START-UP CHECKLIST — 580J 17-30 SINGLE PACKAGE ROOFTOP WITH
HEAT/ELECTRIC COOLING WITH PURON
®
(R-410A) REFRIGERANT
I. PRELIMINARY INFORMATION
MODEL NO. ___________________________________
JOB NAME ____________________________________
SERIAL NO. __________________________________
ADDRESS ____________________________________
START-UP DATE_______________________________
TECHNICIAN NAME ____________________________
ADDITIONAL ACCESSORIES
_____________________________________________________________________________________________________
II. PRE-START-UP
Verify that job site voltage agrees with voltage listed on rating plate (Y/N) _____
Verify that all packaging materials have been removed from unit (Y/N) _____
Remove all shipping hold down bolts and brackets per installation instructions (Y/N) _____
Verify that condensate connection is installed per installation instructions (Y/N) _____
Verify that flue hood is installed (Y/N) _____
Check refrigerant piping for indications of leaks; investigate and repair if necessary (Y/N) _____
Check gas piping for leaks (Y/N) _____
Check all electrical connections and terminals for tightness (Y/N) _____
Check that return (indoor) air filters are clean and in place (Y/N) _____
Verify that unit installation is level (Y/N) _____
Check fan wheels and propeller for location in housing/orifice and setscrew tightness (Y/N) _____
Check to ensure that electrical wiring is not in contact with refrigerant lines or sharp metal edges (Y/N) _____
Check pulley alignment and belt tension per installation instructions (Y/N) _____
II. START-UP (Refer to Unit Service/Maintenance Manual for Start-Up Instructions)
ELECTRICAL
Supply Voltage
L1-L2_____________
L2-L3_____________
L3-L1_____________
Compressor Amps 1
L1 _____________
L2 _____________
L3 _____________
Compressor Amps 2
L1 _____________
L2 _____________
L3 _____________
Indoor Fan Amps
L1 _____________
L2 _____________
L3 _____________
Outdoor Fan Amps
NO.1 _____________
NO.2 _____________
NO.3 _____________
NO.4 _____________
NO.5 _____________
NO.6 _____________
TEMPERATURES
Outdoor-air Temperature
_____________ °F DB (Dry Bulb)
_____________
°
F WB (Wet Bulb)
Return-air Temperature
_____________ °F DB
_____________
°
F WB
Cooling Supply Air Temperature
_____________ °F DB
_____________
°
F WB
Gas Heat Supply Air
_____________ °F DB
_____________
°
F WB
PRESSURES (HEATING MODE)
GAS INLET PRESSURE
_____________ IN. WG
GAS MANIFOLD PRESSURE
_____________ IN. WG (Low Fire)
_____________ IN. WG (High Fire)
NOTE: To avoid injury to personnel and damage to equipment or
property when completing the procedures listed in this start-up
checklist, use good judgment, follow safe practices, and adhere
to the safety considerations/information as outlined in preceding
sections of this Installation Instruction document.
Summary of Contents for LEGACY 580J*20M Series
Page 4: ...4 Fig 2 Unit Dimensional Drawing 17 and 20 Size Unit...
Page 5: ...5 Fig 2 Unit Dimensional Drawing 17 and 20 Size Unit cont...
Page 6: ...6 Fig 3 Unit Dimensional Drawing 24 and 28 Size Unit...
Page 7: ...7 Fig 3 Unit Dimensional Drawing 24 and 28 Size Unit cont...
Page 8: ...8 Fig 4 Unit Dimensional Drawing 30 Size Unit...
Page 9: ...9 Fig 4 Unit Dimensional Drawing 30 Size Unit cont...
Page 13: ...13 Fig 8 Roof Curb Details 17 and 20 Size Units 17 20...
Page 14: ...14 Fig 9 Roof Curb Details 24 and 28 Size Units 24 28...
Page 15: ...15 Fig 10 Roof Curb Details 30 Size Units 30...
Page 25: ...25 Fig 33 Typical Perfect Humidity Adaptive Dehumidification System Humidistat Wiring...
Page 40: ...40 Fig 41 Typical RTU Open System Control Wiring Diagram...
Page 41: ...41 Fig 42 Typical RTU Open System Control Wiring Diagram with Perfect Humidity System...