Bryant DE LUXE 12 SEER 552A User Manual Download Page 6

 

—6—

 

ACCESSORY USAGE GUIDELINE

 

* For tubing line sets greater than 50 ft and/or 20 ft vertical differential, refer to Application Guideline and Service Manual—Air Conditioning and 

Heat Pumps Using Puron® 
Refrigerant.

† Only when low-pressure switch is used.
‡ Required for low-ambient controller (full modulation feature) and MotorMaster® Control only.

 

ACCESSORY DESCRIPTION AND USAGE (Listed Alphabetically)

 

1.

 

Ball Bearing Fan Motor

 

A fan motor with ball bearings which permits speed reduction while maintaining bearing lubrication. 

SUGGESTED USE: Required on all units where Low-Ambient Controller (full modulation feature) or MotorMaster® Control has been added.

2.

 

Coastal Filter

 

A mesh screen inserted under the top cover and inside base pan to protect the condenser coil from corrosive atmosphere without restricting airflow. 

SUGGESTED USE: In geographic areas where salt damage could occur.

In areas with high pollution levels.

3.

 

Compressor Start Assist—Capacitor/Relay Type

 

Start capacitor and start relay which gives a hard” boost to compressor motor at each start-up.

SUGGESTED USE: Installations where interconnecting tube length exceeds 50 ft.

Installations where outdoor design temperature exceeds 105°F (40.6°C).
Installations where low voltage or brown-out conditions may occur.

4.

 

Compressor Start Assist—PTC Type

 

Solid-state electrical device which gives a soft” boost to compressor motor at each start-up.

SUGGESTED USE: Installations with marginal power supply.

5.

 

Crankcase Heater

 

An electric resistance heater which mounts to the base of the compressor to keep the lubricant warm during off cycles. Improves compressor lubrication 
on restart and minimizes chance of refrigerant slugging. May or may not include a thermostat control. 

SUGGESTED USE: When interconnecting tube length exceeds 50 ft.

When unit will be operated below 55°F (12.8°C) outdoor air temperature. Use with Low-Ambient Controller.
All commercial installations.

6.

 

Cycle Protector

 

Solid state timing device which prevents compressor rapid recycling. Control provides an approximate 5-minute delay after power to the compressor has 
been interrupted for any reason, including normal room thermostat cycling. 

SUGGESTED USE: Installations in areas where power interruptions are frequent.

Where user is likely to play” with the room thermostat.
All commercial installations.
Installations where interconnecting tube length exceeds 50 ft.
High-rise applications.

7.

 

Evaporator Freeze Thermostat

 

An SPST temperature actuated switch which stops unit operation when evaporator reaches freeze-up conditions. 

SUGGESTED USE: All units where Winter Start Control has been added.

8.

 

Filter Drier (Suction Line)

 

A device for removing contaminants from refrigerant circulating in an air conditioner: one direction flow.

SUGGESTED USE: All split-system air conditioners.

9.

 

Liquid-Line Solenoid Valve (LSV)

 

An electrically operated shutoff valve to be installed at the outdoor or indoor unit (depending on tubing configuration) and which stops and starts refrigerant 
liquid flow in response to compressor operation. Maintains a column of refrigerant liquid ready for action at next compressor operation cycle.

SUGGESTED USE: For improved system performance in air conditioners for certain combinations of indoor and outdoor units. Refer to ARI Unitary Directory.

In certain long-line applications. Refer to Residential Split System Long-Line Application Guideline and Service Manual.

 

ACCESSORY

REQUIRED FOR

LOW-AMBIENT

APPLICATIONS

(Below 55°F)

REQUIRED FOR

LONG-LINE

APPLICATIONS*

(Over 50 Ft)

REQUIRED FOR

SEA COAST

APPLICATIONS
(Within 2 Miles)

 

Crankcase Heater

Yes

Yes

No

Evaporator Freeze Thermostat

Yes

No

No

Winter Start Control

Yes†

No

No

Accumulator

No

No

No

Compressor Start Assist

Capacitor and Relay

Yes

Yes

No

MotorMaster® Control

or

Low-Ambient Pressure Switch

Yes

No

No

Wind Baffle

See Low-Ambient Instructions

No

No

Coastal Filter

No

No

Yes

Support Feet

Recommended

No

Recommended

Liquid-Line Solenoid Valve

or

Hard Shutoff TXV

No

See Long-Line

Application

Guideline

No

Ball Bearing Fan Motor

Yes‡

No

No

Summary of Contents for DE LUXE 12 SEER 552A

Page 1: ...of the system and componentry The reliability of the existing Quantum Plus models has been proven to provide the lowest incidence of warranty service of any product in the Bryant family in the past fe...

Page 2: ...M A99067 DIMENSIONS IN UNIT SIZE SERIES UNIT DIMENSIONS MINIMUM MOUNTING PAD DIMENSIONS A B C D E F G H J K L M N 018 F 33 13 16 22 1 2 27 1 2 4 1 8 7 1 8 21 15 16 28 3 8 5 8 8 3 16 12 1 2 14 15 1 2 2...

Page 3: ...P L Y I N G W I T H A RI STANDARD 210 U N I T A R Y AIR CO N D I T I O N I N G EQUIPMENT CERTIFICATION APPLIES ONLY WHEN THE COMPLETE SYSTEM IS LISTED WITH ARI REGISTERED QUALITY SYSTEM As an ENERGY S...

Page 4: ...00 2400 2400 OPTIONAL EQUIPMENT Support Feet KSASF0101AAA Coastal Filter KAACF0701SML KAACF0801MED KAACF0701SML KAACF0801MED Time Delay Relay KAATD0101TDR Cycle Protector KSACY0101AAA Crankcase Heater...

Page 5: ...anch Circuit Fuse or Circuit Breaker Size Amps 40 40 60 COMPRESSOR REFRIGERANT Compressor Type Scroll Temperature Current Protection Internal Line Break Refrigerant Type Puron R 410A Amount Lb 5 43 5...

Page 6: ...6 Cycle Protector Solid state timing device which prevents compressor rapid recycling Control provides an approximate 5 minute delay after power to the compressor has been interrupted for any reason...

Page 7: ...ther debris to be flushed from the unit base minimizing corrosion SUGGESTED USE For improved sound ratings Coastal installations Windy areas or where debris is normally circulating Rooftop installatio...

Page 8: ...A024 17 500 TDR 13 00 13 00 11 80 CK5A CK5BW024 17 500 TDR 13 00 13 00 11 90 CK5PW024 17 500 TDR TXV 13 00 11 90 024 F CK5A CK5BA030 23 200 NONE 12 00 12 00 10 30 CC5A CD5AA024 23 000 NONE 11 70 11 70...

Page 9: ...TXV 12 00 10 70 CK5PW024 22 800 TXV 12 00 10 65 CK5PW030 23 000 TXV 12 00 10 70 F A B 4BN F C 024 23 000 TDR 12 00 12 00 10 75 F A B 4BN F C 030 23 400 TDR 12 00 12 00 10 85 FC4CNF024 23 000 TDR TXV...

Page 10: ...11 80 CK3BA030 22 600 TDR 13 00 13 00 11 85 CK5A CK5BA024 22 200 TDR 13 00 13 00 11 65 CK5A CK5BA030 22 600 TDR 13 00 13 00 11 75 CK5A CK5BW024 22 200 TDR 13 00 13 00 11 65 CK5A CK5BW030 22 600 TDR 13...

Page 11: ...00 10 40 COILS 315 A J AV036070 VARIABLE SPEED FURNACE CC5A CD5AA030 27 800 TDR 12 50 12 50 11 10 CC5A CD5AA036 28 800 TDR 13 00 13 00 11 45 CC5A CD5AW030 27 800 TDR 12 50 12 50 11 10 CE3AA030 28 200...

Page 12: ...12 00 10 55 CC5A CD5AW042 34 800 NONE 12 00 12 00 10 45 CE3AA036 34 600 NONE 11 70 11 70 10 45 CE3AA042 35 000 NONE 12 00 12 00 10 60 CF5AA036 34 800 NONE 12 00 12 00 10 50 CK3BA036 35 000 NONE 12 00...

Page 13: ...600 TDR TXV 13 00 11 45 CK5PT036 34 600 TDR TXV 13 00 11 40 CK5PT042 34 600 TDR TXV 13 00 11 45 CK5PW036 34 600 TDR TXV 13 00 11 40 COILS 315 A J AV066135 VARIABLE SPEED FURNACE CC5A CD5AA042 34 600 T...

Page 14: ...0 25 CE3AA048 40 000 NONE 12 00 12 00 10 30 CF5AA048 39 500 NONE 12 00 12 00 10 25 CK3BA042 39 500 NONE 11 70 11 70 10 20 CK3BA048 40 000 NONE 12 00 12 00 10 25 CK5A CK5BA042 39 500 NONE 11 70 11 70 1...

Page 15: ...11 10 CK5A CK5BW048 39 500 TDR 13 00 13 00 11 10 CK5PA042 39 000 TDR TXV 12 50 11 00 CK5PA048 39 500 TDR TXV 12 50 11 10 CK5PT042 39 000 TDR TXV 12 50 11 00 CK5PT048 39 500 TDR TXV 12 50 11 10 CK5PW0...

Page 16: ...10 35 CD5AA048 45 000 NONE 11 70 11 70 10 15 CE3AA048 45 000 NONE 11 70 11 70 10 25 CE3AA060 46 000 NONE 12 00 12 00 10 40 CF5AA048 44 000 NONE 11 70 11 70 10 20 CK3BA048 45 000 NONE 11 70 11 70 10 2...

Page 17: ...DR 12 50 12 50 11 25 CK5PA048 44 500 TDR TXV 12 00 10 80 CK5PA060 45 000 TDR TXV 12 50 11 05 CK5PT048 44 500 TDR TXV 12 00 10 80 CK5PT060 45 000 TDR TXV 12 50 11 05 CK5PW048 44 500 TDR TXV 12 00 10 80...

Page 18: ...85 FC4 B C NB070 58 000 TDR TXV 12 00 10 15 FG3AAA060 56 000 NONE 11 50 11 50 10 10 FK4 C D NB006 58 000 TDR TXV 12 50 12 50 10 75 FV4 A B NB006 58 000 TDR TXV 12 50 10 75 FX4 A B NB060 56 000 TDR TXV...

Page 19: ...elay Relay TXV Puron Thermostatic Expansion Valve NOTES 1 Ratings are net values reflecting the effects of circulating fan motor heat Supplemental electric heat is not included 2 Tested outdoor indoor...

Page 20: ...16 05 16 05 1 63 15 24 15 24 1 80 14 37 14 37 2 00 13 45 13 45 2 21 675 72 19 82 10 51 1 36 19 79 10 76 1 52 19 60 10 97 1 69 18 81 10 83 1 88 17 66 10 48 2 08 16 38 10 04 2 30 67 19 30 14 10 1 35 19...

Page 21: ...22 5 17 0 2 04 21 1 16 5 2 26 19 4 15 7 2 50 18 2 15 3 2 77 16 2 14 4 3 05 62 23 1 21 9 1 83 22 2 21 4 2 03 20 9 20 8 2 26 20 2 20 2 2 51 18 9 18 9 2 79 17 2 17 2 3 08 57 22 6 22 6 1 82 21 8 21 8 2 03...

Page 22: ...24 05 13 90 2 48 22 47 13 40 2 76 20 68 12 80 3 07 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacit...

Page 23: ...62 1 71 22 93 22 93 1 93 21 79 21 79 2 19 20 57 20 57 2 46 19 32 19 32 2 73 17 99 17 99 3 05 67 25 80 19 11 1 72 24 77 19 02 1 94 23 33 18 61 2 19 21 81 18 07 2 45 20 21 17 48 2 75 18 46 16 79 3 05 7...

Page 24: ...25 7 3 03 24 3 24 3 3 36 21 9 21 9 3 71 57 30 2 30 2 2 26 28 6 28 6 2 49 27 0 27 0 2 74 26 1 26 1 3 04 24 6 24 6 3 36 21 9 21 9 3 71 Multipliers for Determining the Performance With Other Indoor Secti...

Page 25: ...5 6 2 68 24 3 24 3 2 96 22 9 22 9 3 29 21 4 21 4 3 65 57 28 6 28 6 2 20 26 9 26 9 2 42 25 4 25 4 2 67 24 5 24 5 2 97 23 4 23 4 3 29 21 4 21 4 3 65 1125 72 34 1 17 8 2 30 33 1 17 6 2 54 31 4 17 0 2 79...

Page 26: ...3 37 31 8 31 8 3 73 29 4 29 4 4 11 26 4 26 4 4 53 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacit...

Page 27: ...57 36 6 36 6 2 73 35 2 35 2 3 03 33 6 33 6 3 37 31 8 31 8 3 73 29 4 29 4 4 11 26 4 26 4 4 53 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor S...

Page 28: ...36 3 36 3 4 36 33 2 33 2 4 82 29 9 29 9 5 33 57 41 1 41 1 3 20 39 6 39 6 3 55 37 4 37 4 3 92 36 2 36 2 4 36 33 1 33 1 4 82 30 3 30 3 5 34 Multipliers for Determining the Performance With Other Indoor...

Page 29: ...92 36 2 36 2 4 36 33 1 33 1 4 82 30 3 30 3 5 34 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity P...

Page 30: ...46 4 46 4 4 03 44 3 44 3 4 47 42 2 42 2 4 97 39 6 39 6 5 51 35 2 35 2 6 09 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooli...

Page 31: ...62 48 7 48 6 3 65 46 4 46 4 4 03 44 4 44 4 4 47 42 2 42 2 4 97 38 5 38 5 5 49 34 4 34 4 6 07 57 48 5 48 5 3 64 46 4 46 4 4 03 44 3 44 3 4 47 42 2 42 2 4 97 39 6 39 6 5 51 35 2 35 2 6 09 Multipliers f...

Page 32: ...36 7 7 64 63 58 6 42 9 4 46 55 0 41 3 4 94 51 2 39 7 5 47 49 2 38 8 6 11 44 4 36 8 6 76 39 2 34 7 7 47 62 57 5 53 4 4 44 54 0 51 7 4 92 50 6 50 0 5 46 48 8 48 8 6 10 45 6 45 6 6 79 41 6 41 6 7 55 57 5...

Page 33: ...24 2 18 17 2 133 2 43 15 6 143 2 69 40 TCG SDT KW 28 2 77 1 1 18 26 7 86 7 1 35 25 1 96 3 1 54 23 6 106 1 74 22 0 116 1 97 20 4 125 2 21 18 8 135 2 46 17 0 144 2 72 45 TCG SDT KW 30 8 78 7 1 18 29 1 8...

Page 34: ...1 25 6 124 3 13 23 3 133 3 48 20 8 142 3 83 40 TCG SDT KW 39 0 78 1 1 71 37 0 87 5 1 95 34 9 97 1 2 22 32 7 107 2 51 30 5 116 2 83 28 1 125 3 17 25 7 134 3 52 23 0 143 3 89 45 TCG SDT KW 42 5 79 9 1 7...

Page 35: ...Continued ARI listing applies only to systems shown in Ratings and Performance table kW Outdoor Unit Kilowatts only SDT Saturated Temperature Leaving Compressor F SST Saturated Temperature Entering C...

Page 36: ...Significant New Alternatives Program SNAP Unit Cabinet Unit cabinet will be constructed of galvanized steel bonderized and coated with a powder coat paint Fans Condenser fan will be direct drive prop...

Reviews: