background image

5

The following items should be performed by a qualified service
technician.
Clean blower motor and wheel as follows:

1. Turn off electrical supply to furnace.
2. Remove main furnace door and blower access panel.
3. Disconnect wires

All factory wires can be left connected, but field thermostat
connections may need to be disconnected depending on

their length and routing.

4. Remove control box mounting screws, and position control

box, transformer, and door switch assembly to right side of

furnace casing.

5. If condensate trap is located in left-- or right--hand side of

furnace casing, proceed to item 6. Otherwise remove trap
and tubing as described below (See Fig. 5.):

a. Disconnect field drain connection from condensate trap.

b. Disconnect drain and relief port tubes from condensate

trap.

c. Remove condensate trap from blower shelf.

6. Remove screws securing blower assembly to blower shelf

and slide blower assembly out of furnace. Detach ground

wire and disconnect blower motor harness plugs from
blower motor.

NOTE

: Blower wheel is fragile. Use care.

7. Clean blower wheel and motor by using a vacuum with soft

brush attachment. Be careful not to disturb balance weights

(clips) on blower wheel vanes. Do not bend wheel or blades
as balance will be affected.

8. If greasy residue is present on blower wheel, remove wheel

from the blower housing and wash it with an appropriate

degreaser. To remove wheel:

a. Mark blower wheel location on shaft before disassembly

to ensure proper reassembly.

b. Loosen setscrew holding blower wheel on motor shaft.

NOTE

: Mark blower mounting arms and blower housing so each

arm is positioned at the same hole location during reassembly.

c. Mark blower wheel orientation and cutoff plate location

to ensure proper reassembly.

d. Remove screws securing cutoff plate and remove cutoff

plate from housing.

e. Remove bolts holding motor mounts to blower housing

and slide motor and mounts out of housing. Disconnect
capacitor and ground wire attached to blower housing

before removing motor. Motor mounts need not be
removed from motor.

f. Remove blower wheel from housing.

UNIT DAMAGE HAZARD

Failure to follow this caution may result in noise or furnace

component failure.
The blower wheel should not be dropped or bent as balance

will be affected.

CAUTION

!

g. Clean wheel per instructions on degreaser cleaner. Do

not get degreaser in motor.

9. Reassemble motor and blower wheel by reversing items 8b

through 8f. Ensure wheel is positioned for proper rotation.
Be sure to reattach ground wire. Tighten setscrew to 140 to

160 in--lb torque.

NOTE

: Be sure to attach ground wire to blower housing.

10. Reinstall blower assembly in furnace.

11. Reinstall control box, transformer, and door switch as-

sembly on blower shelf.

12. Reinstall condensate trap and tubing if previously removed.

a. Reinstall condensate trap in hole in blower shelf.

b. Connect condensate trap drain tubes. See Fig. 5 or

tubing diagram on main furnace door for proper tube
location.

NOTE

: Ensure tubes are not kinked or pinched, as this will affect

operation.

(1.) Connect one tube (blue or blue and white striped)

from collector box.

(2.) Connect one tube (violet or unmarked) from in-

ducer housing.

(3.) Connect one tube (relief port, green or pink) from

collector box.

c. Connect field drain to condensate trap.

NOTE

: Ensure tubes are not kinked or pinched, as this will affect

operation.

13. Reinstall control box, transformer, and door switch as-

sembly on blower shelf.

14. Reconnect wires. Refer to furnace wiring diagram and con-

nect thermostat leads if previously disconnected. (See Fig.
21.)

NOTE

: Refer to Table 3 for motor speed lead reconnection if

leads were not identified before disconnection.

UNIT DAMAGE HAZARD

Failure to adjust the heating speed may shorten heat

exchanger life.
Heating speed selection MUST be adjusted to provide

proper temperature rise as specified on the rating plate.

CAUTION

!

Table 3 – Speed Selection

COLOR

SPEED

FACTORY

ATTACHED TO

Black

High

Cool

Yellow (When Present)

Medium High

Spare

Blue

Medium Low

Heat

Red

Low

Fan

White

Common

Com

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal

injury or death.
Blower access panel door switch opens 115--v power to

furnace control. No component operation can occur.

Caution must be taken when manually closing this

switch for service purposes.

!

WARNING

15. Turn on electrical supply. Manually close blower access

panel door switch. Use a piece of tape to hold switch closed.

Check for proper rotation and speed changes between heat-
ing and cooling by jumpering R to G and R to Y/Y2 on

furnace control thermostat terminals. (See Fig. 15.)

16. If furnace is operating properly, release blower access panel

door switch, replace blower access panel, and replace main

furnace door.

340AA

V

Summary of Contents for Deluxe 340AAV

Page 1: ...potential for personal injury Understand the signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe personal injury or death WARNING signifies a hazard which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor personal injury or produ...

Page 2: ... operation CAUTION GENERAL This furnace can be installed as a direct vent 2 pipe or non direct vent 1 pipe condensing gas furnace These instructions are written as if the furnace is installed in an upflow application An upflow furnace application is where the blower is located below the combustion and controls section of the furnace and conditioned air is discharged upward Since this furnace can b...

Page 3: ...the label attached to the furnace WARNING The minimum maintenance that should be performed on this equipment is as follows 1 Check and clean or replace air filter each month as needed 2 Check blower motor and wheel for cleanliness annually 3 Check electrical connections for tightness and controls for proper operation each heating season Service as necessary 4 Check for proper condensate drainage C...

Page 4: ...nfiguration Shown with Blower Access Panel Removed 1 Turn off electrical supply to furnace 2 Remove filter cabinet door 3 Slide filter out of cabinet 4 If equipped with permanent washable filter clean filter by spraying cold tap water through filter in opposite direction of airflow Rinse filter and let dry Oiling or coating of the filter is not recommended 5 If equipped with factory specified disp...

Page 5: ... CAUTION g Clean wheel per instructions on degreaser cleaner Do not get degreaser in motor 9 Reassemble motor and blower wheel by reversing items 8b through 8f Ensure wheel is positioned for proper rotation Be sure to reattach ground wire Tighten setscrew to 140 to 160 in lb torque NOTE Be sure to attach ground wire to blower housing 10 Reinstall blower assembly in furnace 11 Reinstall control box...

Page 6: ...move screws attaching burner assembly in burner box NOTE Use care when removing and reinstalling burners not to strike the hot surface igniter IGNITER WIRES MUST BE PLACED IN THIS SLOT A05074 Fig 7 Igniter Wire Placement 12 Remove burner assembly from burner box NOTE All burners are attached to burner bracket and can be removed as one assembly 13 Clean burners with soft brush and vacuum 14 Reinsta...

Page 7: ...sconnect wires or connectors to flame rollout switch gas valve igniter and flame sensor 4 Disconnect combustion air intake pipe from intake hous ing 5 Remove the pressure switch tube from intake housing 6 Remove screws attaching intake housing to burner box and rotate intake housing away from burner box for removal 7 Using backup wrench disconnect gas supply pipe from fur nace gas control valve 8 ...

Page 8: ...n made specifically for the detection of leaks to check all connections WARNING 18 Replace main furnace door Secondary Heat Exchangers NOTE The condensing side inside of the secondary heat exchangers CANNOT be serviced or inspected A small number of bottom outlet openings can be inspected by removing the inducer assembly See Flushing Collector Box and Drainage System section for details on removin...

Page 9: ...onnection as shown 3 HORIZONTAL LEFT installations require the collector box pressure tube to be relocated between the inducer housing and the blower shelf to prevent a trap Refer to the Installation Instructions for further details NOTE 324999 201 REV C FIELD INSTALLED FACTORY SUPPLIED DRAINTUBE COUPLING RIGHT DRAIN OPTION BURNER ENCLOSURE PRESSURE REFERENCE TUBE ASSEMBLY BURNER ENCLOSURE PRESSUR...

Page 10: ...triking the igniter on surrounding parts Note that the igniter bracket has a handle that extends to the front of the burner box to aid in handling See Fig 13 d Inspect igniter for signs of damage or failure UNIT DAMAGE HAZARD Failure to follow this caution may result in premature failure of the igniter The igniter is fragile DO NOT allow it to hit burner box parts while removing or replacing it CA...

Page 11: ...se to blow If fuse replacement is required use ONLY a fuse of identical size The furnace control LED will flash status code 24 when fuse needs to be replaced With power to the unit disconnected check all electrical connections for tightness Tighten all screws on electrical connections If any smoky or burned connections are found disassemble the connection clean all parts strip wire and reassemble ...

Page 12: ... same type or equivalent wire W Y GND THERMOSTAT TERMINALS 1 2 3 A02174 Fig 15 Field Wiring BLW NUETRAL STATUS CODE LED SEC 2 SEC 1 EAC 2 L2 FUSE 3 AMP 0 5 AMP 24VAC HUM TEST TWIN G Com W Y R 24V 120 180 90 150 BLOWER OFF DELAY PLT 1 COOL HEAT SPARE 1 SPARE 2 EAC 1 1 AMP 115VAC PR 1 L1 PL2 1 24 V THERMOSTAT TERMINALS 3 AMP FUSE LED OPERATION DIAGNOSTIC LIGHT 115 VAC L2 NEUTRAL CONNECTIONS COOL HEA...

Page 13: ...omotive type CAUTION 6 Replace drain connection cap and clamp to inducer housing 7 Replace main furnace door 8 Propylene glycol need not be removed before restarting fur nace WIRING DIAGRAMS See Fig 21 for wiring diagram A07911 Fig 17 Freeze Protection TROUBLESHOOTING Use the troubleshooting guide the status code LED on the furnace control and the component test to isolate furnace operation proble...

Page 14: ... COM 24v terminals are jumpered longer than 2 sec LED will flash rapidly and ignore component test request A99119 Fig 19 Funnel in Drain Tube and Antifreeze Running Through Trap Component test sequence for single stage furnace is as follows a LED will display status code 11 four times b Inducer motor starts and continues to run until Step f of component test sequence c After 7 sec the hot surface ...

Page 15: ...T CLOSE OR REOPENED If open longer than five minutes inducer shuts off for 15 minutes before retry Check for Excessive wind Proper vent sizing Defective inducer motor Low inducer voltage 115VAC Defective pressure switch Inadequate combustion air supply Restricted vent Disconnected or obstructed pressure tubing Low inlet gas pressure if LGPS used If it opens during blower on delay period blower wil...

Page 16: ...AFT MOTOR RELAY SPST N O ILK BLOWER ACCESS PANEL INTERLOCK SWITCH SPST N O J1 BLOWER OFF DELAY JUMPER SELECTOR J2 COOLING OFF DELAY JUMPER JB JUNCTION BOX LED LIGHT EMITTING DIODE FOR STATUS CODES RED LGPS LOW GAS PRESSURE SWITCH SPST N O LS LIMIT SWITCH AUTO RESET SPST N C OL AUTO RESET INTERNAL MOTOR OVERLOAD TEMPERATURE SWITCH N C PCB PRINTED CIRCUIT BOARD CONTROL PL1 11 CIRCUIT PCB CONNECTOR P...

Page 17: ...est sequence The inducer will start and run for the entire component test The HSI blower motor FAN speed AMBER LED boards only HEAT speed and COOL speed will run for 10 15 seconds each Gas valve and humidifier will not be turned on Was there a previous status code other than 11 Is door switch closed Is there 115V going to switch Replace door switch Replace transformer Does the control respond to W...

Page 18: ... switch open Restricted vent Proper vent sizing Excessive wind Blower motor on incorrect speed tap Input rate to furnace set too high 34 IGNITION PROVING FAILURE If flame is not sensed during the trial for ignition period the control will repeat the ignition sequence 3 more times before lockout 14 occurs If flame signal is lost during the blower on delay period blower will come on for the selected...

Page 19: ...heory and skills programs is available using popular video based formats and materials All include video and or slides plus companion book Classroom ServiceTraining plus hands on the products in our labs can mean increased confidence that really pays dividends in faster troubleshooting fewer callbacks Course descriptions and schedules are in our catalog CALL FOR FREE CATALOG 1 800 644 5544 Package...

Page 20: ...hange at any time specifications or designs without notice and without incurring obligations E2008 Bryant Heating Cooling Systems D 7310 W Morris St D Indianapolis IN 46231 Printed in U S A Edition Date 12 08 Replaces SP05 72 Catalog No SM340AAV 01 340AAV ...

Reviews: