—5—

 

SPECIFICATIONS Continued

 

* Permissible limits of the voltage range at which the unit will operate satisfactorily. Operation outside these limits may result in unit failure.

† If wire is applied at ambient greater than 30°C (86°F), consult Table 310-16 of the NEC (ANSI/NFPA 70).

The ampacity of nonmetallic-sheathed cable (NM), trade name ROMEX, shall be that of 60°C (140°F) conductors, per the NEC (ANSI/NFPA 70) Article 336-26. If 
other than uncoated (non-plated), 60 or 75°C (140 or 167°F) insulation, copper wire (solid wire for 10 AWG and smaller, stranded wire for larger than 10 AWG) is 
used, consult applicable tables of the NEC (ANSI/NFPA 70).

‡ Length shown is as measured 1 way along wire path between unit and service panel for a voltage drop not to exceed 2%.

** Fan motor with ball bearings required.

†† See low-ambient controller Installation Instructions for application.

N/A — Not Applicable.

 

NOTE: 

 

Copper wire must be used from service disconnect to unit. All motors/compressors contain internal overload protection.

 

UNIT SIZE-SERIES

042-F

048-F

060-F

 

Operating Weight (Lb)

213

215

278

 

ELECTRICAL

 

Unit Volts—Hertz—Phase

208/230—60—1

Operating Voltage Range*

187—253

Compressor—Rated Load Amps

18.6

20.5

27.6

Locked Rotor Amps

105.0

109.0

158.0

Condenser Fan Motor—Full Load Amps

1.1

1.1

1.4

Min Unit Ampacity for Wire Sizing

24.4

26.7

35.9

Min Wire Size (60°C Copper) AWG†

10

10

8

Min Wire Size (75°C Copper) AWG†

10

10

8

Max Wire Length (Ft) (60°C Copper)‡

81

74

86

Max Wire Length (Ft) (75°C Copper)‡

77

71

82

Max Branch Circuit Fuse or 

Circuit Breaker Size (Amps)

40

40

60

 

COMPRESSOR & REFRIGERANT

 

Compressor— Type

Scroll

Temperature & Current Protection

Internal Line Break

Refrigerant—Type

Puron® (R-410A)

Amount (Lb)

5.43

5.75

8.00

 

CONDENSER COIL & FAN 

 

Coil Face Area (Sq Ft)

12.2

12.2

18.2

Fins per In.—Rows—Circuits

25—1—2

25—1—2

25—1—3

Fan Motor—HP (PSC) & RPM

1/5 & 825

1/5 & 1100

1/4 & 1100

Volts—Hertz—Phase

208/230—60—1

Condenser Airflow (CFM)

2800

2800

3300

 

OPTIONAL EQUIPMENT

 

Support Feet

KSASF0101AAA

Coastal Filter

KAACF0801MED

Time Delay Relay

KAATD0101TDR

Cycle Protector

KSACY0101AAA

Crankcase Heater

KAACH1201AAA

Start Assist—Capacitor/Relay Type

KSAHS1501AAA

KSAHS1601AAA

Start Assist—PTC Type

KAACS0201PTC

TXV (Hard Shutoff)

KSATX0301PUR

KSATX0401PUR

KSATX0501PUR

Piston Body

KSAPX0101PIS

Filter Drier (Suction Line)

KH45LG141 (RCD)

Evaporator Freeze Thermostat††

KAAFT0101AAA

Liquid-Line Solenoid Valve

KAALS0201LLS

Winter Start Control††

KAAWS0101AAA

Low-Ambient Pressure Switch

KSALA0301410

MotorMaster® Control**

32LT660004 (RCD)

Ball Bearing Fan Motor

HC38GE231 (RCD)

HC40GE232 (RCD)

Thermostat—Auto Changeover, 

Non-Programmable, °F/°C, 
1-Stage Heat, 1-Stage Cool

TSTATBBNAC01-B

Thermostat—Auto Changeover, 

7-Day Programmable, °F/°C, 
1-Stage Heat, 1-Stage Cool

TSTATBBPAC01-B

Thermidistat™ Control—

Programmable Thermostat with Humidity Control

TSTATBBPRH01-B

Builder’s Thermostat—Manual Changeover,

Non-Programmable, °F/°C, 
1-Stage Heat, 1-Stage Cool

TSTATBBBAC01-B

Outdoor Air Temperature Sensor

TSTATXXSEN01-B

Backplate for Non-Programmable Thermostat

TSTATXXNBP01

Backplate for Programmable Thermostat

TSTATXXPBP01

Backplate for Builder’s Thermostat

TSTATXXBBP01

Thermostat Conversion Kit (4 to 5 wire)—10 Pack

TSTATXXCNV10

Summary of Contents for DE LUXE 12 SEER 552A

Page 1: ...of the system and componentry The reliability of the existing Quantum Plus models has been proven to provide the lowest incidence of warranty service of any product in the Bryant family in the past fe...

Page 2: ...M A99067 DIMENSIONS IN UNIT SIZE SERIES UNIT DIMENSIONS MINIMUM MOUNTING PAD DIMENSIONS A B C D E F G H J K L M N 018 F 33 13 16 22 1 2 27 1 2 4 1 8 7 1 8 21 15 16 28 3 8 5 8 8 3 16 12 1 2 14 15 1 2 2...

Page 3: ...P L Y I N G W I T H A RI STANDARD 210 U N I T A R Y AIR CO N D I T I O N I N G EQUIPMENT CERTIFICATION APPLIES ONLY WHEN THE COMPLETE SYSTEM IS LISTED WITH ARI REGISTERED QUALITY SYSTEM As an ENERGY S...

Page 4: ...00 2400 2400 OPTIONAL EQUIPMENT Support Feet KSASF0101AAA Coastal Filter KAACF0701SML KAACF0801MED KAACF0701SML KAACF0801MED Time Delay Relay KAATD0101TDR Cycle Protector KSACY0101AAA Crankcase Heater...

Page 5: ...anch Circuit Fuse or Circuit Breaker Size Amps 40 40 60 COMPRESSOR REFRIGERANT Compressor Type Scroll Temperature Current Protection Internal Line Break Refrigerant Type Puron R 410A Amount Lb 5 43 5...

Page 6: ...6 Cycle Protector Solid state timing device which prevents compressor rapid recycling Control provides an approximate 5 minute delay after power to the compressor has been interrupted for any reason...

Page 7: ...ther debris to be flushed from the unit base minimizing corrosion SUGGESTED USE For improved sound ratings Coastal installations Windy areas or where debris is normally circulating Rooftop installatio...

Page 8: ...A024 17 500 TDR 13 00 13 00 11 80 CK5A CK5BW024 17 500 TDR 13 00 13 00 11 90 CK5PW024 17 500 TDR TXV 13 00 11 90 024 F CK5A CK5BA030 23 200 NONE 12 00 12 00 10 30 CC5A CD5AA024 23 000 NONE 11 70 11 70...

Page 9: ...TXV 12 00 10 70 CK5PW024 22 800 TXV 12 00 10 65 CK5PW030 23 000 TXV 12 00 10 70 F A B 4BN F C 024 23 000 TDR 12 00 12 00 10 75 F A B 4BN F C 030 23 400 TDR 12 00 12 00 10 85 FC4CNF024 23 000 TDR TXV...

Page 10: ...11 80 CK3BA030 22 600 TDR 13 00 13 00 11 85 CK5A CK5BA024 22 200 TDR 13 00 13 00 11 65 CK5A CK5BA030 22 600 TDR 13 00 13 00 11 75 CK5A CK5BW024 22 200 TDR 13 00 13 00 11 65 CK5A CK5BW030 22 600 TDR 13...

Page 11: ...00 10 40 COILS 315 A J AV036070 VARIABLE SPEED FURNACE CC5A CD5AA030 27 800 TDR 12 50 12 50 11 10 CC5A CD5AA036 28 800 TDR 13 00 13 00 11 45 CC5A CD5AW030 27 800 TDR 12 50 12 50 11 10 CE3AA030 28 200...

Page 12: ...12 00 10 55 CC5A CD5AW042 34 800 NONE 12 00 12 00 10 45 CE3AA036 34 600 NONE 11 70 11 70 10 45 CE3AA042 35 000 NONE 12 00 12 00 10 60 CF5AA036 34 800 NONE 12 00 12 00 10 50 CK3BA036 35 000 NONE 12 00...

Page 13: ...600 TDR TXV 13 00 11 45 CK5PT036 34 600 TDR TXV 13 00 11 40 CK5PT042 34 600 TDR TXV 13 00 11 45 CK5PW036 34 600 TDR TXV 13 00 11 40 COILS 315 A J AV066135 VARIABLE SPEED FURNACE CC5A CD5AA042 34 600 T...

Page 14: ...0 25 CE3AA048 40 000 NONE 12 00 12 00 10 30 CF5AA048 39 500 NONE 12 00 12 00 10 25 CK3BA042 39 500 NONE 11 70 11 70 10 20 CK3BA048 40 000 NONE 12 00 12 00 10 25 CK5A CK5BA042 39 500 NONE 11 70 11 70 1...

Page 15: ...11 10 CK5A CK5BW048 39 500 TDR 13 00 13 00 11 10 CK5PA042 39 000 TDR TXV 12 50 11 00 CK5PA048 39 500 TDR TXV 12 50 11 10 CK5PT042 39 000 TDR TXV 12 50 11 00 CK5PT048 39 500 TDR TXV 12 50 11 10 CK5PW0...

Page 16: ...10 35 CD5AA048 45 000 NONE 11 70 11 70 10 15 CE3AA048 45 000 NONE 11 70 11 70 10 25 CE3AA060 46 000 NONE 12 00 12 00 10 40 CF5AA048 44 000 NONE 11 70 11 70 10 20 CK3BA048 45 000 NONE 11 70 11 70 10 2...

Page 17: ...DR 12 50 12 50 11 25 CK5PA048 44 500 TDR TXV 12 00 10 80 CK5PA060 45 000 TDR TXV 12 50 11 05 CK5PT048 44 500 TDR TXV 12 00 10 80 CK5PT060 45 000 TDR TXV 12 50 11 05 CK5PW048 44 500 TDR TXV 12 00 10 80...

Page 18: ...85 FC4 B C NB070 58 000 TDR TXV 12 00 10 15 FG3AAA060 56 000 NONE 11 50 11 50 10 10 FK4 C D NB006 58 000 TDR TXV 12 50 12 50 10 75 FV4 A B NB006 58 000 TDR TXV 12 50 10 75 FX4 A B NB060 56 000 TDR TXV...

Page 19: ...elay Relay TXV Puron Thermostatic Expansion Valve NOTES 1 Ratings are net values reflecting the effects of circulating fan motor heat Supplemental electric heat is not included 2 Tested outdoor indoor...

Page 20: ...16 05 16 05 1 63 15 24 15 24 1 80 14 37 14 37 2 00 13 45 13 45 2 21 675 72 19 82 10 51 1 36 19 79 10 76 1 52 19 60 10 97 1 69 18 81 10 83 1 88 17 66 10 48 2 08 16 38 10 04 2 30 67 19 30 14 10 1 35 19...

Page 21: ...22 5 17 0 2 04 21 1 16 5 2 26 19 4 15 7 2 50 18 2 15 3 2 77 16 2 14 4 3 05 62 23 1 21 9 1 83 22 2 21 4 2 03 20 9 20 8 2 26 20 2 20 2 2 51 18 9 18 9 2 79 17 2 17 2 3 08 57 22 6 22 6 1 82 21 8 21 8 2 03...

Page 22: ...24 05 13 90 2 48 22 47 13 40 2 76 20 68 12 80 3 07 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacit...

Page 23: ...62 1 71 22 93 22 93 1 93 21 79 21 79 2 19 20 57 20 57 2 46 19 32 19 32 2 73 17 99 17 99 3 05 67 25 80 19 11 1 72 24 77 19 02 1 94 23 33 18 61 2 19 21 81 18 07 2 45 20 21 17 48 2 75 18 46 16 79 3 05 7...

Page 24: ...25 7 3 03 24 3 24 3 3 36 21 9 21 9 3 71 57 30 2 30 2 2 26 28 6 28 6 2 49 27 0 27 0 2 74 26 1 26 1 3 04 24 6 24 6 3 36 21 9 21 9 3 71 Multipliers for Determining the Performance With Other Indoor Secti...

Page 25: ...5 6 2 68 24 3 24 3 2 96 22 9 22 9 3 29 21 4 21 4 3 65 57 28 6 28 6 2 20 26 9 26 9 2 42 25 4 25 4 2 67 24 5 24 5 2 97 23 4 23 4 3 29 21 4 21 4 3 65 1125 72 34 1 17 8 2 30 33 1 17 6 2 54 31 4 17 0 2 79...

Page 26: ...3 37 31 8 31 8 3 73 29 4 29 4 4 11 26 4 26 4 4 53 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacit...

Page 27: ...57 36 6 36 6 2 73 35 2 35 2 3 03 33 6 33 6 3 37 31 8 31 8 3 73 29 4 29 4 4 11 26 4 26 4 4 53 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor S...

Page 28: ...36 3 36 3 4 36 33 2 33 2 4 82 29 9 29 9 5 33 57 41 1 41 1 3 20 39 6 39 6 3 55 37 4 37 4 3 92 36 2 36 2 4 36 33 1 33 1 4 82 30 3 30 3 5 34 Multipliers for Determining the Performance With Other Indoor...

Page 29: ...92 36 2 36 2 4 36 33 1 33 1 4 82 30 3 30 3 5 34 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity P...

Page 30: ...46 4 46 4 4 03 44 3 44 3 4 47 42 2 42 2 4 97 39 6 39 6 5 51 35 2 35 2 6 09 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooli...

Page 31: ...62 48 7 48 6 3 65 46 4 46 4 4 03 44 4 44 4 4 47 42 2 42 2 4 97 38 5 38 5 5 49 34 4 34 4 6 07 57 48 5 48 5 3 64 46 4 46 4 4 03 44 3 44 3 4 47 42 2 42 2 4 97 39 6 39 6 5 51 35 2 35 2 6 09 Multipliers f...

Page 32: ...36 7 7 64 63 58 6 42 9 4 46 55 0 41 3 4 94 51 2 39 7 5 47 49 2 38 8 6 11 44 4 36 8 6 76 39 2 34 7 7 47 62 57 5 53 4 4 44 54 0 51 7 4 92 50 6 50 0 5 46 48 8 48 8 6 10 45 6 45 6 6 79 41 6 41 6 7 55 57 5...

Page 33: ...24 2 18 17 2 133 2 43 15 6 143 2 69 40 TCG SDT KW 28 2 77 1 1 18 26 7 86 7 1 35 25 1 96 3 1 54 23 6 106 1 74 22 0 116 1 97 20 4 125 2 21 18 8 135 2 46 17 0 144 2 72 45 TCG SDT KW 30 8 78 7 1 18 29 1 8...

Page 34: ...1 25 6 124 3 13 23 3 133 3 48 20 8 142 3 83 40 TCG SDT KW 39 0 78 1 1 71 37 0 87 5 1 95 34 9 97 1 2 22 32 7 107 2 51 30 5 116 2 83 28 1 125 3 17 25 7 134 3 52 23 0 143 3 89 45 TCG SDT KW 42 5 79 9 1 7...

Page 35: ...Continued ARI listing applies only to systems shown in Ratings and Performance table kW Outdoor Unit Kilowatts only SDT Saturated Temperature Leaving Compressor F SST Saturated Temperature Entering C...

Page 36: ...Significant New Alternatives Program SNAP Unit Cabinet Unit cabinet will be constructed of galvanized steel bonderized and coated with a powder coat paint Fans Condenser fan will be direct drive prop...