21

To control the minimum damper position remotely, remove
the factory-installed jumper on the P and P1 terminals on
the EconoMi$er IV controller. Wire the field-supplied poten-
tiometer to the P and P1 terminals on the EconoMi$er IV
controller. See Fig. 36.

Damper Movement

Damper movement from full open to full closed (or vice
versa) takes 2

1

/

2

 minutes. 

Thermostats

The EconoMi$er IV control works with conventional thermo-
stats that have a Y1 (cool stage 1), Y2 (cool stage 2), W1
(heat stage 1), W2 (heat stage 2), and G (fan). The
EconoMi$er IV control does not support space temperature
sensors. Connections are made at the thermostat terminal
connection board located in the main control box.

Occupancy Control

The factory default configuration for the EconoMi$er IV con-
trol is occupied mode. Occupied status is provided by the
black jumper from terminal TR to terminal N. When unoccu-
pied mode is desired, install a field-supplied timeclock func-
tion in place of the jumper between TR and N. See Fig. 27.
When the timeclock contacts are closed, the EconoMi$er IV
control will be in occupied mode. When the timeclock con-
tacts are open (removing the 24-v signal from terminal N),
the EconoMi$er IV will be in unoccupied mode.

Demand Controlled Ventilation (DCV)

When using the EconoMi$er IV for demand controlled venti-
lation, there are some equipment selection criteria which
should be considered. When selecting the heat capacity and
cool capacity of the equipment, the maximum ventilation
rate must be evaluated for design conditions. The maximum
damper position must be calculated to provide the desired
fresh air.

Typically the maximum ventilation rate will be about 5 to
10% more than the typical cfm required per person, using
normal outside air design criteria.

A proportional anticipatory strategy should be taken with
the following conditions: a zone with a large area, varied
occupancy, and equipment that cannot exceed the required
ventilation rate at design conditions. Exceeding the required
ventilation rate means the equipment can condition air at a
maximum ventilation rate that is greater than the required
ventilation rate for maximum occupancy. A proportional-
anticipatory strategy will cause the fresh air supplied to
increase as the room CO

2

 level increases even though the

CO

2

 set point has not been reached. By the time the CO

2

level reaches the set point, the damper will be at maximum
ventilation and should maintain the set point.

In order to have the CO

2

 sensor control the economizer

damper in this manner, first determine the damper voltage
output for minimum or base ventilation. Base ventilation is
the ventilation required to remove contaminants during
unoccupied periods. The following equation may be used to
determine the percent of outside-air entering the building for
a given damper position. For best results there should be at
least a 10 degree difference in outside and return-air tem-
peratures.

  T

O

 = Outdoor-Air Temperature

  OA = Percent of Outdoor Air

  T

R

 = Return-Air Temperature

  RA = Percent of Return Air

  T

M

 = Mixed-Air Temperature

Once base ventilation has been determined, set the mini-
mum damper position potentiometer to the correct position.

The same equation can be used to determine the occupied or
maximum ventilation rate to the building. For example, an
output of 3.6 volts to the actuator provides a base ventilation
rate of 5% and an output of 6.7 volts provides the maximum
ventilation rate of 20% (or base plus 15 cfm per person). Use
Fig. 37 to determine the maximum setting of the CO

2

 sensor.

For example, a 1100 ppm set point relates to a 15 cfm per
person design. Use the 1100 ppm curve on Fig. 37 to find the
point when the CO

2

 sensor output will be 6.7 volts. Line up

the point on the graph with the left side of the chart to deter-
mine that the range configuration for the CO

2

 sensor should

be 1800 ppm. The EconoMi$er IV controller will output the
6.7 volts from the CO

2

 sensor to the actuator when the CO

2

concentration in the space is at 1100 ppm. The DCV set point
may be left at 2 volts since the CO

2

 sensor voltage will be

ignored by the EconoMi$er IV controller until it rises above
the 3.6 volt setting of the minimum position potentiometer.

Once the fully occupied damper position has been deter-
mined, set the maximum damper demand control ventilation
potentiometer to this position. Do not set to the maximum
position as this can result in over-ventilation to the space
and potential high-humidity levels.

CO

2

 Sensor Configuration

The CO

2

 sensor has preset standard voltage settings that

can be selected anytime after the sensor is powered up. See
Table 5.

Use setting 1 or 2 for Bryant equipment. See Table 5.

1. Press Clear and Mode buttons. Hold at least 5 sec-

onds until the sensor enters the Edit mode.

2. Press Mode twice. The STDSET Menu will appear.

3. Use the Up/Down button to select the preset number.

See Table 5.

4. Press Enter to lock in the selection.

5. Press Mode to exit and resume normal operation.

The custom settings of the CO

2

 sensor can be changed any-

time after the sensor is energized. Follow the steps below to
change the non-standard settings:

1. Press Clear and Mode buttons. Hold at least 5 sec-

onds until the sensor enters the Edit mode.

2. Press Mode twice. The STDSET Menu will appear.

3. Use the Up/Down button to toggle to the NONSTD

menu and press Enter.

4. Use the Up/Down button to toggle through each of

the nine variables, starting with Altitude, until the
desired setting is reached.

5. Press Mode to move through the variables.

6. Press Enter to lock in the selection, then press Mode

to continue to the next variable.

Dehumidification of Fresh Air with DCV Control

Information from ASHRAE indicates that the largest humid-
ity load on any zone is the fresh air introduced. For some
applications, a device such as an energy recovery unit is
added to reduce the moisture content of the fresh air being
brought into the building when the enthalpy is high. In most
cases, the normal heating and cooling processes are more
than adequate to remove the humidity loads for most com-
mercial applications.

If normal rooftop heating and cooling operation is not ade-
quate for the outdoor humidity level, an energy recovery unit
and/or a dehumidification option should be considered.

(T

O

 x

OA

) +  (T

R

 x

RA

) = T

M

100

100

Summary of Contents for DURAPAC PLUS 581B

Page 1: ...ns shipped with curb See Fig 2 Install insulation cant strips roofing felt and counter flashing as shown Duct work must be attached to curb If gas is to be routed through the curb attach the accessory...

Page 2: ...ed to initiate both stages of heat when the temperature is below 45 F Indoor comfort may be compromised when these lower air tempera tures are used with insufficient heating temperature rise III STEP...

Page 3: ...arance 4 ft on each side 7 Direction of airflow 8 Connector packages CRBTMPWR001A01 and 002A01 are for thru the curb type gas Packages CRBTMPWR003A01 and 004A01 are for thru the bottom type gas connec...

Page 4: ...equate combustion and ventilation air space must be pro vided for proper operation of this equipment Be sure that installation complies with all local codes and Section 5 3 Air for Combustion and Vent...

Page 5: ...When connecting the gas line to the unit gas valve the installer MUST use a backup wrench to prevent damage to the valve NOTES 1 Place unit on curb as close as possible to the duct end 2 Dimension in...

Page 6: ...anced Copper Tubes Aluminum Double Wavy Fins Acutrol Metering Device Standard Unit Rows Fins in 2 15 2 15 4 15 4 15 Total Face Area sq ft 5 5 5 5 5 5 5 5 Unit with Perfect Humidity Dehumidification Sy...

Page 7: ...Stage 14 14 14 14 Second Stage 14 14 14 14 Gas Input Btuh First Stage Second Stage 3 phase units 072 50 000 72 000 50 000 72 000 50 000 72 000 50 000 72 000 115 82 000 115 000 82 000 115 000 82 000 1...

Page 8: ...8 Fig 7 Base Unit Dimensions 581B036 072...

Page 9: ...described in Steps 1 4 below 1 If mounted on a roof curb and electrical power is to be run through the basepan an accessory thru the bot tom connection kit is required This is available through the l...

Page 10: ...igured for A C operation Fig 11 Low Voltage Connections With or Without Economizer Field Wiring Fig 12 Field Control Wiring Raceway LEGEND C Contactor COMP Compressors EQUIP Equipment GND Ground IFC I...

Page 11: ...18 5 25 25 18 18 90 90 460 3 60 414 508 5 1 39 0 0 4 2 2 30 9 0 20 9 46 575 3 60 518 632 4 2 31 0 0 4 2 2 30 7 3 20 7 37 048 4 Tons 208 230 1 60 187 254 1 23 7 126 0 0 7 4 9 60 35 2 35 2 45 45 34 34 1...

Page 12: ...TAGE V Ph Hz VOLTAGE RANGE COMPRESSOR each OFM each IFM COMBUSTION FAN MOTOR POWER SUPPLY MINIMUM UNIT DISCONNECT SIZE Min Max Qty RLA LRA FLA FLA RLA MCA MOCP FLA LRA 036 208 230 3 60 187 254 1 10 3...

Page 13: ...cor ner post to the 24 v barrier located on the left side of the control box See Fig 12 The raceway provides the UL required clearance between high and low voltage wiring 3 A field supplied relay must...

Page 14: ...Remove and save 6 screws 3 on each side from sides of the manual outdoor air damper 7 Align screw holes on hood with screw holes on side of manual outdoor air damper See Fig 18 and 19 Secure hood wit...

Page 15: ...the economizer The EconoMi er IV controller is mounted on top of the EconoMi er IV in the position shown in Fig 21 To remove the component box from its shipping posi tion remove the screw holding the...

Page 16: ...shown in Fig 28 Outdoor air leakage is shown in Fig 29 Return air pressure drop is shown in Fig 30 F EconoMi er IV Standard Sensors Outdoor Air Temperature OAT Sensor The outdoor air temperature senso...

Page 17: ...he secondary of the transformer grounded 3 For field installed remote minimum position POT remove black wire jumper between P and P1 and set control minimum position POT to the minimum position Fig 27...

Page 18: ...additional acces sory dry bulb sensor part number CRTEMPSN002A00 The accessory sensor must be mounted in the return airstream See Fig 34 Wiring is provided in the EconoMi er IV wiring harness See Fig...

Page 19: ...int EXH SET potentiometer See Fig 32 The set point represents the damper position above which the exhaust fans will be turned on When there is a call for exhaust the EconoMi er IV controller provides...

Page 20: ...4 75 24 80 27 80 27 85 29 90 32 95 35 100 38 APPROXIMATE DRY BULB TEMPERATURE F C A A B B C C D D R E L A T I V E H U M I D I T Y HIGH LIMIT CURVE TR1 24 Vac COM TR 24 Vac HOT 1 2 3 4 5 EF EF1 _ P1 T1...

Page 21: ...xed Air Temperature Once base ventilation has been determined set the mini mum damper position potentiometer to the correct position The same equation can be used to determine the occupied or maximum...

Page 22: ...e and tighten mounting nuts see Fig 39 3 Adjust bolt and nut on mounting plate to secure motor in fixed position Table 6A 581B Fan Rpm at Motor Pulley Setting With Standard Motor Approximate fan rpm s...

Page 23: ...NUOUS BHP MAXIMUM OPERATING WATTS UNIT VOLTAGE MAXIMUM AMP DRAW 036 Single 1 20 1000 208 230 4 9 Three 1 20 1000 208 230 4 9 460 2 2 575 2 2 048 Single 1 20 1000 208 230 4 9 Three 1 20 1000 208 230 4...

Page 24: ...V 0 045 0 065 0 08 0 12 0 145 0 175 0 22 0 255 Horizontal EconoMi er IV 0 1 0 125 0 15 0 18 0 225 0 275 FIOP Factory Installed Option UNIT 581B ARI RATING decibels OCTAVE BANDS 63 125 250 500 1000 200...

Page 25: ...71 702 1249 0 77 765 1000 1041 0 59 587 1104 0 67 662 1163 0 74 737 1219 0 81 811 1272 0 89 883 1100 1066 0 68 674 1129 0 76 759 1188 0 85 843 1243 0 93 925 1296 1 01 1007 1200 1093 0 77 767 1155 0 8...

Page 26: ...tts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1200 1093 0 77 767 1155 0 87 861 1213 0 96 955 1268 1 05 1047 1321 1 14 1137 1300 1119 0 87 866 1181 0 98 970 1239 1 08 1073 1294 1 18 1175 1346 1 28 1275...

Page 27: ...1900 1438 1 57 1391 1504 1 73 1537 1567 1 90 1685 1626 2 06 1833 1682 2 23 1983 2000 1471 1 72 1523 1536 1 89 1677 1598 2 06 1831 1657 2 24 1986 2100 1504 1 87 1665 1569 2 06 1825 1630 2 24 1986 2200...

Page 28: ...90 1686 1600 2 06 1833 1660 2 23 1977 1718 2 38 2118 2100 1502 1 89 1681 1568 2 07 1840 1631 2 25 1996 2200 1535 2 06 1834 1600 2 25 2002 2300 1569 2 25 1996 2400 2500 2600 2700 2800 2900 3000 Bhp Br...

Page 29: ...1000 1042 0 70 700 1107 0 83 825 1168 0 96 956 1225 1 10 1091 1100 1065 0 77 765 1130 0 90 896 1190 1 04 1032 1247 1 18 1173 1200 1089 0 84 837 1153 0 98 974 1213 1 12 1115 1300 1113 0 92 915 1177 1...

Page 30: ...1201 1 15 1149 1500 1163 1 10 1092 1600 1189 1 20 1191 1700 1800 1900 2000 Bhp Brake Horsepower Watts Input Watts to Motor AIRFLOW CFM EXTERNAL STATIC PRESSURE in wg 0 2 0 4 0 6 0 8 1 0 Rpm Bhp Watts...

Page 31: ...CFM EXTERNAL STATIC PRESSURE in wg 0 2 0 4 0 6 0 8 1 0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1500 800 0 39 350 904 0 49 438 999 0 60 535 1087 0 72 640 1169 0 85 753 16...

Page 32: ...65 1 32 1173 1432 1 48 1313 1497 1 64 1459 1559 1 82 1612 1800 1321 1 28 1137 1390 1 43 1273 1455 1 59 1415 1518 1 76 1563 1579 1 93 1718 1900 1348 1 40 1243 1415 1 56 1381 1479 1 72 1526 1541 1 89 16...

Page 33: ...1 02 903 1166 1 21 1070 1242 1 40 1245 1313 1 61 1427 2100 1032 0 95 844 1120 1 14 1010 1200 1 33 1184 1275 1 54 1365 1345 1 75 1553 2200 1073 1 07 954 1158 1 27 1127 1236 1 47 1307 1308 1 68 1495 137...

Page 34: ...lastic caps identify these valves These valves have O rings inside which screw the cap onto a brass body to prevent leaks No field access to these valves is available at this time Ensure the plastic c...

Page 35: ...induced draft motor will start 5 After a call for heating the main burners should light within 5 seconds If the burner does not light then there is a 22 second delay before another 5 second try If th...

Page 36: ...roportionally As the CO2 level decreases because of the increase in fresh air the outdoor air damper will be proportionally closed Damper position will follow the higher demand condition from DCV mode...

Page 37: ...extremely low sensible heat ratio capability Similar to the subcooling mode of operation hot gas reheat mode operates only when the outside air temperature is warmer than 40 F Below this temperature a...

Page 38: ...same dimensions as original filters E Outdoor Air Inlet Screens Clean screen with steam or hot water and a mild detergent Do not use disposable filters in place of screen II LUBRICATION A Compressors...

Page 39: ...t only the subcooling reheat dehumidification coil liquid line solenoid valve be energized The subcooling reheat dehumid ification coil liquid line solenoid valve MUST be energized to use the charging...

Page 40: ...40 Fig 48 Cooling Charging Chart Standard 581B036 Fig 49 Cooling Charging Chart Standard 581B048 Fig 50 Cooling Charging Chart Standard 581B060 Fig 51 Cooling Charging Chart Standard 581B072...

Page 41: ...rfect Humidity Dehumidification System NOTE When using the charging charts it is important that only the subcooling reheat dehu midification coil liquid line solenoid valve be energized The subcooling...

Page 42: ...lems when the power supply is uninterrupted The LED can be observed through the viewport When a break in power occurs the IGC will be reset resulting in a loss of fault history and the evaporator fan...

Page 43: ...HEAT UNITS 60 000 BTUH INPUT 581B036060N 581B048060N 581B060060N 72 000 BTUH INPUT 581B036071 581B036072 581B048071 581B048072 581B060071 581B060072 581B072072 MEDIUM AND HIGH HEAT UNITS 90 000 BTUH I...

Page 44: ...Ignitor IDM Induced Draft Motor IFC Indoor Fan Contactor IFM Indoor Fan Motor IGC Integrated Gas Unit Controller LPS Low Pressure Switch LS Limit Switch MGV Main Gas Valve Splice Splice Marked Factory...

Page 45: ...with range on unit nameplate information Ignition Lockout LED 5 Flashes Unit unsuccessfully attempted ignition for 15 minutes Check ignitor and flame sensor electrode spacing gaps etc Ensure that flam...

Page 46: ...Check orifice to burner alignment Burners Will Not Turn Off Unit is locked into Heating mode for a one minute minimum Wait until mandatory one minute time period has elapsed or reset power to unit PR...

Page 47: ...eplace Restriction in refrigerant system Locate restriction and remove Compressor Operates Continuously Dirty air filter Replace filter Unit undersized for load Decrease load or increase unit size The...

Page 48: ...ed Ventilation and Power Exhaust To check DCV and Power Exhaust 1 Make sure EconoMi er IV preparation procedure has been performed 2 Ensure terminals AQ and AQ1 are open The LED for both DCV and Exhau...

Page 49: ...ng 24 vac Occupied no power Unoccupied Modulation is based on the supply air sensor signal Modulation is based on the DCV signal Modulation is based on the greater of DCV and supply air sensor signals...

Page 50: ...ping 4 9 34 Gas pressure 1 7 Heat anticipator settings 7 9 Heat exchanger 7 High flow valves 34 High pressure switch 7 Horizontal units 1 2 Humidistat 13 Indoor air quality sensor 19 Integrated gas co...

Page 51: ......

Page 52: ...PER INSTALLATION INSTRUCTIONS CHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS CHECK GAS PIPING FOR LEAKS CHECK THAT RETURN INDOOR AIR FILTERS ARE CLEAN AND IN PLACE VERIFY THAT UNIT INSTA...

Reviews: