Bryant DE LUXE 12 SEER 552A User Manual Download Page 36

SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE

UNIT MUST BE INSTALLED IN ACCORDANCE

WITH INSTALLATION INSTRUCTIONS

Cancels:  PDS 552A.18.2

New:  PDS 552A.18.3

© 2003 Bryant Heating & Cooling Systems, 7310 W. Morris St.    Indpls, IN 46231

—36—

PRINTED IN U.S.A.      Catalog No.  5255-206      10-03

GUIDE SPECIFICATIONS

GENERAL

System Description

Outdoor-mounted, air-cooled, split-system air conditioner unit
suitable for ground or rooftop installation. Unit consists of a her-
metic compressor, an air-cooled coil, propeller-type condenser
fan, and a control box. Unit will discharge supply air upward as
shown on contract drawings. Unit will be used in a refrigeration
circuit to match up to a packaged fan coil or coil unit.

Quality Assurance

Unit will be rated in accordance with the latest edition of ARI
Standard 210.
Unit will be certified for capacity and efficiency, and listed in the
lastest ARI directory.
Unit construction will comply with latest edition of ANSI/
ASHRAE and with NEC.
Unit will be constructed in accordance with UL standards and
will carry the UL label of approval. Unit will have c-UL approval.
Unit cabinet will be capable of withstanding Federal Test Method
Standard No. 141 (Method 6061) 500-hr salt spray test.
Air-cooled condenser coils will be leak tested at 150 psig and
pressure tested at 450 psig.
Unit constructed in ISO9001 approved facility.

Delivery, Storage, and Handling

Unit will be shipped as single package only and is stored and
handled per unit manufacturer’s recommendations.

Warranty (for inclusion by specifying engineer)

U.S. and Canada only.

PRODUCTS

Equipment

Factory assembled, single piece, air-cooled air conditioner unit.
Contained within the unit enclosure is all factory wiring, piping,
controls, compressor, refrigerant charge Puron® (R-410A), and
special features required prior to field start-up.

Refrigerant
Refrigerant will be Puron (R-410A) HFC Refrigerant with zero
ozone depletion potential. R-410A is approved under the EPA’s
Significant New Alternatives Program (SNAP).
Unit Cabinet
Unit cabinet will be constructed of galvanized steel, bonderized,
and coated with a powder coat paint.
Fans
Condenser fan will be direct-drive propeller type, discharging air
upward.

Air-Cooled, Split-System

Air Conditioner

552A

1-1/2 to 5 Tons Nominal

Fans
Condenser fan will be direct-drive propeller type, discharging air
upward.
Condenser fan motors will be totally enclosed, 1-phase type
with class B insulation and permanently lubricated bearings.
Shafts will be corrosion resistant.
Fan blades will be statically and dynamically balanced.
Condenser fan openings will be equipped with PVC-coated
steel wire safety guards.

Compressor
Compressor will be hermetically sealed.
Compressor will be mounted on rubber vibration isolators.
Condenser Coil
Condenser coil will be air cooled.
Coil will be constructed of aluminum fins mechanically bonded
to copper tubes which are then cleaned, dehydrated, and
sealed.
Refrigeration Components
Refrigeration circuit components will include liquid-line shutoff
valve with sweat connections, vapor-line shutoff valve with
sweat connections, system charge of Puron® (R-410A)
refrigerant, and compressor oil.

Operating Characteristics

The capacity of the unit will meet or exceed _____ Btuh at a
suction temperature of _____ °F. The power consumption at full
load will not exceed _____ kW.
Combination of the unit and the evaporator or fan coil unit will
have a total net cooling capacity of _____ Btuh or greater at
conditions of _____ CFM entering air temperature at the
evaporator at _____ °F wet bulb and _____ °F dry bulb, and air
entering the unit at _____ °F.
The system will have an SEER of _____ Btuh/watt or greater at
DOE conditions.

Electrical Requirements

Nominal unit electrical characteristics will be _____ v, single
phase, 60 hz. The unit will be capable of satisfactory operation
within voltage limits of _____ v to _____ v.
Unit electrical power will be single point connection.
Control circuit will be 24v.

Special Features

Refer to section of this literature identifying accessories and
descriptions for specific features and available enhancements.

Summary of Contents for DE LUXE 12 SEER 552A

Page 1: ...of the system and componentry The reliability of the existing Quantum Plus models has been proven to provide the lowest incidence of warranty service of any product in the Bryant family in the past fe...

Page 2: ...M A99067 DIMENSIONS IN UNIT SIZE SERIES UNIT DIMENSIONS MINIMUM MOUNTING PAD DIMENSIONS A B C D E F G H J K L M N 018 F 33 13 16 22 1 2 27 1 2 4 1 8 7 1 8 21 15 16 28 3 8 5 8 8 3 16 12 1 2 14 15 1 2 2...

Page 3: ...P L Y I N G W I T H A RI STANDARD 210 U N I T A R Y AIR CO N D I T I O N I N G EQUIPMENT CERTIFICATION APPLIES ONLY WHEN THE COMPLETE SYSTEM IS LISTED WITH ARI REGISTERED QUALITY SYSTEM As an ENERGY S...

Page 4: ...00 2400 2400 OPTIONAL EQUIPMENT Support Feet KSASF0101AAA Coastal Filter KAACF0701SML KAACF0801MED KAACF0701SML KAACF0801MED Time Delay Relay KAATD0101TDR Cycle Protector KSACY0101AAA Crankcase Heater...

Page 5: ...anch Circuit Fuse or Circuit Breaker Size Amps 40 40 60 COMPRESSOR REFRIGERANT Compressor Type Scroll Temperature Current Protection Internal Line Break Refrigerant Type Puron R 410A Amount Lb 5 43 5...

Page 6: ...6 Cycle Protector Solid state timing device which prevents compressor rapid recycling Control provides an approximate 5 minute delay after power to the compressor has been interrupted for any reason...

Page 7: ...ther debris to be flushed from the unit base minimizing corrosion SUGGESTED USE For improved sound ratings Coastal installations Windy areas or where debris is normally circulating Rooftop installatio...

Page 8: ...A024 17 500 TDR 13 00 13 00 11 80 CK5A CK5BW024 17 500 TDR 13 00 13 00 11 90 CK5PW024 17 500 TDR TXV 13 00 11 90 024 F CK5A CK5BA030 23 200 NONE 12 00 12 00 10 30 CC5A CD5AA024 23 000 NONE 11 70 11 70...

Page 9: ...TXV 12 00 10 70 CK5PW024 22 800 TXV 12 00 10 65 CK5PW030 23 000 TXV 12 00 10 70 F A B 4BN F C 024 23 000 TDR 12 00 12 00 10 75 F A B 4BN F C 030 23 400 TDR 12 00 12 00 10 85 FC4CNF024 23 000 TDR TXV...

Page 10: ...11 80 CK3BA030 22 600 TDR 13 00 13 00 11 85 CK5A CK5BA024 22 200 TDR 13 00 13 00 11 65 CK5A CK5BA030 22 600 TDR 13 00 13 00 11 75 CK5A CK5BW024 22 200 TDR 13 00 13 00 11 65 CK5A CK5BW030 22 600 TDR 13...

Page 11: ...00 10 40 COILS 315 A J AV036070 VARIABLE SPEED FURNACE CC5A CD5AA030 27 800 TDR 12 50 12 50 11 10 CC5A CD5AA036 28 800 TDR 13 00 13 00 11 45 CC5A CD5AW030 27 800 TDR 12 50 12 50 11 10 CE3AA030 28 200...

Page 12: ...12 00 10 55 CC5A CD5AW042 34 800 NONE 12 00 12 00 10 45 CE3AA036 34 600 NONE 11 70 11 70 10 45 CE3AA042 35 000 NONE 12 00 12 00 10 60 CF5AA036 34 800 NONE 12 00 12 00 10 50 CK3BA036 35 000 NONE 12 00...

Page 13: ...600 TDR TXV 13 00 11 45 CK5PT036 34 600 TDR TXV 13 00 11 40 CK5PT042 34 600 TDR TXV 13 00 11 45 CK5PW036 34 600 TDR TXV 13 00 11 40 COILS 315 A J AV066135 VARIABLE SPEED FURNACE CC5A CD5AA042 34 600 T...

Page 14: ...0 25 CE3AA048 40 000 NONE 12 00 12 00 10 30 CF5AA048 39 500 NONE 12 00 12 00 10 25 CK3BA042 39 500 NONE 11 70 11 70 10 20 CK3BA048 40 000 NONE 12 00 12 00 10 25 CK5A CK5BA042 39 500 NONE 11 70 11 70 1...

Page 15: ...11 10 CK5A CK5BW048 39 500 TDR 13 00 13 00 11 10 CK5PA042 39 000 TDR TXV 12 50 11 00 CK5PA048 39 500 TDR TXV 12 50 11 10 CK5PT042 39 000 TDR TXV 12 50 11 00 CK5PT048 39 500 TDR TXV 12 50 11 10 CK5PW0...

Page 16: ...10 35 CD5AA048 45 000 NONE 11 70 11 70 10 15 CE3AA048 45 000 NONE 11 70 11 70 10 25 CE3AA060 46 000 NONE 12 00 12 00 10 40 CF5AA048 44 000 NONE 11 70 11 70 10 20 CK3BA048 45 000 NONE 11 70 11 70 10 2...

Page 17: ...DR 12 50 12 50 11 25 CK5PA048 44 500 TDR TXV 12 00 10 80 CK5PA060 45 000 TDR TXV 12 50 11 05 CK5PT048 44 500 TDR TXV 12 00 10 80 CK5PT060 45 000 TDR TXV 12 50 11 05 CK5PW048 44 500 TDR TXV 12 00 10 80...

Page 18: ...85 FC4 B C NB070 58 000 TDR TXV 12 00 10 15 FG3AAA060 56 000 NONE 11 50 11 50 10 10 FK4 C D NB006 58 000 TDR TXV 12 50 12 50 10 75 FV4 A B NB006 58 000 TDR TXV 12 50 10 75 FX4 A B NB060 56 000 TDR TXV...

Page 19: ...elay Relay TXV Puron Thermostatic Expansion Valve NOTES 1 Ratings are net values reflecting the effects of circulating fan motor heat Supplemental electric heat is not included 2 Tested outdoor indoor...

Page 20: ...16 05 16 05 1 63 15 24 15 24 1 80 14 37 14 37 2 00 13 45 13 45 2 21 675 72 19 82 10 51 1 36 19 79 10 76 1 52 19 60 10 97 1 69 18 81 10 83 1 88 17 66 10 48 2 08 16 38 10 04 2 30 67 19 30 14 10 1 35 19...

Page 21: ...22 5 17 0 2 04 21 1 16 5 2 26 19 4 15 7 2 50 18 2 15 3 2 77 16 2 14 4 3 05 62 23 1 21 9 1 83 22 2 21 4 2 03 20 9 20 8 2 26 20 2 20 2 2 51 18 9 18 9 2 79 17 2 17 2 3 08 57 22 6 22 6 1 82 21 8 21 8 2 03...

Page 22: ...24 05 13 90 2 48 22 47 13 40 2 76 20 68 12 80 3 07 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacit...

Page 23: ...62 1 71 22 93 22 93 1 93 21 79 21 79 2 19 20 57 20 57 2 46 19 32 19 32 2 73 17 99 17 99 3 05 67 25 80 19 11 1 72 24 77 19 02 1 94 23 33 18 61 2 19 21 81 18 07 2 45 20 21 17 48 2 75 18 46 16 79 3 05 7...

Page 24: ...25 7 3 03 24 3 24 3 3 36 21 9 21 9 3 71 57 30 2 30 2 2 26 28 6 28 6 2 49 27 0 27 0 2 74 26 1 26 1 3 04 24 6 24 6 3 36 21 9 21 9 3 71 Multipliers for Determining the Performance With Other Indoor Secti...

Page 25: ...5 6 2 68 24 3 24 3 2 96 22 9 22 9 3 29 21 4 21 4 3 65 57 28 6 28 6 2 20 26 9 26 9 2 42 25 4 25 4 2 67 24 5 24 5 2 97 23 4 23 4 3 29 21 4 21 4 3 65 1125 72 34 1 17 8 2 30 33 1 17 6 2 54 31 4 17 0 2 79...

Page 26: ...3 37 31 8 31 8 3 73 29 4 29 4 4 11 26 4 26 4 4 53 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacit...

Page 27: ...57 36 6 36 6 2 73 35 2 35 2 3 03 33 6 33 6 3 37 31 8 31 8 3 73 29 4 29 4 4 11 26 4 26 4 4 53 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor S...

Page 28: ...36 3 36 3 4 36 33 2 33 2 4 82 29 9 29 9 5 33 57 41 1 41 1 3 20 39 6 39 6 3 55 37 4 37 4 3 92 36 2 36 2 4 36 33 1 33 1 4 82 30 3 30 3 5 34 Multipliers for Determining the Performance With Other Indoor...

Page 29: ...92 36 2 36 2 4 36 33 1 33 1 4 82 30 3 30 3 5 34 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity P...

Page 30: ...46 4 46 4 4 03 44 3 44 3 4 47 42 2 42 2 4 97 39 6 39 6 5 51 35 2 35 2 6 09 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooli...

Page 31: ...62 48 7 48 6 3 65 46 4 46 4 4 03 44 4 44 4 4 47 42 2 42 2 4 97 38 5 38 5 5 49 34 4 34 4 6 07 57 48 5 48 5 3 64 46 4 46 4 4 03 44 3 44 3 4 47 42 2 42 2 4 97 39 6 39 6 5 51 35 2 35 2 6 09 Multipliers f...

Page 32: ...36 7 7 64 63 58 6 42 9 4 46 55 0 41 3 4 94 51 2 39 7 5 47 49 2 38 8 6 11 44 4 36 8 6 76 39 2 34 7 7 47 62 57 5 53 4 4 44 54 0 51 7 4 92 50 6 50 0 5 46 48 8 48 8 6 10 45 6 45 6 6 79 41 6 41 6 7 55 57 5...

Page 33: ...24 2 18 17 2 133 2 43 15 6 143 2 69 40 TCG SDT KW 28 2 77 1 1 18 26 7 86 7 1 35 25 1 96 3 1 54 23 6 106 1 74 22 0 116 1 97 20 4 125 2 21 18 8 135 2 46 17 0 144 2 72 45 TCG SDT KW 30 8 78 7 1 18 29 1 8...

Page 34: ...1 25 6 124 3 13 23 3 133 3 48 20 8 142 3 83 40 TCG SDT KW 39 0 78 1 1 71 37 0 87 5 1 95 34 9 97 1 2 22 32 7 107 2 51 30 5 116 2 83 28 1 125 3 17 25 7 134 3 52 23 0 143 3 89 45 TCG SDT KW 42 5 79 9 1 7...

Page 35: ...Continued ARI listing applies only to systems shown in Ratings and Performance table kW Outdoor Unit Kilowatts only SDT Saturated Temperature Leaving Compressor F SST Saturated Temperature Entering C...

Page 36: ...Significant New Alternatives Program SNAP Unit Cabinet Unit cabinet will be constructed of galvanized steel bonderized and coated with a powder coat paint Fans Condenser fan will be direct drive prop...

Reviews: