A08015
DETAIL A
(914 mm)
A08487
SMALL CABINET
LARGE CABINET
Unit*
024
024
030
030
036
036
Unit*
042
042
048
048
060
060
lb
kg
lb
kg
lb
kg
lb
kg
lb
kg
lb
kg
Rigging
Weight
260
118
265
120
271
123
Rigging
Weight
356
161
362
164
376
171
* For 460 volt units, add 14 lb (6.35 kg) to the rigging weight.
NOTE: See dimensional drawing for corner weighs.
Fig. 5 -- 704D Unit Suggested Rigging
A
B
C
MAXIMUM ALLOWABLE
DIFFERENCE in. (mm)
A-C
1/4
1/4
1/4
(6.35)
(6.35)
(6.35)
A-B
B-C
A07925
Fig. 6 -- Unit Leveling Tolerances
UNIT FALLING HAZARD
Failure to follow this warning could result in personal
injury or death.
Never stand beneath rigged units or lift over people.
!
WARNING
PROPERTY DAMAGE HAZARD
Failure to follow this warning could result in personal
injury/death or property damage.
Rigging brackets for one unit use only.
When removing a
unit at the end of its useful life, use a new set of brackets.
!
WARNING
USE OF RIGGING BRACKET
Field Installation of Rigging Bracket (if not already
installed)
1. Remove unit from shipping carton. Leave top shipping skid
on the unit for use as a spreader bar to prevent the rigging
straps from damaging the unit. If the skid is not available,
use a spreader bar of sufficient length to protect the unit
from damage.
2. Remove 4 screws in unit corner posts.
3. Attach each of the 4 metal rigging brackets under the panel
rain lip (See Fig. 5). Use the screws removed in step 2
above to secure the brackets to the unit.
PROPERTY DAMAGE HAZARD
Failure to follow this warning could result in personal
injury/death or property damage.
Rigging bracket MUST be under the rain lip to provide
adequate lifting.
!
WARNING
PROPERTY DAMAGE HAZARD
Failure to follow this warning could result in personal
injury/death or property damage.
Do not strip screws when re--securing the unit. If a screw is
stripped, replace the stripped one with a larger diameter screw
(included). When straps are taut, the clevis should be a
minimum of 36 in. (914.4 mm) above the unit top cover.
!
WARNING
Rigging/Lifting of Unit
1. Bend top of brackets down approximately 30 degrees from
the corner posts.
2. Attach straps of equal length to the rigging brackets at
opposite ends of the unit. Be sure straps are rated to hold the
weight of the unit (See Fig. 5).
3. Attach a clevis of sufficient strength in the middle of the
straps. Adjust the clevis location to ensure unit is lifted level
with the ground.
704D
Summary of Contents for LEGACY PURON 704D Series
Page 3: ...3 A08584 Fig 2 704D024 036 Unit Dimensions 704D ...
Page 4: ...4 A08585 Fig 3 704D042 060 Unit Dimensions 704D ...
Page 14: ...14 A08050 Fig 13 Wiring Diagram 208 230 1 60 704D ...
Page 15: ...15 A08051 Fig 14 Wiring Diagram 208 230 3 60 704D ...
Page 16: ...16 A08007 Fig 15 Wiring Diagram 460 3 60 704D ...
Page 17: ...17 A08490 Fig 16 Cooling Charging Chart 704D ...