17
COMBINATION RATINGS CONTINUED
Unit Size
--- Series
Indoor Model
Cooling
Capacity
ARI Standard Ratings
Cooling
Heating
Furnace Model
Factory
Enhance
Standard
Rating
SEER
TDR
EER
High Temp
Low Temp
HSPF
E
Capacity
E
COP
H
Capacity
H
COP
048--B
CSPH*4812A**
47,000
TDR&TXV
14.00
12.00
47,000
3.66
29,800
2.54
8.2
315(A,J)AV048090
CSPH*4812A**
47,000
TDR&TXV
14.50
12.00
47,000
3.66
29,800
2.54
8.2
315(A,J)AV060110
CSPH*4812A**
47,500
TDR&TXV
14.50
12.00
47,000
3.70
29,600
2.56
8.2
315(A,J)AV066135
CSPH*4812A**
47,500
TDR&TXV
15.00
12.50
47,000
3.72
29,600
2.58
8.2
315(A,J)AV066155
CSPH*4812A**
47,000
TDR&TXV
14.00
12.00
47,000
3.62
29,800
2.52
8.2
355AAV060080
CSPH*4812A**
47,000
TDR&TXV
14.50
12.00
47,000
3.64
29,800
2.52
8.2
355AAV060100
CSPH*4812A**
47,000
TDR&TXV
14.50
12.00
47,000
3.64
29,800
2.54
8.2
355AAV060120
CSPH*4812A**
48,000
TXV
14.00
11.50
48,500
3.72
30,600
2.54
8.3
CSPH*6012A**
48,000
TDR&TXV
14.50
12.00
47,000
3.72
29,800
2.58
8.2
315(A,J)AV048090
CSPH*6012A**
48,000
TDR&TXV
14.50
12.00
47,000
3.74
29,600
2.58
8.3
315(A,J)AV060110
CSPH*6012A**
48,000
TDR&TXV
15.00
12.50
47,000
3.78
29,600
2.60
8.3
315(A,J)AV066135
CSPH*6012A**
48,000
TDR&TXV
15.00
12.50
47,000
3.80
29,400
2.62
8.4
315(A,J)AV066155
CSPH*6012A**
48,000
TDR&TXV
14.50
12.00
47,000
3.70
29,800
2.56
8.2
355AAV060080
CSPH*6012A**
48,000
TDR&TXV
14.50
12.00
47,000
3.72
29,800
2.56
8.2
355AAV060100
CSPH*6012A**
48,000
TDR&TXV
14.50
12.00
47,000
3.70
29,800
2.56
8.2
355AAV060120
CSPH*6012A**
48,000
TXV
14.00
12.00
48,500
3.78
30,800
2.56
8.3
060--B
*FX4CN(B,F)060
60,000
TDR&TXV
14.00
11.50
59,500
3.70
37,000
2.60
8.4
FE4ANB006
59,500
TDR&TXV
14.00
11.50
59,000
3.68
36,000
2.62
8.3
FV4BNB006
59,500
TDR&TXV
14.00
11.50
59,000
3.68
36,000
2.62
8.3
FY4ANB060
59,500
TDR&TXV
13.00
10.80
60,000
3.56
37,800
2.50
8.0
CAP**6021A**
58,000
TDR&TXV
13.50
11.20
59,000
3.52
36,400
2.52
8.0
315(A,J)AV060110
CAP**6021A**
58,000
TXV
13.50
11.20
59,000
3.52
36,600
2.52
7.9
CAP**6024A**
58,500
TDR&TXV
13.50
11.20
59,000
3.54
36,200
2.54
8.0
315(A,J)AV066135
CAP**6024A**
59,000
TDR&TXV
13.50
11.20
58,500
3.58
36,000
2.56
8.0
315(A,J)AV066155
CAP**6024A**
59,000
TXV
13.20
11.00
60,000
3.58
37,200
2.54
8.0
CNPH*6024A**
58,500
TDR&TXV
13.50
11.20
58,500
3.48
36,200
2.52
7.9
315(A,J)AV060110
CNPH*6024A**
58,500
TDR&TXV
13.50
11.20
59,000
3.52
36,000
2.54
7.9
315(A,J)AV066135
CNPH*6024A**
58,500
TDR&TXV
13.50
11.20
59,000
3.54
36,000
2.56
8.0
315(A,J)AV066155
CNPH*6024A**
59,000
TXV
13.20
11.00
60,000
3.58
37,000
2.54
8.0
CNPV*6024A**
58,500
TDR&TXV
13.50
11.20
59,000
3.52
36,000
2.54
7.9
315(A,J)AV066135
CNPV*6024A**
58,500
TDR&TXV
13.50
11.20
59,000
3.54
36,000
2.56
8.0
315(A,J)AV066155
CNPV*6024A**
59,000
TXV
13.20
11.00
60,000
3.58
37,000
2.54
8.0
CSPH*6012A**
58,500
TDR&TXV
13.50
11.20
58,500
3.58
36,400
2.54
8.0
315(A,J)AV060110
CSPH*6012A**
58,500
TDR&TXV
13.50
11.20
58,500
3.60
36,000
2.56
8.0
315(A,J)AV066135
CSPH*6012A**
59,000
TDR&TXV
13.50
11.20
58,500
3.64
36,000
2.58
8.0
315(A,J)AV066155
CSPH*6012A**
58,500
TXV
13.20
11.00
60,000
3.64
37,200
2.56
8.0
* Ratings are net values reflecting the effects of circulating fan heat. Supplemental electric heat is not included. Ratings are based on:
Cooling Standard:
80
_
F (27
_
C) db 67
_
F (19
_
C) wb indoor entering air temperature and 95
_
F (35
_
C) db air entering outdoor unit.
High---Temp Heating Standard:
70
_
F (21
_
C) db indoor entering air temperature and 47
_
F (8
_
C) db 43
˚
F (6
_
C) wb air entering outdoor unit.
Low---Temp Heating Standard:
70
_
F (21
_
C) db indoor entering air temperature and 17
_
F (
±
9
_
C) db 15
˚
F (
±
10
_
C) wb air entering outdoor unit.
SEER
— Seasonal Energy Efficiency Ratio
COP
— Coefficient of Performance
TDR
— Time---Delay Relay
HSPF
— Heating Seasonal Performance Factor
EER
— Energy Efficiency Ratio
265A
Summary of Contents for PREFERRED 265A