5
Gask et around
outer edge
Insulated
deck
pan
Gask et around
duct
S/A
R/A
HVAC
unit
base
*Gask eting
outer flange
Flashing field
supplied
Roofing material
field supplied
Cant str ip
field supplied
*Provided with roof curb
Roof
Ductwork
field supplied
Insulation (field
supplied)
Roof curb*
Wood nailer*
Gask eting
inner flange*
Scre w
(NO TE A)
Roof Curb for Small Cabinet
Note A: When unit mounting scre w is used,
retainer bra cke t must also be used.
HVAC unit
base
*Gask eting
outer flange
Flashing field
supplied
Roofing material
field supplied
Cant str ip
field supplied
*Provided with roof curb
Roof
Ductwork
field supplied
Insulation (field
supplied)
Roof curb*
Wood nailer*
Gask eting
inner flange*
Scre w
(NOTE A)
Roof Curb for
Large Cabinet
Note A: When unit mounting scre w is used,
retainer bra cket
must also be used.
A
B Typ.
Supply opening
(B x C)
Long
Support
D
F
Return opening
(B X C)
Insulated
deck pan
Short
Support
C Typ.
G
E
F
G
D
E
A05308
UNIT SIZE
CATALOG
NUMBER
A
IN. (MM)
B
IN. (MM)
C
IN. (MM)
D
IN. (MM)
E
IN. (MM)
F
IN. (MM)
G
IN. (MM)
704D024--036
CPRFCURB006A00
8 (203)
11 (279)
16--1/2 (419)
28--3/4 (730)
30--3/8 (771)
44--5/16 (1126)
45--15/16 (1167)
CPRFCURB007A00
14 (356)
11 (279)
16--1/2 (419)
28--3/4 (730)
30--3/8 (771)
44--5/16 (1126)
45--15/16 (1167)
704D042--060
CPRFCURB008A00
8 (203)
16--3/16 (411)
17--3/8 (441)
40--1/4 (1022) 41--15/16 (1065)
44--7/16 (1129)
46--1/16 (1169)
CPRFCURB009A00
14 (356) 16--3/16 (411)
17--3/8 (441)
40--1/4 (1022) 41--15/16 (1065)
44--7/16 (1129)
46--1/16 (1169)
NOTES:
1. Roof curb must be set up for unit being installed.
2. Seal strip must be applied, as required, to unit being installed.
3. Roof curb is made of 16--gauge steel.
4. Attach ductwork to curb (flanges of duct rest on curb).
5. Insulated panels: 1--in. (25.4 mm) thick fiberglass 1 lb. density.
6. When unit mounting screw is used (see Note A), a retainer bracket must be used as well. This bracket must also be used when required by code for hurricane or seismic
conditions. This bracket is available through Micrometl.
Fig. 4 -- Roof Curb Dimensions
704D
Summary of Contents for LEGACY PURON 704D Series
Page 3: ...3 A08584 Fig 2 704D024 036 Unit Dimensions 704D ...
Page 4: ...4 A08585 Fig 3 704D042 060 Unit Dimensions 704D ...
Page 14: ...14 A08050 Fig 13 Wiring Diagram 208 230 1 60 704D ...
Page 15: ...15 A08051 Fig 14 Wiring Diagram 208 230 3 60 704D ...
Page 16: ...16 A08007 Fig 15 Wiring Diagram 460 3 60 704D ...
Page 17: ...17 A08490 Fig 16 Cooling Charging Chart 704D ...