Accessory Description and Usage (Listed Alphabetically) -- CONTINUED

10. Outdoor Air Temperature Sensor

Designed for use with Bryant Thermostats listed in this

publication. This device enables the thermostat to display the
outdoor temperature. This device also is required to enable special

thermostat features such as auxiliary heat lock out.

Usage Guideline:

Suggested for all Bryant thermostats listed in this

publication.

11. Outdoor Thermostat

An SPDT temperature--actuated switch which turns on

supplemental electric heaters when outdoor air temperature drops
below a user--selected set point.

Usage Guideline:

Electric supplemental heat applications in non--variable

speed indoor units when electric heat staging is desired.

12. Secondary Outdoor Thermostat

An SPDT temperature--actuated switch which turns on third--stage

of supplemental electric heaters when outdoor air temperature
drops below the second--stage set point.

Usage Guideline:

Outdoor thermostat applications where electric heater is

capable of 3--stage operation.

13. Snow Stand

Coated wire rack which supports unit 18 in. (457.2 mm) above

mounting pad to allow for drainage from unit base.

Usage Guideline:

Suggested in the following applications:

Heat pump installations in heavy snowfall areas.
Heat pump installations in snow drift locations.
Heat pump installations in areas of prolonged
subfreezing temperatures.
All commercial installations.

Note

: Snow stand does not support 26” X 26” (660 X 660 mm)

small basepan size.

14. Sound Hood

Wraparound sound reducing cover for the compressor. Reduces the

sound level by about 2 dBA.

Usage Guideline:

Suggested when unit is installed closer than 15 ft.

(4.577 m) to quiet areas, bedrooms, etc.
Suggested when unit is installed between two houses less

than 10 ft. (3.05 m) apart.

15. Thermostatic Expansion Valve (TXV) Bi--Flow

A modulating flow--control valve which meters refrigerant liquid

flow rate into the evaporator in response to the superheat of the
refrigerant gas leaving the evaporator.

Usage Guideline:

Accessory required to meet AHRI rating and system

reliability, where indoor not equipped.
Required in all heat pump applications designed with
Puron refrigerant.

16. Time--Delay Relay

An SPST delay relay which briefly continues operation of indoor

blower motor to provide additional cooling after the compressor
cycles off.

Note:

Most indoor unit controls include this feature. For those that

do not, use the guideline below.

Usage Guideline:

Accessory required to meet AHRI rating, where indoor

not equipped.

215B

Summary of Contents for Legacy 215B

Page 1: ...n INDUSTRY LEADING FEATURES BENEFITS Efficiency S 15 SEER 12 5 EER 8 0 9 0 HSPF S Microtube Technologyt refrigeration system S Indoor air quality accessories available Sound S Sound level as low as 69...

Page 2: ...frigerant charging and air flow instructions Failure to confirm proper charge and air flow may reduce energy efficiency and shorten equipment life Use of the AHRI Certified TM Mark indicates a manufac...

Page 3: ...diameters shown in the chart below are acceptable for HP systems with Puron refrigerant Vapor Line Sizing and Cooling Capacity Losses Puronr Refrigerant 1 Stage Heat Pump Applications Unit Nominal Siz...

Page 4: ...50 250 250 250 250 24000 HP with Puron 3 8 250 250 250 250 250 250 250 30000 HP with Puron 3 8 250 250 250 250 250 250 250 36000 HP with Puron 3 8 250 250 250 250 250 250 250 42000 HP with Puron 3 8 2...

Page 5: ...or liquid line solenoid valve ACCESSORY THERMOSTATS THERMOSTAT SUBBASE PKG DESCRIPTION T6 PRH01 A Programmable Thermidistat T6 NRH01 A Non programmable Thermidistat T6 PHP01 Preferred Series Programm...

Page 6: ...f cycles Improves compressor lubrication on restart and minimizes the chance of liquid slugging Usage Guideline Required in low ambient cooling applications Required in long line applications Suggeste...

Page 7: ...e Guideline Suggested in the following applications Heat pump installations in heavy snowfall areas Heat pump installations in snow drift locations Heat pump installations in areas of prolonged subfre...

Page 8: ...units and requires external power source Copper wire must be used from service disconnect to unit All motors compressors contain internal overload protection Complies with 2007 requirements of ASHRAE...

Page 9: ...3 4 16 3 4 17 215 257 36 1 8 X 39 1 4 X 39 3 8 215B042 A X O O O 35 28 15 16 3 7 8 7 8 6 9 16 28 7 16 9 1 8 2 15 16 5 8 17 16 3 4 14 3 4 245 290 36 1 8 X 39 1 4 X 32 9 16 215B048 A X O O O 35 28 15 16...

Page 10: ...25 5 431 8 97 5 116 6 917 7 X 997 7 X 999 5 215B042 A X O O O 889 0 734 8 97 9 22 2 166 1 722 8 231 3 74 5 16 3 431 8 425 5 374 7 111 1 131 5 917 7 X 997 7 X 826 8 215B048 A X O O O 889 0 734 8 97 9 2...

Page 11: ...ED HEATING CAPACITY MBTUH OUTDOOR TEMPERATURE F C BASED ON INDOOR ENT AIR AT 70 F 21 1 C AND AT RATED CFM 215BNA018 FX4DNF019 215BNA024 FX4DNF025 215BNA042 FX4DNF043 215BNA030 FX4DNF031 215BNA060 FX4D...

Page 12: ...7 2 24 609 6 Service 6 152 4 12 304 8 24 609 6 Service 24 609 6 Service 24 609 6 Service Note Numbers in mm 18 457 2 18 457 2 12 304 8 IMPORTANT When installing multiple units in an alcove roof well o...

Page 13: ...00 11 2 13 0 18 000 3 62 8 0 11 200 2 40 3646483 215BNA018 A CNPV 1917A 315 A J AV048090 17 600 12 5 15 0 17 800 3 80 8 5 10 500 2 54 3646690 215BNA018 A CNPV 1917A 353 A B AV036060 18 000 13 0 15 5 1...

Page 14: ...24 A CNPH 2417A TDR 23 400 11 2 13 5 24 000 3 80 8 3 15 200 2 54 3646719 215BNA024 A CNPH 3017A 353 A B AV036080 23 400 12 5 15 5 24 000 4 00 9 0 14 600 2 72 3647035 215BNA024 A CNPH 3017A 313 AV02404...

Page 15: ...4 3647339 215BNA030 A FE4ANF002 UI 28 200 12 5 15 0 28 200 3 92 8 5 16 800 2 62 3647348 215BNA030 A FF1ENP030 27 600 11 2 13 5 29 000 3 68 8 0 17 500 2 48 3647350 215BNA030 A FF1ENP031 28 200 12 0 14...

Page 16: ...0 2 62 3646876 215BNA030 A CNPH 3617A 355 A C AV042080 27 800 12 5 15 0 28 000 3 80 8 1 16 700 2 58 3646909 215BNA030 A CNPH 3617A 355 A C AV060080 28 000 12 5 15 0 28 200 3 82 8 1 16 700 2 60 3646944...

Page 17: ...215BNA030 A CSPH 3612A 315 A J AV048090 28 000 12 5 15 3 28 200 3 98 8 5 16 800 2 66 3646539 215BNA030 A CSPH 3612A 315 A J AV060110 28 000 12 5 15 0 28 400 3 98 8 5 16 800 2 66 3646577 215BNA030 A C...

Page 18: ...34 800 3 60 7 9 21 200 2 48 3647080 215BNA036 A CNPH 3617A 313 AV048090 33 400 12 0 14 5 34 600 3 68 8 1 21 000 2 54 3647108 215BNA036 A CNPH 3617A 313 AV060110 33 600 12 0 14 5 34 600 3 70 8 1 21 000...

Page 19: ...221A 353 A B AV060100 33 800 12 0 14 5 34 600 3 76 8 2 21 000 2 58 3646884 215BNA036 A CNPV 4221A 355 A C AV042080 33 600 12 0 14 0 34 800 3 70 8 1 21 200 2 54 3646919 215BNA036 A CNPV 4221A 355 A C A...

Page 20: ...A042 A CAP 4221A 313 AV060110 41 000 12 5 14 5 42 000 3 72 8 3 25 600 2 58 3646510 215BNA042 A CAP 4221A 315 A J AV060110 41 000 12 0 14 5 42 000 3 68 8 2 25 600 2 56 3646779 215BNA042 A CAP 4221A 353...

Page 21: ...042 A CNPH 4821A 315 A J AV048090 41 500 12 0 14 5 42 000 3 78 8 4 25 800 2 62 3646522 215BNA042 A CNPH 4821A 315 A J AV060110 41 500 12 5 15 0 42 000 3 80 8 5 25 800 2 62 3646560 215BNA042 A CNPH 482...

Page 22: ...3 86 8 4 26 000 2 66 3646672 215BNA042 A CSPH 4212A 353AAV036040 41 500 12 0 14 5 42 000 3 82 8 3 26 200 2 62 3646865 215BNA042 A CSPH 4212A 355 A C AV042060 41 500 12 0 14 5 42 000 3 80 8 2 26 200 2...

Page 23: ...14 0 45 500 3 74 8 1 29 000 2 60 3647262 215BNA048 A CAP 6025A TDR 46 500 11 5 13 5 46 500 3 74 8 1 29 800 2 56 3647269 215BNA048 A CNPF 4818A TDR 44 500 11 5 13 5 45 500 3 56 7 7 29 000 2 50 3646756...

Page 24: ...NA048 A CSPH 4812A 313 AV048090 46 000 12 0 14 0 45 500 3 72 8 0 28 800 2 58 3647127 215BNA048 A CSPH 4812A 313 AV060110 46 000 12 0 14 5 45 000 3 74 8 0 28 600 2 60 3647151 215BNA048 A CSPH 4812A 313...

Page 25: ...56 500 3 72 8 3 35 200 2 64 3647310 215BNA060 A CNPV 6024A TDR 55 500 11 5 13 5 56 500 3 66 8 2 36 000 2 60 3647148 215BNA060 A CNPV 6124A 313 AV060135 56 500 12 0 14 5 56 500 3 78 8 5 35 600 2 66 364...

Page 26: ...90 15 90 1 61 14 98 14 98 1 81 14 00 14 00 2 04 57 13 9 18 29 18 29 1 12 17 54 17 54 1 27 16 74 16 74 1 43 15 88 15 88 1 61 14 96 14 96 1 81 13 98 13 98 2 04 COOLING INDOOR MODEL CAPACITY POWER FURNAC...

Page 27: ...1 09 CSPH 3012A 0 98 1 09 FB4CNF024 0 98 1 02 FB4CNF030 0 98 0 98 CAP 2414A 0 98 0 98 315 A J AV036070 CAP 3014A 0 98 0 98 315 A J AV036070 COOLING INDOOR MODEL CAPACITY POWER FURNACE MODEL CNPH 2417...

Page 28: ...355 A C AV060120 CSPH 2412A 0 98 0 98 355 A C AV060120 CSPH 3012A 0 98 0 98 355 A C AV060120 CNPH 2417A 0 98 0 98 355AAV042040 CNPH 3017A 0 98 0 98 355AAV042040 CSPH 2412A 0 98 0 98 355AAV042040 CSPH...

Page 29: ...PF 3618A 0 97 1 09 CNPH 3017A 0 97 1 09 CNPH 3617A 0 97 1 09 CNPV 3014A 0 97 1 09 CNPV 3017A 0 97 1 09 CNPV 3117A 1 00 1 09 CNPV 3617A 0 97 1 09 CNPV 3621A 0 97 1 09 COOLING INDOOR MODEL CAPACITY POWE...

Page 30: ...617A 0 97 0 97 355 A C AV060080 CNPV 3621A 0 97 0 97 355 A C AV060080 CSPH 3012A 0 97 1 01 355 A C AV060080 CSPH 3612A 0 97 0 97 355 A C AV060080 CAP 3621A 0 97 0 97 355 A C AV060100 CNPH 3017A 0 97 1...

Page 31: ...1A 0 97 1 08 CAP 4224A 0 97 1 08 CNPF 3618A 0 97 1 10 CNPH 3617A 0 97 1 10 CNPH 4221A 0 97 1 08 CNPV 3617A 0 97 1 10 CNPV 3621A 0 97 1 10 CNPV 3717A 1 01 1 09 CNPV 4217A 0 98 1 09 COOLING INDOOR MODEL...

Page 32: ...1 355 A C AV060100 CAP 4221A 0 97 1 01 355 A C AV060100 CNPH 3617A 0 96 1 00 355 A C AV060100 CNPH 4221A 0 97 1 01 355 A C AV060100 CNPV 3621A 0 96 1 00 355 A C AV060100 CNPV 4221A 0 97 1 01 355 A C A...

Page 33: ...PV 4821A 1 01 1 10 CNPV 4824A 1 01 1 10 CSPH 4212A 0 99 1 07 CSPH 4812A 1 01 1 10 CNPH 4221A 0 98 1 03 315 A J AV036070 CNPH 4821A 1 00 1 04 315 A J AV036070 COOLING INDOOR MODEL CAPACITY POWER FURNAC...

Page 34: ...060120 CNPH 4221A 0 99 1 03 355 A C AV060120 CNPH 4821A 1 00 1 00 355 A C AV060120 CNPV 4324A 1 01 1 01 355 A C AV060120 CNPV 4824A 1 00 1 00 355 A C AV060120 CSPH 4212A 1 00 1 04 355 A C AV060120 CSP...

Page 35: ...PH 6012A 0 98 1 06 CAP 4817A 0 96 1 04 315 A J AV048090 CNPH 4821A 0 95 0 99 315 A J AV048090 CNPH 6024A 0 97 1 01 315 A J AV048090 CNPH 6124A 0 97 1 01 315 A J AV048090 COOLING INDOOR MODEL CAPACITY...

Page 36: ...313 AV048090 CNPH 6024A 0 98 1 02 313 AV048090 CNPH 6124A 0 98 1 02 313 AV048090 CNPV 4821A 0 96 1 00 313 AV048090 CSPH 4812A 0 97 1 01 313 AV048090 CSPH 6012A 0 98 1 02 313 AV048090 CAP 4821A 0 95 0...

Page 37: ...08 CSPH 6012A 0 97 1 06 CAP 6021A 0 97 1 06 315 A J AV060110 CNPH 6024A 0 97 1 06 315 A J AV060110 CNPH 6124A 0 98 1 07 315 A J AV060110 COOLING INDOOR MODEL CAPACITY POWER FURNACE MODEL CSPH 6012A 0...

Page 38: ...OR MODEL CAPACITY POWER FURNACE MODEL FX4DNF019 1 00 1 00 FB4CNF018 1 01 1 05 FB4CNF024 1 01 1 05 FE4ANF002 1 00 1 02 FF1ENP018 1 01 1 12 FF1ENP019 1 01 1 05 FF1ENP024 1 01 1 10 FF1ENP025 1 01 1 02 FV...

Page 39: ...A 1 00 1 02 315 A J AV048090 CNPH 3017A 1 00 1 02 315 A J AV048090 CNPV 2417A 1 00 1 02 315 A J AV048090 CNPV 3017A 1 00 1 02 315 A J AV048090 CNPV 3117A 1 00 0 98 315 A J AV048090 CSPH 2412A 1 00 1 0...

Page 40: ...7A 0 98 1 02 315 A J AV048090 CAP 3617A 0 98 1 01 315 A J AV048090 CNPH 3017A 0 98 1 02 315 A J AV048090 CNPH 3617A 0 98 1 02 315 A J AV048090 CNPV 3017A 0 98 1 02 315 A J AV048090 CNPV 3117A 0 99 0 9...

Page 41: ...5 A C AV060120 CNPH 3617A 0 99 1 02 355 A C AV060120 CSPH 3012A 0 99 1 02 355 A C AV060120 CSPH 3612A 0 99 0 99 355 A C AV060120 CNPH 3017A 0 99 1 03 355AAV042040 CNPH 3617A 0 99 1 03 355AAV042040 CSP...

Page 42: ...PH 3617A 0 97 1 05 315 A J AV048090 CNPH 4221A 0 98 1 03 315 A J AV048090 CNPV 3617A 0 97 1 05 315 A J AV048090 CNPV 3717A 0 99 0 99 315 A J AV048090 CNPV 4217A 0 98 1 02 315 A J AV048090 CSPH 3612A 0...

Page 43: ...CNPV 4324A 0 99 0 98 355 A C AV060120 CSPH 3612A 0 98 1 02 355 A C AV060120 CSPH 4212A 0 98 1 00 355 A C AV060120 CAP 4224A 0 98 1 04 355AAV042040 CNPH 3617A 0 98 1 07 355AAV042040 CNPH 4221A 0 98 1...

Page 44: ...AV060110 CAP 4821A 1 01 1 02 315 A J AV060110 CNPH 4221A 1 01 1 05 315 A J AV060110 CNPH 4821A 1 01 1 02 315 A J AV060110 CNPV 4221A 1 01 1 05 315 A J AV060110 CNPV 4324A 1 01 0 99 315 A J AV060110 CN...

Page 45: ...NPV 4324A 1 01 1 01 355AAV042040 CNPV 4824A 1 01 1 04 355AAV042040 CSPH 4212A 1 01 1 04 355AAV042040 CSPH 4812A 1 01 1 03 355AAV042040 CAP 4817A 1 01 1 03 313 AV048070 CNPH 4221A 1 01 1 07 313 AV04807...

Page 46: ...0110 CNPV 6124A 0 98 0 99 315 A J AV060110 CSPH 4812A 0 98 1 02 315 A J AV060110 CSPH 6012A 0 98 1 00 315 A J AV060110 CAP 4824A 0 97 1 00 315 A J AV066135 CAP 6024A 0 97 0 99 315 A J AV066135 CNPH 48...

Page 47: ...13 AV060110 CSPH 4812A 0 97 1 00 313 AV060110 CSPH 6012A 0 98 0 98 313 AV060110 CAP 4824A 0 98 1 01 313 AV060135 CAP 6024A 0 98 1 00 313 AV060135 CNPH 4821A 0 97 1 00 313 AV060135 CNPH 6024A 0 98 1 00...

Page 48: ...99 1 04 CAP 6025A 0 99 1 04 CNPH 6024A 0 99 1 04 CNPH 6124A 0 99 1 03 CNPV 6024A 0 99 1 04 CNPV 6124A 0 99 1 02 CSPH 6012A 0 99 1 03 CAP 6021A 0 99 1 04 315 A J AV060110 CNPH 6024A 0 99 1 04 315 A J A...

Page 49: ...coat paint Fans Condenser fan will be direct drive propeller type discharging air upward Condenser fan motors will be totally enclosed 1 phase type with class B insulation and permanently lubricated b...

Page 50: ...r change at any time specifications or designs without notice and without incurring obligations E2010 Bryant Heating Cooling Systems D 7310 W Morris St D Indianapolis IN 46231 Printed in U S A Edition...

Reviews: