Bryant DURAPAC 558F Installation & Service Instructions Manual Download Page 26

26

As the refrigerant leaves the evaporator, the refrigerant
passes a subcooler control low-pressure switch (S-LPS1 for
circuit 1 or S-LPS2 for circuit 2) in the suction line. This low-
pressure switch will deactivate the Perfect Humidity™ pack-
age when the suction pressure reaches 60 psig. The
subcooler control low-pressure switch is an added safety
device to protect against evaporator coil freeze-up during low
ambient operation. The subcooler control low-pressure
switch will only deactivate the 3-way liquid line solenoid
valve in the Perfect Humidity circuit. The compressors will
continue to run as long as there is a call for cooling, regard-
less of the position of the subcooler control low-pressure
switch. The     3-way solenoid valve and the Perfect Humidity
package will be reactivated only when the call for cooling has
been satisfied, the subcooler control low-pressure switch has
closed above 80 psig, and a new call for cooling exists. The
crankcase heaters on the scroll compressors provide addi-
tional protection for the compressors due to the additional
refrigerant charge in the subcooler.

When the humidistat or light commercial thermidistat con-
trol is satisfied, the control cuts power to and deenergizes
the LLSVs. The refrigerant is routed back through the evap-
orators and the subcooler coils are removed from the refrig-
erant loops. When the thermostat is satisfied, C1 and C2 are
deenergized and the compressors, IFM, and OFMs shut off.
If the thermostat fan selector switch is in the ON position,
the IFM will run continuously.

SERVICE

I. CLEANING

Inspect unit interior at beginning of each heating and cooling
season and as operating conditions require. Remove unit top
panel and/or side panels for access to unit interior.

A. Evaporator Coil

Clean as required with a commercial coil cleaner.

NOTE: 

The 558F300 unit has a mist eliminator screen

attached to the evaporator coil to prevent condensate runoff
at high wet-bulb conditions. Check periodically and clean as
necessary.

B. Condenser Coil

Clean condenser coil annually and as required by location
and outdoor-air conditions. Inspect coil monthly — clean as
required.

C. Condensate Drain

Check and clean each year at start of cooling season.

D. Filters

Clean or replace at start of each heating and cooling season,
or more often if operating conditions require. Refer to Table 1
for type and size.

NOTE: 

The 558F300 unit requires industrial grade throw-

away filters capable of withstanding face velocities up to
625 fpm. Ensure that replacement filters for the 558F300
units are rated for 625 fpm.

E. Outdoor-Air Inlet Screen

Clean screens with steam or hot water and a mild detergent.
Do not use throwaway filters in place of screens.

II. LUBRICATION

A. Compressors

Each compressor is charged with the correct amount of oil at
the factory. Conventional white oil (Sontext 200LT) is used.
White oil is compatible with 3GS oil, and 3GS oil may be
used if the addition of oil is required. See compressor name-
plate for original oil charge. A complete recharge should be
four ounces less than the original oil charge. When a com-
pressor is exchanged in the field it is possible that a major
portion of the oil from the replaced compressor may still be
in the system. While this will not affect the reliability of the
replacement compressor, the extra oil will add rotor drag and
increase power usage. To remove this excess oil, an access
valve may be added to the lower portion of the suction line at
the inlet of the compressor. The compressor should then be
run for 10 minutes, shut down, and the access valve opened
until no oil flows. This should be repeated twice to make sure
the proper oil level has been achieved.

B. Fan Shaft Bearings

The bearings are of the pillow block type and have grease fit-
tings. The bearing opposite the motor end has an extended
tube line so it can be lubricated from the motor side. Lubri-
cate the bearings twice annually.

Typical lubricants are given below:

*Preferred lubricant because it contains rust and oxidation inhibitors.

C. Condenser and Evaporator-Fan Motor Bearings

The condenser and evaporator-fan motors have permanently
sealed bearings, so no field lubrication is necessary.

III. EVAPORATOR FAN PERFORMANCE ADJUSTMENT
(Fig. 33 and 34)

Fan motor pulleys are factory set for speed shown in Table 1.

To change fan speeds:

1. Shut off unit power supply.

2. Loosen nuts on the 2 carriage bolts in the motor

mounting base. Install jacking bolt and plate under
motor base (bolt and plate are shipped in installer’s
packet). See Fig. 34. Using bolt and plate, raise motor
to top of slide and remove belt. Secure motor in this
position by tightening the nuts on the carriage bolts.

3. Loosen movable-pulley flange setscrew (see Fig. 33).

4. Screw movable flange toward fixed flange to increase

speed and away from fixed flange to decrease speed.
Increasing fan speed increases load on motor. Do not
exceed maximum speed specified in Table 1.

See Table 7 for air quantity limits.

5. Set movable flange at nearest keyway of pulley hub

and tighten setscrew. (See Table 1 for speed change
for each full turn of pulley flange.)

6. Replace and tighten belts. See Belt Tension Adjust-

ment section on page 27.

To align fan and motor pulleys:

1. Loosen fan pulley setscrews.

2. Slide fan pulley along fan shaft.

3. Make angular alignment by loosening motor from

mounting plate.

WARNING: 

 Before performing service or mainte-

nance operations on unit, turn off main power switch
to unit and install lockout tag on disconnect switch.
Turn off accessory heater power switch if applicable.
Electrical shock could cause personal injury.

MANUFACTURER

LUBRICANT

Texaco

Regal AFB-2*

Mobil

Mobilplex EP No. 1

Sunoco

Prestige 42

Texaco

Multifak 2

Summary of Contents for DURAPAC 558F

Page 1: ...nd counter flashing as shown Ductwork can be secured to roof curb before unit is set in place IMPORTANT The gasketing of the unit to the roof curb or adapter roof curb is critical for a leak proof sea...

Page 2: ...2 Fig 1A Roof Curb Details 558F180 240...

Page 3: ...3 Fig 1B Roof Curb Details 558F300...

Page 4: ...inserting hooks into unit base rails as shown Use corner post from packaging to protect coil from damage Use bumper boards for spreader bars 5 Weights do not include optional EconoMi er See Fig 4 6 fo...

Page 5: ...5 Fig 4 Base Unit Dimensions 558F180 210...

Page 6: ...6 Fig 5 Base Unit Dimensions 558F240...

Page 7: ...x access Right Side 4 0 1219 for proper operation of damper and power exhaust if so equipped Top 6 0 1829 to assure proper condenser fan operation Local codes or jurisdiction may prevail 7 With the ex...

Page 8: ...Fins in 4 15 4 15 4 15 4 15 Total Face Area sq ft 17 5 17 5 17 5 17 5 EVAPORATOR FAN Centrifugal Type Quantity Size in 2 12x12 2 12 x 12 2 12 x 12 2 12 x 12 Type Drive Belt Belt Belt Belt Nominal Cfm...

Page 9: ...ovided in drain hole and must be removed when unit is operating One 3 4 in half coupling is provided inside unit evaporator sec tion for condensate drain connection An 81 2 in x 3 4 in diameter nipple...

Page 10: ...option according to the installation instructions included with the accessory Locate thermostat assembly on a solid wall in the conditioned space to sense average temperature Route thermostat cable o...

Page 11: ...10 208 230 187 253 30 1 225 28 8 195 3 0 5 1 7 5 0 15 8 15 8 87 87 110 110 4 6 18 8 92 92 110 110 26 34 71 82 109 122 110 125 4 6 18 8 26 34 71 82 114 128 125 150 42 56 117 135 166 155 175 175 4 6 18...

Page 12: ...CA calculation for 558F units with electric heaters over 50 kW 1 25 x IFM amps 1 00 x heater FLA 4 Use the following table to determine heater capacity at actual voltage EXAMPLE 34 kW at 230 v heater...

Page 13: ...osition and close the door The handle should fit over the end of the shaft when the door is closed 8 The handle must be in the OFF position to open the control box door D Optional Convenience Outlet O...

Page 14: ...Sensor Installation Perform the following procedure to install the outdoor air enthalpy sensor part no CROUTENT001A00 1 Remove the outdoor air temperature sensor cover See Fig 22 Save cover and screw...

Page 15: ...Discharge Air Thermistor DAT The discharge air thermistor is factory mounted on the supply fan housing in the fan section of the unit The DAT is factory wired to the EconoMi er Control Module E CO2 C...

Page 16: ...ation air Either put the thermostat in the continuous fan mode or jumper the R and G terminals at the rooftop unit connection board Table 4 EconoMi er Switchover Control Strategy Must be selected manu...

Page 17: ...t and Winter Start Kit purchased separately The Motormaster I device controls outdoor fan no 1 while outdoor fans no 2 and 3 are sequenced off by the Accessory Fan Motor Sequencing Kit Accessory Fan M...

Page 18: ...t Control 10 F Installation 558F180 210 300 Install Field Fabricated Wind Baffles Wind baffles must be field fabricated for all units to ensure proper cooling cycle operation at low ambient temperatur...

Page 19: ...er I Sensor Locations NOTE All sensors are located on the eighth hairpin up from the bottom Fig 28 Motormaster III Sensor Locations 558F180 558F210 558F240 Fig 29 Typical Perfect Humidify Dehumidifica...

Page 20: ...mal start up levels NOTE When compressors are rotating in the wrong direc tion the unit will have increased noise levels and will not provide heating and cooling After a few minutes of reverse operati...

Page 21: ...86 4143 1142 5 23 4461 1193 5 61 4781 AIRFLOW Cfm AVAILABLE EXTERNAL STATIC PRESSURE in wg 1 4 1 6 1 8 2 0 2 2 2 4 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts...

Page 22: ...91 5810 8 000 1242 6 44 5415 1289 6 80 5714 1334 7 16 6018 1357 7 34 6171 1379 7 52 6325 8 500 1279 7 10 5966 1324 7 45 6268 1368 7 82 6573 1389 8 00 6728 1411 8 18 6883 9 000 1317 7 80 6561 1360 8 1...

Page 23: ...54 3752 1069 4 91 4060 1123 5 29 4375 1174 5 68 4 698 8 000 948 4 43 3667 1005 4 80 3969 1060 5 17 4278 1112 5 56 4593 1163 5 94 4915 1213 6 34 5 243 8 500 1001 5 11 4226 1054 5 49 4537 1106 5 87 4853...

Page 24: ...er modulates to the minimum position when the IFM is energized The EconoMi er provides Stage 1 of cooling by modulating the return and outdoor air dampers to main tain a 55 F supply air set point If...

Page 25: ...ehumidification cir cuits are always energized If Perfect Humidity circuit modulation is desired a field installed wall mounted humidistat or light commercial ther midistat is required If the Perfect...

Page 26: ...ressor is charged with the correct amount of oil at the factory Conventional white oil Sontext 200LT is used White oil is compatible with 3GS oil and 3GS oil may be used if the addition of oil is requ...

Page 27: ...just belt tension 1 Loosen fan motor bolts 2 Adjust belt tension Turn motor jacking bolt to move motor mounting plate up or down for proper belt tension 3 8 in deflec tion at midspan with one finger 9...

Page 28: ...FLASH code will not be cleared and the EconoMi er will remain in the safe operation mode The sensor fault must be corrected to enable EconoMi er to revert to normal operation If the CONFIG button is p...

Page 29: ...e subcooler coil A tap is provided on the unit to measure liquid pressure entering the sub cooler leaving the condenser X FILTER DRIER Replace whenever refrigerant system is exposed to atmosphere XI P...

Page 30: ...r Motor CR Control Relay CT Current Transformer DAT Discharge Air Thermistor DM Damper Motor DU Dummy Terminal EC Enthalpy Control EQUIP Equipment FL Fuse Link FLA Full Load Amps FPT Freeze Protection...

Page 31: ...31 Fig 38 Typical Wiring Schematic 558F240 208 230 3 60 Shown ELECTRIC HEAT 208 240 v Amps 200 230 v kW A 71 3 82 3 25 7 34 2 B 117 135 42 2 56 1 C 156 180 56 2 74 8...

Page 32: ...32 Fig 38 Typical Wiring Schematic 558F240 208 230 3 60 Shown cont Fig 39 Typical Component Arrangement 558F240 Shown...

Page 33: ...place Restriction in refrigerant system Locate restriction and remove Compressor operates continuously Dirty air filter Replace filter Unit undersized for load Decrease load or increase unit size Ther...

Page 34: ...t MIN POS to 100 to verify operation and then set to correct setting EconoMi er Changeover Set Point Set Too High or Too Low Set at correct value See Table 5 Discharge Air Thermistor Faulty If STATUS...

Page 35: ...Cleaning 26 Installation 14 15 Size 8 Filter drier 29 Freeze protection thermostat 8 29 Heat anticipator settings 14 High pressure switch 8 29 Horizontal adapter roof curb 4 Humidistat 18 20 Low pres...

Page 36: ......

Page 37: ......

Page 38: ...selection of product theory and skills programs are available using popular video based for mats and materials All include video and or slides plus companion book Classroom Service Training which incl...

Page 39: ......

Page 40: ...E PROPERLY TENSIONED VERIFY THAT SCROLL COMPRESSOR IS ROTATING IN THE CORRECT DIRECTION VERIFY THAT CRANKCASE HEATER HAS BEEN ENERGIZED FOR 24 HOURS II START UP ELECTRICAL SUPPLY FAN AMPS EXHAUST FAN...

Reviews: