Outdoor Fan
UNIT OPERATION HAZARD
Failure to follow this caution may result in damage to unit
components.
Keep the outdoor fan free from all obstructions to ensure
proper cooling operation. Never place articles on top of the
unit.
CAUTION
!
1. Remove 6 screws holding outdoor grille and motor to top
cover.
2. Turn motor/grille assembly upside down on top cover to
expose the fan blade.
3. Inspect the fan blades for cracks or bends.
4. If fan needs to be removed, loosen the setscrew and slide the
fan off the motor shaft.
5. When replacing fan blade, position blade back to the same
position as before.
6. Ensure that setscrew engages the flat area on the motor shaft
when tightening.
7. Replace grille.
Electrical Controls and Wiring
Inspect and check the electrical controls and wiring annually. Be
sure to turn off the gas supply, and then the electrical power to the
unit.
Remove access panels (see Fig. 18) to locate all the electrical
controls and wiring. Check all electrical connections for tightness.
Tighten all screw connections. If any discolored or burned
connections are noticed, disassemble the connection, clean all the
parts, re--strip the wire end and reassemble the connection properly
and securely.
After inspecting the electrical controls and wiring, replace the
access panels (see Fig. 18). Start the unit, and observe at least one
complete heating cycle and one complete cooling cycle to ensure
proper operation. If discrepancies are observed in any operating
cycle, or if a suspected malfunction has occurred, check each
electrical component with the proper electrical instrumentation.
Refer to the unit wiring label when making these checkouts.
NOTE
: Refer to the heating and/or cooling sequence of operation
in this publication as an aid in determining proper control
operation.
Refrigerant Circuit
Annually inspect all refrigerant tubing connections and the unit
base for oil accumulations. Detecting oil generally indicates a
refrigerant leak.
674D
--
--
A
Summary of Contents for Legacy 674D
Page 3: ...3 A09473 Fig 2 674D A24 36 Unit Dimensions 674D A...
Page 4: ...4 A09474 Fig 3 674D A42 60 Unit Dimensions 674D A...
Page 24: ...24 A10207C Fig 14 208 230 1 60 Connection Wiring Diagram Unit 674D 674D A...
Page 25: ...25 A10207L Fig 14 Cont 208 230 1 60 Ladder Wiring Diagram Unit 674D A 674D A...
Page 26: ...26 A10208C Fig 15 208 230 3 60 Connection Wiring Diagram Unit 674D A 674D A...
Page 27: ...27 A10208L Fig 15 Cont 208 230 3 60 Ladder Wiring Diagram Unit 674D A 674D A...
Page 28: ...28 A08019 Fig 16 Cooling Charging Table Subcooling 674D A...
Page 49: ...49 A10059 Fig 49 Economizer Wiring Diagram 674D A...