27
—
IV. EVAPORATOR FAN SERVICE AND REPLACEMENT
The 558F units use a fan motor mounting system that fea-
tures a slide-out motor mounting plate. To replace or service
the motor, slide out the bracket. See Fig. 34.
1. Remove the evaporator-fan access panel and the
heating control access panel.
2. Remove the center post (located between the evapora-
tor fan and heating control access panels) and all
screws securing it.
3. Loosen nuts on the two carriage bolts in the motor
mounting base.
4. Using jacking bolt under motor base, raise motor to
top of slide and remove belt. Secure motor in this
position by tightening the nuts on the carriage bolts.
5. Remove the belt drive.
6. Remove jacking bolt and tapped jacking bolt plate.
7. Remove the 2 screws that secure the motor mounting
plate to the motor support channel.
8. Remove the 3 screws from the end of the motor sup-
port channel that interfere with the motor slide path.
9. Slide out the motor and motor mounting plate.
10. Disconnect wiring connections and remove the
4 mounting bolts.
11. Remove the motor.
12. To install the new motor, reverse Steps 1-11.
V. BELT TENSION ADJUSTMENT
To adjust belt tension:
1. Loosen fan motor bolts.
2. Adjust belt tension:
Turn motor jacking bolt to move motor mounting
plate up or down for proper belt tension (
3
/
8
in. deflec-
tion at midspan with one finger [9 lb force]).
3. Tighten nuts.
4. Adjust bolts and nut on mounting plate to secure
motor in fixed position.
VI. CONDENSER-FAN ADJUSTMENT
A. 558F180,210,300 Units (Fig. 35)
1. Shut off unit power supply.
2. Remove access panel(s) closest to the fan to be
adjusted.
3. Loosen fan hub setscrews.
4. Adjust fan height on shaft using a straightedge
placed across the fan orifice.
5. Tighten setscrews and replace panel(s).
6. Turn on unit power.
B. 558F240 Units (Fig. 36)
1. Shut off unit power supply.
2. Remove fan top-grille assembly and loosen fan hub
screws.
3. Adjust fan height on unit, using a straightedge
placed across the fan orifice.
4. Tighten setscrews and replace rubber hubcap to pre-
vent hub from rusting to motor shaft.
5. Fill hub recess with permagum if rubber hubcap is
missing.
Fig. 33 — Evaporator-Fan Pulley Alignment
and Adjustment
NOTE:
A 3
1
/
2
-in. bolt and threaded plate are included in the installer’s
packet. They should be added to the motor support channel below the
motor mounting plate to aid in raising the motor. The plate part number
is 50DP503842. The adjustment bolt is
3
/
8
-16 x 1
3
/
4
in.-LG.
Fig. 34 — Evaporator-Fan Motor Section
Summary of Contents for DURAPAC 558F
Page 2: ...2 Fig 1A Roof Curb Details 558F180 240...
Page 3: ...3 Fig 1B Roof Curb Details 558F300...
Page 5: ...5 Fig 4 Base Unit Dimensions 558F180 210...
Page 6: ...6 Fig 5 Base Unit Dimensions 558F240...
Page 36: ......
Page 37: ......
Page 39: ......