AIR DELIVERY (CFM) AT INDICATED EXTERNAL

STATIC PRESSURE AND VOLTAGE

 

NOTE: 

 

Data reflects a dry coil, filter, and 11-kw electric heater installed.

 

AIR DELIVERY PERFORMANCE CORRECTION

COMPONENT PRESSURE DROP (IN. WC) AT INDICATED AIRFLOW

 

Subtract the above pressure drop corrections from unit airflow data when that component or condition is used. The remaining external static pressure will be 
available for the duct system.

 

ESTIMATED SOUND POWER LEVEL (dBA)

 

* Estimated sound power levels have been derived using the method described in the 

 

1987 ASHRAE HVAC Systems & Applications Handbook, 

 

Chapter 52, p. 52.7.

 

OTHER ACCESSORIES

 

* 6 pack

 

EXTERNAL STATIC PRESSURE—IN. WC

UNIT

 SIZE

BLOWER MOTOR

SPEED

0.1

0.2

0.3

0.4

0.5

208V

230V

208V

230V

208V

230V

208V

230V

208V

230V

 

018

High

610

720

580

665

540

610

475

540

380

415

Low

480

580

450

545

415

500

375

430

320

340

024

High

895

985

860

955

825

915

785

865

730

805

Low

650

740

620

710

585

680

550

640

510

600

030

High

1160

1190

1105

1135

1050

1080

990

1020

935

960

Low

885

1025

870

985

835

940

810

890

770

840

 

AIR DELIVERY (CFM)

400

500

600

700

800

900

1000

1100

 

Electric 
Heaters

1-Element

5 kw

0.007

0.010

0.015

0.025

0.035

0.055

0.070

0.080

2-Element

7.5 & 11 kw

0.010

0.012

0.018

0.028

0.050

0.075

0.100

0.130

Dry-to-
Wet
Coil

018

0.019

0.029

0.036

0.043

024

0.030

0.039

0.051

0.062

0.076

030

0.058

0.070

0.082

0.091

 

UNIT

SIZE

CONDITIONS

OCTAVE BAND CENTER FREQUENCY*

CFM

Ext Static 

Pressure

63

125

250

500

1000

2000

4000

 

FF1-018

600

0.25

64.7

60.7

56.7

53.7

51.7

49.7

45.7

FF1-024

800

0.25

66.0

62.0

58.0

55.0

53.0

51.0

47.0

FF1-030

1000

0.25

67.0

63.0

59.0

56.0

54.0

52.0

48.0

 

KIT NUMBER

DESCRIPTION

USED ON SIZES

 

KFDCC0101DCC

Cooling Control Package

All

KFBLG0106LGL*

Louvered Wall Panel with Frame

All

Summary of Contents for FAN COIL UNITS FF1DNA

Page 1: ...t applications in con ditioned space Additional insulation is required if the unit is installed in an unconditioned space Unit is supplied with replaceable filter Multispeed direct drive PSC blower motors have been selected to provide the proper air handling for both heating and cooling Motors are suspended at 3 points on rubber grommets for qui eter operation All refrigerant lines electrical powe...

Page 2: ...F 1 D N A 018 075 Electric Heater kw 000 005 075 011 Nominal Capacity Btu 018 18 000 024 24 000 030 30 000 A Standard E TXV N 208 230 1 60 D Major Series 1 Upflow F Through the Wall F Fan Coil MODEL FF1DNA FF1DNE 018 024 030 Fan Rpm 2 Speed Motor HP PSC Wheel In 810 750 1 12 10 x 6 980 780 1 5 10 x 6 1110 950 1 3 10 x 6 Filter Permanent In 16 x 20 16 x 20 16 x 20 Connections Sweat Suction OD Liqui...

Page 3: ...IA SECONDARY DRAIN LOW VOLTAGE ENTRY 7 8 DIA HOLE POWER ENTRY 1 3 8 DIA KNOCKOUT 7 8 DIA HOLE 22 1 8 11 3 16 3 1 4 24 1 16 5 11 16 5 10 1 16 1 5 8 5 3 16 1 9 16 2 13 16 2 7 16 2 3 8 7 8 3 4 15 3 16 8 1 4 4 3 16 3 4 11 1 16 9 7 16 13 16 11 1 16 5 38 1 16 REFRIGERANT LINES ENTRY SUCTION 018 024 030 3 4 I D SWEAT LIQUID 3 8 I D SWEAT CONDENSATE 3 4 NPT UNIT CONNECTION SIZES NOTE 1 SERIES DESIGNATION ...

Page 4: ...Installed Electric Heat Packages Table UNITS WITH FACTORY INSTALLED ELECTRIC HEATERS OR CONTROLS SIZES 018005 018075 018011 RATINGS PERFORMANCES Nominal Capacity Btuh 18 000 18 000 18 000 Nominal Airflow CFM 650 650 650 Electric Heating Output kw 240v 5 0 7 5 11 0 Electric Heating Capacity MBH 208 230v 13 5 16 3 19 9 24 2 28 9 35 1 ELECTRICAL Unit Volts Phase 60 Hz 208 230 1 208 230 1 208 230 1 Op...

Page 5: ... Unit Volts Phase 60 Hz 208 230 1 208 230 1 208 230 1 208 230 1 208 230 1 208 230 1 Operating Voltage Range 187 253 187 253 187 253 187 253 187 253 187 253 Internal Circuit Protection None Full Load Amps 18 1 20 0 27 1 30 0 39 8 44 0 18 1 20 0 27 1 30 0 39 8 44 0 Minimum Ampacity for Wire Sizing 24 5 26 9 35 8 39 4 51 6 56 9 25 2 27 5 36 4 40 0 52 3 57 5 Minimum Wire Size 10 10 8 8 6 6 10 10 8 8 6...

Page 6: ...16 17 18 Sensible Heat Capacity 1000 Btuh Gross Cooling Capacity 1000 Btuh BF Bypass Factor NOTES 1 Net capacities shown include a deduction for evaporator fan motor heat 2 Contact manufacturer for cooling capacities at conditions other than shown in table 3 Formulas Leaving db entering db Leaving wb wb corresponding to enthalpy of air leaving coil hlwb hlwb hewb where hewb enthalpy of air enterin...

Page 7: ...20 580 665 540 610 475 540 380 415 Low 480 580 450 545 415 500 375 430 320 340 024 High 895 985 860 955 825 915 785 865 730 805 Low 650 740 620 710 585 680 550 640 510 600 030 High 1160 1190 1105 1135 1050 1080 990 1020 935 960 Low 885 1025 870 985 835 940 810 890 770 840 AIR DELIVERY CFM 400 500 600 700 800 900 1000 1100 Electric Heaters 1 Element 5 kw 0 007 0 010 0 015 0 025 0 035 0 055 0 070 0 ...

Page 8: ...iscussed in this manual including Unit Familiarization Maintenance Installation Overview Operating Sequence A large selection of product theory and skills programs is available using popular video based formats and materials All include video and or slides plus companion book Classroom Service Training plus hands on the products in our labs can mean increased confidence that really pays dividends ...

Reviews: