33
—
Table 28 — Fan Performance 581B072 — Horizontal Discharge Units; High-Static Motor (Belt Drive)*
LEGEND
*Motor drive range: 1300 to 1686 rpm. All other rpms require field-
supplied drive.
NOTES:
1.
Boldface
indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.90.
3. See below for general fan performance notes.
GENERAL FAN PERFORMANCE NOTES
1. Values include losses for filters, unit casing, and wet coils. See Fig. 38 and
Table 9 for accessory/FIOP static pressure information.
2. Extensive motor and electrical testing on these units ensures that the full range
of the motor can be utilized with confidence. Using the fan motors up to
the ratings shown will not result in nuisance tripping or premature motor failure.
Unit warranty will not be affected. See Tables 7 and 8 for additional information.
3. Use of a field-supplied motor may affect wire sizing. Contact your Bryant repre-
sentative to verify.
4. Interpolation is permissible. Do not extrapolate.
AIRFLOW
CFM
EXTERNAL STATIC PRESSURE (in. wg)
0.2
0.4
0.6
0.8
1.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
1800
913
0.64
569
1010
0.80
715
1098
0.98
869
1178
1.16
1032
1252
1.35
1203
1900
952
0.73
652
1046
0.91
805
1131
1.09
965
1210
1.28
1134
1282
1.48
1311
2000
992
0.84
744
1083
1.02
903
1166
1.21
1070
1242
1.40
1245
1313
1.61
1427
2100
1032
0.95
844
1120
1.14
1010
1200
1.33
1184
1275
1.54
1365
1345
1.75
1553
2200
1073
1.07
954
1158
1.27
1127
1236
1.47
1307
1308
1.68
1495
1377
1.90
1689
2300
1114
1.21
1074
1196
1.41
1254
1272
1.62
1440
1343
1.84
1634
1409
2.07
1834
2400
1155
1.36
1204
1234
1.57
1391
1308
1.78
1584
1377
2.01
1784
1443
2.24
1990
2500
1196
1.51
1345
1273
1.73
1538
1345
1.96
1738
1412
2.19
1945
1477
2.43
2157
2600
1238
1.69
1497
1312
1.91
1697
1382
2.14
1904
1448
2.38
2117
1511
2.63
2335
2700
1280
1.87
1660
1352
2.10
1867
1420
2.34
2081
1484
2.59
2300
1546
2.84
2526
2800
1322
2.07
1835
1392
2.31
2050
1458
2.56
2270
1521
2.81
2496
—
—
—
2900
1364
2.28
2023
1432
2.53
2245
1496
2.78
2472
—
—
—
—
—
—
3000
1406
2.50
2224
1472
2.76
2452
—
—
—
—
—
—
—
—
—
AIRFLOW
CFM
EXTERNAL STATIC PRESSURE (in. wg)
1.2
1.4
1.6
1.8
2.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
1800
1322
1.56
1382
1388
1.77
1568
1451
1.98
1762
1510
2.21
1962
1568
2.44
2169
1900
1351
1.68
1495
1416
1.90
1686
1477
2.12
1885
1536
2.35
2090
1593
2.59
2302
2000
1380
1.82
1617
1444
2.04
1814
1505
2.27
2017
1563
2.51
2227
1619
2.75
2443
2100
1411
1.97
1748
1473
2.20
1950
1533
2.43
2159
1590
2.67
2374
—
—
—
2200
1441
2.13
1890
1503
2.36
2097
1562
2.60
2311
1618
2.85
2532
—
—
—
2300
1473
2.30
2041
1533
2.54
2254
1591
2.79
2474
—
—
—
—
—
—
2400
1505
2.48
2203
1564
2.73
2422
—
—
—
—
—
—
—
—
—
2500
1537
2.68
2376
—
—
—
—
—
—
—
—
—
—
—
—
2600
1571
2.88
2560
—
—
—
—
—
—
—
—
—
—
—
—
2700
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
2800
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
2900
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
3000
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Bhp
—
Brake Horsepower
Watts
—