64
6.4.1.
Electric Heat
If you have a fan coil with electric heaters, this menu item will allow the heaters to
be exercised. With self--identifying electric heaters, three stages of electric heat are
available to be exercised in any combination. Non--identifying heaters will only
provide one stage of heat; or perhaps may have fixed--timed staging. See the
instructions provided with the electric heat accessory. After the selections are made,
touch
START
.
S
Low Heat:
Selectable from 0 to 120 minutes
d
Default = 5 minutes
S
Medium Heat:
Selectable from 0 to 120 minutes
d
Default = 5 minutes
S
High Heat:
Selectable from 0 to 120 minutes
d
Default = 5 minutes
6.4.2.
Furnace
Make sure the furnace is properly installed.
This option allows the furnace to be exercised. First, a low heat run time and high
heat run time are selected. The furnace will execute its ignition start--up sequence.
This sequence will be displayed on the screen. After the gas valve and blower
motor turn on, the screen will show the current operating status of the furnace. After
the selections are made, touch
START
.
S
Low Heat:
Selectable from 0 to 120 minutes
d
Default = 5 minutes
S
High Heat:
Selectable from 0 to 120 minutes
d
Default = 5 minutes
Summary of Contents for Evolution Connex Control
Page 108: ...99 A160170 NIM Chart...
Page 109: ...100 A160171 Wiring Diagram Single Stage Non Communicating Heat Pump NIM...
Page 110: ...101 A160172 Wiring Diagram Two Stage Non Communicating Heat Pump NIM...
Page 111: ...102 R G FE Fan Coil or Variable Speed Furnace A07114 G Input Wiring for Blower Operation...
Page 112: ...103 R G FE Fan Coil or Variable Speed Furnace A07115 G Input Wiring for System Shutdown...
Page 115: ...106 NOTES...