4 3 73 30 9 25 7 4 07 63 33 7 26 9 3 08 32 1 26 2 3 37 30 6 25 5 3 69 28 8 24 7 4 04 62 33 7 33 5 3 08 32 3 32 3 3 37 30 9 30 9 3 69 29 5 29 5 4 05 57 33 7 33 7 3 08 32 3 32 3 3 ...

Page 23: ... 1 00 FC4BNF 038 0 99 1 09 COILS 333 B J AV060100 VARIABLE SPEED FURNACE FG3AAA 048 0 95 1 06 CC5A CD5A CD5BC 048 0 95 1 00 FK4BNB 003 0 96 1 03 CC5A CD5A CD5BW 048 0 95 0 99 FK4BNF 005 1 01 1 05 CD3 A B A 048 0 95 0 99 FK4CNF 003 0 96 1 00 CD5A CD5BA 048 0 95 0 99 005 1 00 1 00 CE3AA 048 0 96 1 00 CC5A CD5A CD5BA 042 0 95 1 06 CJ5A CK5A CK5BA 042 0 96 0 98 043 0 95 1 06 CJ5A CK5A CK5BW 048 0 98 0...

Page 24: ...9 2 29 4 3 7 37 5 28 7 4 17 63 40 3 30 1 3 03 38 6 29 4 3 37 37 0 28 7 3 7 34 8 27 7 4 13 62 40 0 37 6 3 03 38 2 36 7 3 36 36 4 35 7 3 7 34 6 34 6 4 13 57 39 0 39 0 3 02 37 7 37 7 3 36 36 4 36 4 3 7 34 6 34 6 4 13 1409 72 47 4 25 4 3 13 45 1 24 7 3 47 43 1 24 0 3 8 41 1 23 3 4 26 67 43 7 33 1 3 10 41 9 32 4 3 44 39 8 31 6 3 8 37 9 30 8 4 21 63 40 9 32 2 3 07 39 3 31 4 3 41 37 5 30 7 3 7 35 3 29 7 ...

Page 25: ...ILS 333 B J AV060120 VARIABLE SPEED FURNACE 070 1 00 1 06 CC5A CD5A CD5BA 060 0 96 0 99 FG3AAA 048 0 95 1 04 CC5A CD5A CD5BW 060 0 98 0 99 060 0 97 1 04 CD3 A B A 060 0 96 0 99 FK4BNB 006 1 01 1 00 CE3AA 060 0 98 1 00 FK4CNB 006 1 01 0 98 CJ5A CK5A CK5BA 060 0 97 1 00 FK4CNF 005 1 00 1 00 CJ5A CK5A CK5BW 048 0 96 1 00 CC5A CD5A CD5BA 060 0 95 1 04 CJ5A CK5A CK5BX 060 0 99 0 99 CC5A CD5A CD5BC 048 ...

Page 26: ...60 8 31 7 6 0 57 5 30 5 6 69 67 61 8 43 4 4 89 59 0 42 3 5 41 56 1 41 2 5 9 53 0 39 9 6 61 63 57 9 42 4 4 84 55 3 41 2 5 36 52 6 40 0 5 9 49 7 38 8 6 54 62 57 1 52 7 4 83 54 5 51 5 5 35 51 9 50 1 5 9 49 2 48 7 6 53 57 55 7 55 7 4 81 53 6 53 6 5 34 51 4 51 4 5 9 49 0 49 0 6 53 2012 72 67 8 35 6 5 05 64 7 34 5 5 58 61 5 33 3 6 1 58 0 32 2 6 79 67 63 1 46 5 4 99 60 2 45 4 5 52 56 8 44 0 6 0 53 6 42 8...

Page 27: ...0 1 41 9 19 8 45 1 46 10 9 9 93 1 51 12 8 11 3 1 5 14 9 13 6 1 63 17 3 17 3 1 72 19 9 19 9 1 84 22 9 22 9 2 0 700 7 68 7 07 1 42 9 26 8 51 1 47 11 0 10 0 1 51 12 8 11 4 1 5 15 0 13 6 1 63 17 4 17 4 1 72 20 0 20 0 1 84 23 0 23 0 2 0 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Heating Indoor Section Size Heating Capacity Power Capacity Power FC4BNF 024 ...

Page 28: ...BLE SPEED FURNACE 030 1 00 1 00 CC5A CD5A CD5BA 030 0 96 1 00 033 1 00 0 97 CC5A CD5A CD5BW 030 0 96 1 00 F A B 4AN F C 024 1 00 1 02 CD3 A B A 030 0 96 1 00 030 1 00 1 00 CE3AA 030 0 96 0 95 FD3ANA 024 1 00 1 06 COILS 333 B J AV060100 VARIABLE SPEED FURNACE 030 1 00 1 01 CC5A CD5A CD5BA 030 0 96 0 99 FF1 A B NA 024 1 00 1 01 CC5A CD5A CD5BW 030 0 96 0 99 030 1 00 0 99 CD3 A B A 030 0 96 0 99 FG3A...

Page 29: ... CC5A CD5A CD5BA 036 0 97 0 93 FD3ANA 030 1 00 1 01 CD5A CD5BW 036 0 97 0 93 FF1 A B NA 030 1 00 0 99 CD3 A B A 036 0 97 0 93 FG3AAA 036 1 00 1 01 CE3AA 036 0 97 0 95 FK4BNF 001 1 00 0 96 COILS 355MAV042040 VARIABLE SPEED FURNACE 002 1 00 0 92 CC5A CD5A CD5BA 036 1 00 0 95 003 0 99 0 91 CD5A CD5BW 036 1 00 0 95 004 1 00 0 88 CD3 A B A 036 1 00 0 95 FK4CNF 001 0 99 0 94 CJ5A CK5A CK5BW 030 0 98 0 9...

Page 30: ...B 4AN F B 042 1 00 1 00 CC5A CD5A CD5BA 042 0 98 0 95 FG3AAA 036 1 00 1 03 CC5A CD5A CD5BW 042 0 98 0 95 FK4BNF 001 1 00 1 00 CD3 A B A 042 0 98 0 95 002 1 00 0 97 CC5A CD5A CD5BC 048 0 97 0 97 003 0 99 0 94 CE3AA 042 0 98 0 94 004 1 00 0 92 CJ5A CK5A CK5BA 042 0 99 0 94 FK4CNF 001 0 98 0 99 CJ5A CK5A CK5BW 036 0 98 0 94 002 0 99 0 97 CK3BA 036 0 98 0 94 003 0 98 0 94 042 0 99 0 94 CD5A CD5BW 036 ...

Page 31: ... 30 9 28 1 3 00 35 7 35 7 3 17 41 3 41 3 3 37 1200 15 9 14 6 2 55 19 2 17 7 2 66 22 8 20 8 2 76 26 7 23 7 2 87 31 1 28 3 3 00 36 0 36 0 3 16 41 6 41 6 3 36 1300 16 1 14 8 2 57 19 4 17 8 2 68 23 0 20 9 2 78 26 9 23 9 2 88 31 3 28 5 3 01 36 2 36 2 3 16 41 9 41 9 3 35 75 1100 15 4 14 1 2 62 18 9 17 3 2 74 22 4 20 4 2 87 26 2 23 3 2 99 30 6 27 8 3 14 35 4 35 4 3 31 40 9 40 9 3 52 1200 15 6 14 3 2 64 1...

Page 32: ...FG3AAA 048 1 00 1 10 CJ5A CK5A CK5BW 048 1 00 1 05 FK4BNB 003 1 00 1 08 CK3BA 042 0 98 1 04 FK4BNF 005 1 00 0 99 048 1 00 1 05 FK4CNF 003 0 98 1 06 COILS 333 B J AV060120 VARIABLE SPEED FURNACE 005 1 00 1 00 CC5A CD5A CD5BC 048 0 98 1 10 CC5A CD5A CD5BA 042 1 00 1 12 CC5A CD5A CD5BW 048 0 98 1 10 043 1 00 1 12 CD3 A B A 048 0 98 1 10 CC5A CD5A CD5BC 048 1 00 1 15 CD5A CD5BA 048 0 98 1 10 CC5A CD5A...

Page 33: ...10 CK3BA 048 0 98 1 09 060 1 03 1 08 060 0 98 1 08 FC4BNB 054 1 03 1 01 COILS 333 B J AV060120 VARIABLE SPEED FURNACE 070 1 03 1 03 CC5A CD5A CD5BA 060 0 98 1 10 FG3AAA 048 1 01 1 12 CC5A CD5A CD5BW 060 1 00 1 05 060 1 01 1 10 CD3 A B A 060 0 98 1 10 FK4BNB 006 1 01 0 96 CE3AA 060 1 00 1 05 FK4CNB 006 1 01 0 97 CJ5A CK5A CK5BA 060 0 98 1 08 FK4CNF 005 1 00 1 00 CJ5A CK5A CK5BW 048 0 98 1 10 CC5A C...

Page 34: ...61 0 61 0 5 38 71 6 71 6 5 91 2012 28 3 26 0 4 02 33 5 30 8 4 21 39 4 35 9 4 42 45 6 40 5 4 6 53 1 48 3 4 95 61 6 61 6 5 32 71 5 71 5 5 84 75 1575 27 4 25 2 4 16 32 6 30 0 4 41 38 3 35 0 4 67 44 4 39 4 4 9 51 6 47 0 5 29 59 8 59 8 5 72 69 3 69 3 6 27 1750 27 6 25 4 4 16 32 9 30 2 4 40 38 6 35 2 4 64 44 7 39 7 4 9 52 0 47 3 5 23 60 3 60 3 5 64 70 0 70 0 6 17 2012 28 0 25 7 4 19 33 2 30 5 4 41 39 0 ...

Page 35: ...ntal planes 7 Maximum elevation of indoor coil above or below base of outdoor unit is indoor coil above 50 ft indoor coil below 150 ft See items 8 and 9 following 8 For interconnecting refrigerant tube lengths greater than 50 ft consult Long Line Application Guideline available from equipment distributor 9 Not more than 36 in of refrigerant tube should be buried in the ground If necessary to bury ...

Page 36: ...cussed in this manual including Unit Familiarization Maintenance Installation Overview Operating Sequence A large selection of product theory and skills programs is available using popular video based formats and materials All include video and or slides plus companion book Classroom Service Training plus hands on the products in our labs can mean increased confidence that really pays dividends in...

Reviews: