—8—
EVOLUTION™* CONTROLS
* When applied with Bryant’s Perfect Humidity™ series 355, 315 and FE Indoor Models.
† Must be installed in Dual-Fuel Evolution system applications.
ACCESSORY USAGE GUIDELINE
* For tubing line sets greater than 50 ft, refer to Residential Split-System Long-Line Application Guideline and Service Manual.
† Only when low-pressure switch is used.
‡ Required for low-ambient controller (full modulation feature) and MotorMaster® Control only.
ACCESSORY DESCRIPTION AND USAGE (Listed Alphabetically)
1.
Ball-Bearing Fan Motor
A fan motor with ball bearings which permits speed reduction while maintaining bearing lubrication.
Usage Guideline:
Required on all units when low-ambient controller (full modulation feature) or MotoMaster®—Low-Ambient Controller is installed.
2.
Coastal Filter
A mesh screen inserted under the top cover and inside the base pan to protect the condenser coil from salt damage without restricting airflow.
3.
Compressor Start Assist – Capacitor and Relay
Start capacitor and relay gives a "hard" boost to compressor motor at each start up.
Usage Guideline:
Required for reciprocating compressors in the following applications:
Long line
Low ambient
Hard shut off expansion valve on indoor coil
Liquid line solenoid on indoor coil
Required for scroll compressors in the following applications:
Long line
Low ambient
Suggested for all compressors in areas with a history of low voltage problems.
4.
Compressor Start Assist — PTC Type
Solid state electrical device which gives a "soft" boost to the reciprocating compressor at each start-up.
Usage Guideline:
Suggested in installations with marginal power supply.
DESCRIPTION
ACCESSORY
Evolution Control Deluxe 7-Day Programmable (Wall-mounted system control.)
SYSTXBBUID01
Evolution Zone Control Deluxe Zoning 7-Day Programmable
(Wall-mounted control for a multi-zone system.)
SYSTXBBUIZ01
Evolution 4-Zone Damper Control Module (Wall-mounted control for a four-zone system.)
SYSTXBB4ZC01
Evolution Smart Sensor (Optional wall control used to monitor temperature
and/or fan control in an individual zone.)
SYSTXBBSMS01
Evolution Remote Room Sensor (Monitors temperature in an individual zone.)
SYSTXBBRRS01
Evolution System Access Module
(Hardware for wireless access and control via phone or internet.)
SYSTXBBSAM01
Evolution Network Interface Module (Connects Heat Recovery or
Energy Recovery Ventilators or older two-speed outdoor models to system.)
SYSTXBBNIM01†
Back Plate for Evolution Control (Decorative wall plate.)
SYSTXXXBPU01
ACCESSORY
REQUIRED FOR
LOW-AMBIENT
APPLICATIONS
(Below 55°F)
REQUIRED FOR
LONG-LINE
APPLICATIONS*
(Over 50 Ft)
REQUIRED FOR
SEA COAST
APPLICATIONS
(Within 2 Miles)
Crankcase Heater
Yes
Yes
No
Evaporator Freeze Thermostat
Yes
No
No
Winter Start Control
Yes†
No
No
Accumulator
No
No
No
Compressor Start Assist—
Capacitor/Relay Type
Yes
Yes
No
MotorMaster® Low-Ambient Controller
or
Low-Ambient Pressure Switch
Yes
No
No
Wind Baffle
See Low-Ambient Instructions
No
No
Coastal Filter
No
No
Yes
Support Feet
Recommended
No
Recommended
Liquid-Line Solenoid Valve
or
Hard Shutoff TXV
No
See Long-Line
Application
Guideline
No
Ball Bearing Fan Motor
Yes‡
No
No
Z
O
N
I
N
G