—5—

 

SPECIFICATIONS Continued

 

 * Rated in accordance with U.S. Government DOE test procedures and/or ARI Standard 210/240-94.

†  Use copper wire only. Use 75°C in this application. When using non-metallic (NM) sheathed cable, wire size required should be based on that of 60°C con-

ductors, instead of wire sizes shown in table above per NEC 1996 Article 336-30. Length shown is as measured 1 way along wire path between unit and 
service panel for voltage drop not to exceed 2%.

‡  Check outdoor unit for required piston size.

††    018 Size with 11-kw heater not approved for use with heat pumps.

 

UNITS WITH FACTORY-INSTALLED ELECTRIC HEATERS OR CONTROLS

UNIT SIZE

024005

024075

024011

030005

030075

030011

RATINGS & PERFORMANCES

 

Nominal Capacity (Btuh)*

24,000

24,000

24,000

30,000

30,000

30,000

Nominal Airflow (CFM)

870

1080

Electric Heating Output (kw @240v)

5.0

7.5

11.0

5.0

7.5

11.0

Electric Heating Capacity (MBH @208/230v)

14.0/16.9

20.4/24.7

29.4/35.7

14.3/17.2

20.7/25.0

29.7/36.0

 

ELECTRICAL

 

Unit Volts-Phase (60 Hz)

208/230—1

208/230—1

208/230—1

208/230—1

208/230—1

208/230—1

Operating Voltage Range

187—253

187—253

187—253

187—253

187—253

187—253

Internal Circuit Protection

None

Full Load Amps

18.1/20.0

27.1/30.0

39.8/44.0

18.1/20.0

27.1/30.0

39.8/44.0

Minimum Ampacity for Wire Sizing

24.5/26.9

35.8/39.4

51.6/56.9

25.2/27.5

36.4/40.0

52.3/57.5

Minimum Wire Size†

10/10

8/8

6/6

10/10

8/8

6/6

Maximum Wire Length (Ft)†

112/112

117/117

122/122

112/112

117/117

125/125

Maximum Fuse Size (Amps or Ckt Bkr)

25/30

40/40

60/60

30/30

40/40

60/60

Control Transformer 24V (Va)

40

 

INDOOR COIL

 

Rows & Fins Per In.

3 & 14

Height x Width (In.)

18 x 17.8

22 x 17.8

Face Area (Sq Ft)

2.23

2.73

R-22 Refrigerant Metering Device-FF1DNA

Check-Flo-Rater

R-22 Refrigerant Metering Device-FF1DNE

TXV

Piston Number‡

63

70

Condensate Drain Connection (Pri-Sec)

3/4 FPT

 

INDOOR BLOWER & MOTOR

 

Wheel Diameter x Width (In.)

10 x 6

Filter Size—Cleanable (In.)

16 x 20 x 1

Blower Motor HP

1/5

1/3

Blower Motor Speeds & Type

2 (PSC)

Full Load Amps

1.5

2.0

 

OPTIONAL EQUIPMENT (P/N’s)

 

Louvered Wall Panel with Frame              (6 Pack)

KFBLG0106LGL

Electric Heat Package

See ‘‘Optional Field-Installed Electric Heat Packages’’ Table

Summary of Contents for FAN COIL UNITS FF1DNA

Page 1: ...t applications in con ditioned space Additional insulation is required if the unit is installed in an unconditioned space Unit is supplied with replaceable filter Multispeed direct drive PSC blower motors have been selected to provide the proper air handling for both heating and cooling Motors are suspended at 3 points on rubber grommets for qui eter operation All refrigerant lines electrical powe...

Page 2: ...F 1 D N A 018 075 Electric Heater kw 000 005 075 011 Nominal Capacity Btu 018 18 000 024 24 000 030 30 000 A Standard E TXV N 208 230 1 60 D Major Series 1 Upflow F Through the Wall F Fan Coil MODEL FF1DNA FF1DNE 018 024 030 Fan Rpm 2 Speed Motor HP PSC Wheel In 810 750 1 12 10 x 6 980 780 1 5 10 x 6 1110 950 1 3 10 x 6 Filter Permanent In 16 x 20 16 x 20 16 x 20 Connections Sweat Suction OD Liqui...

Page 3: ...IA SECONDARY DRAIN LOW VOLTAGE ENTRY 7 8 DIA HOLE POWER ENTRY 1 3 8 DIA KNOCKOUT 7 8 DIA HOLE 22 1 8 11 3 16 3 1 4 24 1 16 5 11 16 5 10 1 16 1 5 8 5 3 16 1 9 16 2 13 16 2 7 16 2 3 8 7 8 3 4 15 3 16 8 1 4 4 3 16 3 4 11 1 16 9 7 16 13 16 11 1 16 5 38 1 16 REFRIGERANT LINES ENTRY SUCTION 018 024 030 3 4 I D SWEAT LIQUID 3 8 I D SWEAT CONDENSATE 3 4 NPT UNIT CONNECTION SIZES NOTE 1 SERIES DESIGNATION ...

Page 4: ...Installed Electric Heat Packages Table UNITS WITH FACTORY INSTALLED ELECTRIC HEATERS OR CONTROLS SIZES 018005 018075 018011 RATINGS PERFORMANCES Nominal Capacity Btuh 18 000 18 000 18 000 Nominal Airflow CFM 650 650 650 Electric Heating Output kw 240v 5 0 7 5 11 0 Electric Heating Capacity MBH 208 230v 13 5 16 3 19 9 24 2 28 9 35 1 ELECTRICAL Unit Volts Phase 60 Hz 208 230 1 208 230 1 208 230 1 Op...

Page 5: ... Unit Volts Phase 60 Hz 208 230 1 208 230 1 208 230 1 208 230 1 208 230 1 208 230 1 Operating Voltage Range 187 253 187 253 187 253 187 253 187 253 187 253 Internal Circuit Protection None Full Load Amps 18 1 20 0 27 1 30 0 39 8 44 0 18 1 20 0 27 1 30 0 39 8 44 0 Minimum Ampacity for Wire Sizing 24 5 26 9 35 8 39 4 51 6 56 9 25 2 27 5 36 4 40 0 52 3 57 5 Minimum Wire Size 10 10 8 8 6 6 10 10 8 8 6...

Page 6: ...16 17 18 Sensible Heat Capacity 1000 Btuh Gross Cooling Capacity 1000 Btuh BF Bypass Factor NOTES 1 Net capacities shown include a deduction for evaporator fan motor heat 2 Contact manufacturer for cooling capacities at conditions other than shown in table 3 Formulas Leaving db entering db Leaving wb wb corresponding to enthalpy of air leaving coil hlwb hlwb hewb where hewb enthalpy of air enterin...

Page 7: ...20 580 665 540 610 475 540 380 415 Low 480 580 450 545 415 500 375 430 320 340 024 High 895 985 860 955 825 915 785 865 730 805 Low 650 740 620 710 585 680 550 640 510 600 030 High 1160 1190 1105 1135 1050 1080 990 1020 935 960 Low 885 1025 870 985 835 940 810 890 770 840 AIR DELIVERY CFM 400 500 600 700 800 900 1000 1100 Electric Heaters 1 Element 5 kw 0 007 0 010 0 015 0 025 0 035 0 055 0 070 0 ...

Page 8: ...iscussed in this manual including Unit Familiarization Maintenance Installation Overview Operating Sequence A large selection of product theory and skills programs is available using popular video based formats and materials All include video and or slides plus companion book Classroom Service Training plus hands on the products in our labs can mean increased confidence that really pays dividends ...

Reviews: