35
Table 15 — Enthalpy Operation with DCV (CO
2
Sensor) — 1 Speed Fan
*With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on second stage of mechanical cooling Y2-O after the delay if the call for Y1-I
and Y2-I have not been satisfied.
Table 16 — Dry Bulb Operation No DCV (CO
2
Sensor) — 2 Speed Fan
*With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on second stage of mechanical cooling Y2-O after the delay if the call for Y1-I
and Y2-I have not been satisfied.
DEMAND
CONTROLLED
VENTILATION (DCV)
OUTSIDE AIR
GOOD TO
ECONOMIZE
Y1-I
Y2-I
FAN
SPEED
Y1-O
Y2-O
OCCUPIED
UNOCCUPIED
Below CO
2
Set
No
OFF
OFF
HIGH
0v/Off
0v/Off
VENTMIN
Closed
ON
OFF
HIGH
24v/On
0v/Off
VENTMIN
Closed
ON
ON
HIGH
24v/On
24v/On
VENTMIN
Closed
Yes
OFF
OFF
HIGH
0v/Off
0v/Off
VENTMIN
Closed
ON
OFF
HIGH
0v/Off
0v/Off
VENTMIN to
Full-Open
Closed to Full-Open
ON
ON
HIGH
24v/On
0v/Off
VENTMIN to
Full-Open
Closed to Full-Open
Above CO
2
Set
No
OFF
OFF
HIGH
0v/Off
0v/Off
VENTMIN to
VENTMAX
Closed
ON
OFF
HIGH
24v/On
0v/Off
VENTMIN to
VENTMAX
Closed
ON
ON
HIGH
24v/On
24v/On
VENTMIN to
VENTMAX
Closed
Yes
OFF
OFF
HIGH
0v/Off
0v/Off
VENTMIN to
VENTMAX
Closed
ON
OFF
HIGH
0v/Off
0v/Off
VENTMIN to
Full-Open
Closed to Full-Open
ON
ON
HIGH
24v/On
0v/Off*
VENTMIN to
Full-Open
Closed to Full-Open
DEMAND
CONTROLLED
VENTILATION (DCV)
OUTSIDE AIR
GOOD TO
ECONOMIZE
Y1-I
Y2-I
FAN
SPEED
Y1-O
Y2-O
OCCUPIED
UNOCCUPIED
NONE
NO
OFF
OFF
LOW
0v/Off
0v/Off
MIN POS
Closed
ON
OFF
LOW
24v/On
0v/Off
MIN POS
Closed
ON
ON
HIGH
24v/On
24v/On
MIN POS
Closed
NONE
YES
OFF
OFF
LOW
0v/Off
0v/Off
MIN POS
Closed
ON
OFF
LOW
0v/Off
0v/Off
MIN POS to Full
Open
Closed to Full-Open
ON
ON
HIGH
24v/On
0v/Off*
MIN POS to Full
Open
Closed to Full-Open
Summary of Contents for LEGACY 580J*20M Series
Page 4: ...4 Fig 2 Unit Dimensional Drawing 17 and 20 Size Unit...
Page 5: ...5 Fig 2 Unit Dimensional Drawing 17 and 20 Size Unit cont...
Page 6: ...6 Fig 3 Unit Dimensional Drawing 24 and 28 Size Unit...
Page 7: ...7 Fig 3 Unit Dimensional Drawing 24 and 28 Size Unit cont...
Page 8: ...8 Fig 4 Unit Dimensional Drawing 30 Size Unit...
Page 9: ...9 Fig 4 Unit Dimensional Drawing 30 Size Unit cont...
Page 13: ...13 Fig 8 Roof Curb Details 17 and 20 Size Units 17 20...
Page 14: ...14 Fig 9 Roof Curb Details 24 and 28 Size Units 24 28...
Page 15: ...15 Fig 10 Roof Curb Details 30 Size Units 30...
Page 25: ...25 Fig 33 Typical Perfect Humidity Adaptive Dehumidification System Humidistat Wiring...
Page 40: ...40 Fig 41 Typical RTU Open System Control Wiring Diagram...
Page 41: ...41 Fig 42 Typical RTU Open System Control Wiring Diagram with Perfect Humidity System...