6

ACCESSORY USAGE GUIDELINE

Accessory

REQUIRED FOR LOW---AMBIENT

COOLING APPLICATIONS

(Below 55

°

F / 12.8

°

C)

REQUIRED FOR

LONG LINE APPLICATIONS*

(Over 80 ft. / 24.38 m)

REQUIRED FOR

SEA COAST APPLICATIONS

(Within 2 miles / 3.22 km)

Accumulator

Standard

Standard

Standard

Ball Bearing Fan Motor

Yes

{

No

No

Compressor Start Assist Capacitor and

Relay

Yes

Yes

No

Crankcase Heater

Yes

Yes

No

Evaporator Freeze Thermostat

Yes

No

No

Hard Shutoff TXV

Yes

Yes

Yes

Isolation Relay

Yes

No

No

Liquid Line Solenoid Valve

No

See Long---Line Application Guideline

No

Motor Master

®

Control or

Low Ambient Switch

Yes

No

No

Support Feet

Recommended

No

Recommended

* For tubing line sets between 80 and 200 ft. (24.38 and 60.96 m) and/or 20 ft. (6.09 m) vertical differential, refer to Residential Split---System Longline

Application Guideline.

{

Additional requirement for Low---Ambient Controller (full modulation feature) MotorMaster

r

Control.

Accessory Description and Usage (Listed Alphabetically)

1. Ball--Bearing Fan Motor

A fan motor with ball bearings which permits speed reduction

while maintaining bearing lubrication.

Usage Guideline:

Required on all units when using MotorMaster

r

2. Compressor Start Assist -- Capacitor and Relay

Start capacitor and relay gives a ”hard” boost to compressor motor

at each start up.

Usage Guideline:

Required for reciprocating compressors in the following

applications:

Long line
Low ambient cooling
Hard shut off expansion valve on indoor coil
Liquid line solenoid on indoor coil

Required for single--phase scroll compressors in the
following applications:

Long line
Low ambient cooling

Suggested for all compressors in areas with a history of

low voltage problems.

3. Compressor Start Assist — PTC Type

Solid state electrical device which gives a ”soft” boost to the
compressor at each start--up.

Usage Guideline:

Suggested in installations with marginal power supply.

4. Crankcase Heater

An electric resistance heater which mounts to the base of the
compressor to keep the lubricant warm during off cycles. Improves

compressor lubrication on restart and minimizes the chance of
liquid slugging.

Usage Guideline:

Required in low ambient cooling applications.
Required in long line applications.
Suggested in all commercial applications.

5. Evaporator Freeze Thermostat

An SPST temperature--actuated switch that stops unit operation
when evaporator reaches freeze--up conditions.

Usage Guideline:

Required when low ambient kit has been added.

6. Isolation Relay

An SPDT relay which switches the low--ambient controller out of

the outdoor fan motor circuit when the heat pump switches to
heating mode.

Usage Guideline:

Required in all heat pumps where low ambient kit has
been added.

7. Liquid--Line Solenoid Valve (LLS)

An electrically operated shutoff valve which stops and starts

refrigerant liquid flow in response to compressor operation. It is to

be installed at the outdoor unit to control refrigerant off cycle
migration in the heating mode.

Usage Guideline:

An LLS is required in all long line heat pump

applications to control refrigerant off cycle migration in

the heating mode. See Long Line Guideline.

8. Low--Ambient Pressure Switch Kit

A long life pressure switch which is mounted to outdoor unit
service valve. It is designed to cycle the outdoor fan motor in order

to maintain head pressure within normal operating limits. The
control will maintain working head pressure at low--ambient

temperatures down to 0

_

F (--17.8

_

C) when properly installed.

Usage Guideline:

A Low--Ambient Pressure Switch or MotorMaster

r

Low--Ambient Controller must be used when cooling
operation is used at outdoor temperatures below 55

_

F

(12.8

_

C).

9. MotorMaster

r

Low--Ambient Controller

A fan--speed control device activated by a temperature sensor,

designed to control condenser fan motor speed in response to the
saturated, condensing temperature during operation in cooling

mode only. For outdoor temperatures down to --20

_

F (--28.9

_

C), it

maintains condensing temperature at 100

_

F

±

10

_

F (37.8

_

C

±

6.5

_

C).

Usage Guideline:

A MotorMaster

r

Low Ambient Controller or

Low--Ambient Pressure Switch must be used when
cooling operation is used at outdoor temperatures

below 55

_

F (12.8

_

C).

Suggested for all commercial applications.

215B

Summary of Contents for Legacy 215B

Page 1: ...n INDUSTRY LEADING FEATURES BENEFITS Efficiency S 15 SEER 12 5 EER 8 0 9 0 HSPF S Microtube Technologyt refrigeration system S Indoor air quality accessories available Sound S Sound level as low as 69...

Page 2: ...frigerant charging and air flow instructions Failure to confirm proper charge and air flow may reduce energy efficiency and shorten equipment life Use of the AHRI Certified TM Mark indicates a manufac...

Page 3: ...diameters shown in the chart below are acceptable for HP systems with Puron refrigerant Vapor Line Sizing and Cooling Capacity Losses Puronr Refrigerant 1 Stage Heat Pump Applications Unit Nominal Siz...

Page 4: ...50 250 250 250 250 24000 HP with Puron 3 8 250 250 250 250 250 250 250 30000 HP with Puron 3 8 250 250 250 250 250 250 250 36000 HP with Puron 3 8 250 250 250 250 250 250 250 42000 HP with Puron 3 8 2...

Page 5: ...or liquid line solenoid valve ACCESSORY THERMOSTATS THERMOSTAT SUBBASE PKG DESCRIPTION T6 PRH01 A Programmable Thermidistat T6 NRH01 A Non programmable Thermidistat T6 PHP01 Preferred Series Programm...

Page 6: ...f cycles Improves compressor lubrication on restart and minimizes the chance of liquid slugging Usage Guideline Required in low ambient cooling applications Required in long line applications Suggeste...

Page 7: ...e Guideline Suggested in the following applications Heat pump installations in heavy snowfall areas Heat pump installations in snow drift locations Heat pump installations in areas of prolonged subfre...

Page 8: ...units and requires external power source Copper wire must be used from service disconnect to unit All motors compressors contain internal overload protection Complies with 2007 requirements of ASHRAE...

Page 9: ...3 4 16 3 4 17 215 257 36 1 8 X 39 1 4 X 39 3 8 215B042 A X O O O 35 28 15 16 3 7 8 7 8 6 9 16 28 7 16 9 1 8 2 15 16 5 8 17 16 3 4 14 3 4 245 290 36 1 8 X 39 1 4 X 32 9 16 215B048 A X O O O 35 28 15 16...

Page 10: ...25 5 431 8 97 5 116 6 917 7 X 997 7 X 999 5 215B042 A X O O O 889 0 734 8 97 9 22 2 166 1 722 8 231 3 74 5 16 3 431 8 425 5 374 7 111 1 131 5 917 7 X 997 7 X 826 8 215B048 A X O O O 889 0 734 8 97 9 2...

Page 11: ...ED HEATING CAPACITY MBTUH OUTDOOR TEMPERATURE F C BASED ON INDOOR ENT AIR AT 70 F 21 1 C AND AT RATED CFM 215BNA018 FX4DNF019 215BNA024 FX4DNF025 215BNA042 FX4DNF043 215BNA030 FX4DNF031 215BNA060 FX4D...

Page 12: ...7 2 24 609 6 Service 6 152 4 12 304 8 24 609 6 Service 24 609 6 Service 24 609 6 Service Note Numbers in mm 18 457 2 18 457 2 12 304 8 IMPORTANT When installing multiple units in an alcove roof well o...

Page 13: ...00 11 2 13 0 18 000 3 62 8 0 11 200 2 40 3646483 215BNA018 A CNPV 1917A 315 A J AV048090 17 600 12 5 15 0 17 800 3 80 8 5 10 500 2 54 3646690 215BNA018 A CNPV 1917A 353 A B AV036060 18 000 13 0 15 5 1...

Page 14: ...24 A CNPH 2417A TDR 23 400 11 2 13 5 24 000 3 80 8 3 15 200 2 54 3646719 215BNA024 A CNPH 3017A 353 A B AV036080 23 400 12 5 15 5 24 000 4 00 9 0 14 600 2 72 3647035 215BNA024 A CNPH 3017A 313 AV02404...

Page 15: ...4 3647339 215BNA030 A FE4ANF002 UI 28 200 12 5 15 0 28 200 3 92 8 5 16 800 2 62 3647348 215BNA030 A FF1ENP030 27 600 11 2 13 5 29 000 3 68 8 0 17 500 2 48 3647350 215BNA030 A FF1ENP031 28 200 12 0 14...

Page 16: ...0 2 62 3646876 215BNA030 A CNPH 3617A 355 A C AV042080 27 800 12 5 15 0 28 000 3 80 8 1 16 700 2 58 3646909 215BNA030 A CNPH 3617A 355 A C AV060080 28 000 12 5 15 0 28 200 3 82 8 1 16 700 2 60 3646944...

Page 17: ...215BNA030 A CSPH 3612A 315 A J AV048090 28 000 12 5 15 3 28 200 3 98 8 5 16 800 2 66 3646539 215BNA030 A CSPH 3612A 315 A J AV060110 28 000 12 5 15 0 28 400 3 98 8 5 16 800 2 66 3646577 215BNA030 A C...

Page 18: ...34 800 3 60 7 9 21 200 2 48 3647080 215BNA036 A CNPH 3617A 313 AV048090 33 400 12 0 14 5 34 600 3 68 8 1 21 000 2 54 3647108 215BNA036 A CNPH 3617A 313 AV060110 33 600 12 0 14 5 34 600 3 70 8 1 21 000...

Page 19: ...221A 353 A B AV060100 33 800 12 0 14 5 34 600 3 76 8 2 21 000 2 58 3646884 215BNA036 A CNPV 4221A 355 A C AV042080 33 600 12 0 14 0 34 800 3 70 8 1 21 200 2 54 3646919 215BNA036 A CNPV 4221A 355 A C A...

Page 20: ...A042 A CAP 4221A 313 AV060110 41 000 12 5 14 5 42 000 3 72 8 3 25 600 2 58 3646510 215BNA042 A CAP 4221A 315 A J AV060110 41 000 12 0 14 5 42 000 3 68 8 2 25 600 2 56 3646779 215BNA042 A CAP 4221A 353...

Page 21: ...042 A CNPH 4821A 315 A J AV048090 41 500 12 0 14 5 42 000 3 78 8 4 25 800 2 62 3646522 215BNA042 A CNPH 4821A 315 A J AV060110 41 500 12 5 15 0 42 000 3 80 8 5 25 800 2 62 3646560 215BNA042 A CNPH 482...

Page 22: ...3 86 8 4 26 000 2 66 3646672 215BNA042 A CSPH 4212A 353AAV036040 41 500 12 0 14 5 42 000 3 82 8 3 26 200 2 62 3646865 215BNA042 A CSPH 4212A 355 A C AV042060 41 500 12 0 14 5 42 000 3 80 8 2 26 200 2...

Page 23: ...14 0 45 500 3 74 8 1 29 000 2 60 3647262 215BNA048 A CAP 6025A TDR 46 500 11 5 13 5 46 500 3 74 8 1 29 800 2 56 3647269 215BNA048 A CNPF 4818A TDR 44 500 11 5 13 5 45 500 3 56 7 7 29 000 2 50 3646756...

Page 24: ...NA048 A CSPH 4812A 313 AV048090 46 000 12 0 14 0 45 500 3 72 8 0 28 800 2 58 3647127 215BNA048 A CSPH 4812A 313 AV060110 46 000 12 0 14 5 45 000 3 74 8 0 28 600 2 60 3647151 215BNA048 A CSPH 4812A 313...

Page 25: ...56 500 3 72 8 3 35 200 2 64 3647310 215BNA060 A CNPV 6024A TDR 55 500 11 5 13 5 56 500 3 66 8 2 36 000 2 60 3647148 215BNA060 A CNPV 6124A 313 AV060135 56 500 12 0 14 5 56 500 3 78 8 5 35 600 2 66 364...

Page 26: ...90 15 90 1 61 14 98 14 98 1 81 14 00 14 00 2 04 57 13 9 18 29 18 29 1 12 17 54 17 54 1 27 16 74 16 74 1 43 15 88 15 88 1 61 14 96 14 96 1 81 13 98 13 98 2 04 COOLING INDOOR MODEL CAPACITY POWER FURNAC...

Page 27: ...1 09 CSPH 3012A 0 98 1 09 FB4CNF024 0 98 1 02 FB4CNF030 0 98 0 98 CAP 2414A 0 98 0 98 315 A J AV036070 CAP 3014A 0 98 0 98 315 A J AV036070 COOLING INDOOR MODEL CAPACITY POWER FURNACE MODEL CNPH 2417...

Page 28: ...355 A C AV060120 CSPH 2412A 0 98 0 98 355 A C AV060120 CSPH 3012A 0 98 0 98 355 A C AV060120 CNPH 2417A 0 98 0 98 355AAV042040 CNPH 3017A 0 98 0 98 355AAV042040 CSPH 2412A 0 98 0 98 355AAV042040 CSPH...

Page 29: ...PF 3618A 0 97 1 09 CNPH 3017A 0 97 1 09 CNPH 3617A 0 97 1 09 CNPV 3014A 0 97 1 09 CNPV 3017A 0 97 1 09 CNPV 3117A 1 00 1 09 CNPV 3617A 0 97 1 09 CNPV 3621A 0 97 1 09 COOLING INDOOR MODEL CAPACITY POWE...

Page 30: ...617A 0 97 0 97 355 A C AV060080 CNPV 3621A 0 97 0 97 355 A C AV060080 CSPH 3012A 0 97 1 01 355 A C AV060080 CSPH 3612A 0 97 0 97 355 A C AV060080 CAP 3621A 0 97 0 97 355 A C AV060100 CNPH 3017A 0 97 1...

Page 31: ...1A 0 97 1 08 CAP 4224A 0 97 1 08 CNPF 3618A 0 97 1 10 CNPH 3617A 0 97 1 10 CNPH 4221A 0 97 1 08 CNPV 3617A 0 97 1 10 CNPV 3621A 0 97 1 10 CNPV 3717A 1 01 1 09 CNPV 4217A 0 98 1 09 COOLING INDOOR MODEL...

Page 32: ...1 355 A C AV060100 CAP 4221A 0 97 1 01 355 A C AV060100 CNPH 3617A 0 96 1 00 355 A C AV060100 CNPH 4221A 0 97 1 01 355 A C AV060100 CNPV 3621A 0 96 1 00 355 A C AV060100 CNPV 4221A 0 97 1 01 355 A C A...

Page 33: ...PV 4821A 1 01 1 10 CNPV 4824A 1 01 1 10 CSPH 4212A 0 99 1 07 CSPH 4812A 1 01 1 10 CNPH 4221A 0 98 1 03 315 A J AV036070 CNPH 4821A 1 00 1 04 315 A J AV036070 COOLING INDOOR MODEL CAPACITY POWER FURNAC...

Page 34: ...060120 CNPH 4221A 0 99 1 03 355 A C AV060120 CNPH 4821A 1 00 1 00 355 A C AV060120 CNPV 4324A 1 01 1 01 355 A C AV060120 CNPV 4824A 1 00 1 00 355 A C AV060120 CSPH 4212A 1 00 1 04 355 A C AV060120 CSP...

Page 35: ...PH 6012A 0 98 1 06 CAP 4817A 0 96 1 04 315 A J AV048090 CNPH 4821A 0 95 0 99 315 A J AV048090 CNPH 6024A 0 97 1 01 315 A J AV048090 CNPH 6124A 0 97 1 01 315 A J AV048090 COOLING INDOOR MODEL CAPACITY...

Page 36: ...313 AV048090 CNPH 6024A 0 98 1 02 313 AV048090 CNPH 6124A 0 98 1 02 313 AV048090 CNPV 4821A 0 96 1 00 313 AV048090 CSPH 4812A 0 97 1 01 313 AV048090 CSPH 6012A 0 98 1 02 313 AV048090 CAP 4821A 0 95 0...

Page 37: ...08 CSPH 6012A 0 97 1 06 CAP 6021A 0 97 1 06 315 A J AV060110 CNPH 6024A 0 97 1 06 315 A J AV060110 CNPH 6124A 0 98 1 07 315 A J AV060110 COOLING INDOOR MODEL CAPACITY POWER FURNACE MODEL CSPH 6012A 0...

Page 38: ...OR MODEL CAPACITY POWER FURNACE MODEL FX4DNF019 1 00 1 00 FB4CNF018 1 01 1 05 FB4CNF024 1 01 1 05 FE4ANF002 1 00 1 02 FF1ENP018 1 01 1 12 FF1ENP019 1 01 1 05 FF1ENP024 1 01 1 10 FF1ENP025 1 01 1 02 FV...

Page 39: ...A 1 00 1 02 315 A J AV048090 CNPH 3017A 1 00 1 02 315 A J AV048090 CNPV 2417A 1 00 1 02 315 A J AV048090 CNPV 3017A 1 00 1 02 315 A J AV048090 CNPV 3117A 1 00 0 98 315 A J AV048090 CSPH 2412A 1 00 1 0...

Page 40: ...7A 0 98 1 02 315 A J AV048090 CAP 3617A 0 98 1 01 315 A J AV048090 CNPH 3017A 0 98 1 02 315 A J AV048090 CNPH 3617A 0 98 1 02 315 A J AV048090 CNPV 3017A 0 98 1 02 315 A J AV048090 CNPV 3117A 0 99 0 9...

Page 41: ...5 A C AV060120 CNPH 3617A 0 99 1 02 355 A C AV060120 CSPH 3012A 0 99 1 02 355 A C AV060120 CSPH 3612A 0 99 0 99 355 A C AV060120 CNPH 3017A 0 99 1 03 355AAV042040 CNPH 3617A 0 99 1 03 355AAV042040 CSP...

Page 42: ...PH 3617A 0 97 1 05 315 A J AV048090 CNPH 4221A 0 98 1 03 315 A J AV048090 CNPV 3617A 0 97 1 05 315 A J AV048090 CNPV 3717A 0 99 0 99 315 A J AV048090 CNPV 4217A 0 98 1 02 315 A J AV048090 CSPH 3612A 0...

Page 43: ...CNPV 4324A 0 99 0 98 355 A C AV060120 CSPH 3612A 0 98 1 02 355 A C AV060120 CSPH 4212A 0 98 1 00 355 A C AV060120 CAP 4224A 0 98 1 04 355AAV042040 CNPH 3617A 0 98 1 07 355AAV042040 CNPH 4221A 0 98 1...

Page 44: ...AV060110 CAP 4821A 1 01 1 02 315 A J AV060110 CNPH 4221A 1 01 1 05 315 A J AV060110 CNPH 4821A 1 01 1 02 315 A J AV060110 CNPV 4221A 1 01 1 05 315 A J AV060110 CNPV 4324A 1 01 0 99 315 A J AV060110 CN...

Page 45: ...NPV 4324A 1 01 1 01 355AAV042040 CNPV 4824A 1 01 1 04 355AAV042040 CSPH 4212A 1 01 1 04 355AAV042040 CSPH 4812A 1 01 1 03 355AAV042040 CAP 4817A 1 01 1 03 313 AV048070 CNPH 4221A 1 01 1 07 313 AV04807...

Page 46: ...0110 CNPV 6124A 0 98 0 99 315 A J AV060110 CSPH 4812A 0 98 1 02 315 A J AV060110 CSPH 6012A 0 98 1 00 315 A J AV060110 CAP 4824A 0 97 1 00 315 A J AV066135 CAP 6024A 0 97 0 99 315 A J AV066135 CNPH 48...

Page 47: ...13 AV060110 CSPH 4812A 0 97 1 00 313 AV060110 CSPH 6012A 0 98 0 98 313 AV060110 CAP 4824A 0 98 1 01 313 AV060135 CAP 6024A 0 98 1 00 313 AV060135 CNPH 4821A 0 97 1 00 313 AV060135 CNPH 6024A 0 98 1 00...

Page 48: ...99 1 04 CAP 6025A 0 99 1 04 CNPH 6024A 0 99 1 04 CNPH 6124A 0 99 1 03 CNPV 6024A 0 99 1 04 CNPV 6124A 0 99 1 02 CSPH 6012A 0 99 1 03 CAP 6021A 0 99 1 04 315 A J AV060110 CNPH 6024A 0 99 1 04 315 A J A...

Page 49: ...coat paint Fans Condenser fan will be direct drive propeller type discharging air upward Condenser fan motors will be totally enclosed 1 phase type with class B insulation and permanently lubricated b...

Page 50: ...r change at any time specifications or designs without notice and without incurring obligations E2010 Bryant Heating Cooling Systems D 7310 W Morris St D Indianapolis IN 46231 Printed in U S A Edition...

Reviews: