23
—
Table 11 — Fan Performance — 558F300*
LEGEND
*Standard low-medium static drive range is 1066 to 1283 rpm. Alternate high-
static drive range is 1332 to 1550. Other rpms require a field-supplied drive.
NOTES:
1. Maximum continuous bhp is 10.20 (208/230 v) or 11.80 (460 v) and the
maximum continuous watts are 9510 (208/230 v) or 11,000 (460 v). Do not
adjust motor rpm such that motor maximum bhp and/or watts is exceeded at
the maximum operating cfm.
2. See below for general fan performance notes.
GENERAL FAN PERFORMANCE NOTES
NOTES:
1. Values include losses for filters, unit casing, and wet coils. See Table 12
below for accessory/factory-installed option static pressure information.
2. Extensive motor and electrical testing on these units ensures that the full
range of the motor can be utilized with confidence. Using your fan motors up
to the wattage ratings shown will not result in nuisance tripping or premature
motor failure. Unit warranty will not be affected. See Table 14 for Evaporator-
Fan Motor Performance on page 24 for additional information.
3. Use of a field-supplied motor may affect wire sizing. Contact your Bryant
representative for details.
4. Interpolation is permissible. Do not extrapolate.
Table 12 — Accessory/FIOP Static Pressure (in. wg)* — 558F180-300
LEGEND
*The static pressure must be added to external static pressure. The
sum and the evaporator entering-air cfm should then be used in con-
junction with the Fan Performance tables to determine blower rpm and
watts.
AIRFLOW
(Cfm)
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
0.2
0.4
0.6
0.8
1.0
1.2
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
7,000
845
3.26
2693
909
3.60
2979
969
3.96
3272
1028
4.32
3574
1083
4.70
3883
1137
5.08
4,200
7,500
896
3.82
3156
956
4.17
3450
1014
4.54
3752
1069
4.91
4060
1123
5.29
4375
1174
5.68
4,698
8,000
948
4.43
3667
1005
4.80
3969
1060
5.17
4278
1112
5.56
4593
1163
5.94
4915
1213
6.34
5,243
8,500
1001
5.11
4226
1054
5.49
4537
1106
5.87
4853
1156
6.26
5175
1205
6.66
5504
1253
7.06
5,838
9,000
1053
5.85
4836
1104
6.23
5155
1154
6.63
5478
1202
7.02
5808
1248
7.43
6142
1294
7.84
6,483
9,500
1106
6.65
5498
1155
7.04
5824
1202
7.44
6155
1248
7.85
6492
1293
8.26
6833
1336
8.68
7,179
10,000
1159
7.52
6214
1206
7.92
6547
1251
8.33
6886
1295
8.74
7229
1338
9.16
7577
1380
9.59
7,929
10,500
1213
8.45
6984
1257
8.86
7325
1300
9.28
7671
1342
9.70
8020
1384
10.13
8375
1424
10.56
8,733
11,000
1266
9.45
7810
1309
9.87
8159
1350
10.29
8511
1391
10.73
8868
1431
11.16
9229
1470
11.60
9,594
11,250
1293
9.97
8245
1334
10.40
8597
1375
10.83
8953
1415
11.26
9313
1454
11.70
9677
1493
12.15
10,045
AIRFLOW
(Cfm)
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
1.4
1.6
1.8
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
7,000
1189
5.47
4,524
1239
5.87
4,854
1288
4.91
5191
7,500
1224
6.08
5,026
1272
6.48
5,362
1320
5.56
5703
8,000
1261
6.75
5,577
1307
7.16
5,917
1353
6.26
6263
8,500
1299
7.47
6,177
1344
7.89
6,523
1388
7.02
6873
9,000
1338
8.26
6,828
1382
8.68
7,179
1424
7.85
7534
9,500
1379
9.11
7,530
1421
9.54
7,887
1462
8.74
8247
10,000
1421 10.02
8,286
1461
10.46
8,648
1501
9.70
9014
10,500
1464 11.00
9,096
1503
11.45
9,464
1541
10.73
9835
11,000
1508 12.05
9,963
1546
12.50
10,336
—
—
—
11,250
1530 12.60
10,417
—
—
—
—
—
—
Bhp
—
Brake Horsepower
Watts —
Input Watts to Motor
COMPONENT
CFM
5400
6000
7200
9000
10,000
11,250
EconoMi$er
0.06
0.07
0.09
0.11
0.12
0.14
Glycol Coil
0.30
0.35
0.44
0.58
0.66
0.77
Electric Heat (kW)
26/34
0.08
0.09
0.11
0.15
0.17
0.20
32
0.08
0.09
0.11
0.15
0.17
0.20
42/56
0.11
0.12
0.15
0.19
0.21
0.24
55
0.11
0.12
0.15
0.19
0.21
0.24
56/75
0.14
0.15
0.20
0.24
0.26
0.29
80
0.14
0.15
0.20
0.24
0.26
0.29
Perfect Humidity™ Dehumidification
Package
0.06
0.07
0.10
0.16
0.20
0.25
FIOP —
Factory-Installed Option
Summary of Contents for DURAPAC 558F
Page 2: ...2 Fig 1A Roof Curb Details 558F180 240...
Page 3: ...3 Fig 1B Roof Curb Details 558F300...
Page 5: ...5 Fig 4 Base Unit Dimensions 558F180 210...
Page 6: ...6 Fig 5 Base Unit Dimensions 558F240...
Page 36: ......
Page 37: ......
Page 39: ......