background image

5

The coil can be connected to outdoor units using accessory
refrigerant line sets or field--supplied lines of refrigerant grade.
See Table 3 for coil connection tube size.

Table 3 – Coil Connection Tube Size

MODEL NUMBER

COIL CONNECTION TUBE SIZE

in (mm)

Liquid

Suction

CNPHP2417A

3/8 (10)

5/8 (16)

CNPHP3017A

3/8 (10)

3/4 (19)

CNPHP3617A

3/8 (10)

3/4 (19)

CNPHP4221A

3/8 (10)

7/8 (22)

CNPHP4821A

3/8 (10)

7/8 (22)

CNPHP6024A

3/8 (10)

7/8 (22)

CNPHP6124A

3/8 (10)

7/8 (22)

UNIT DAMAGE HAZARD

Failure to follow this caution may result in product damage.
To avoid valve damage to the refrigerant control device while

brazing, valves must be wrapped with a heat--sinking material

such as a wet cloth.

CAUTION

!

1. Remove cabinet access door.
2. Remove rubber plugs from coil stubs using a pulling and

twisting motion. Hold coil stubs steady to avoid bending or
distorting.

3. Wrap TXV and nearby tubing with a heat--sinking material

such as a wet cloth.

4. Fit refrigerant lines into coil stubs. Wrap a heat sinking

material such as a wet cloth behind braze joints.

5. Use 1/2 psig Nitrogen purge in the suction and out the

liquid line.

6. Braze using a Sil--Fos or Phos--copper alloy. Do not use soft

solder.

7. After brazing, allow joints to cool. Slide rubber grommets

over joints. Position tubing at center of each grommet to

ensure an air seal around the tube.

8. Always evacuate lines and reclaim refrigerant when making

connections or flaring refrigerant lines. Leak check
connections before insulating entire suction line.

9. If outdoor equipment will not be installed until a later date,

braze liquid and suction lines closed outside. Add a
Schraeder port test fitting to the suction line outside.

CONDENSATE DRAIN LINE CONNECTION

PROPERTY DAMAGE HAZARD

Failure to follow this caution may result in property damage.
When installing over a finished ceiling and/or living area,

install a field--fabricated secondary condensate pan under the

entire unit.

CAUTION

!

The coil is designed to dispose of accumulated water through
built--in condensate drain fittings. It is recommended that PVC

fittings be used on the condensate pan. Do not over--tighten. Finger
tighten plus 1--1/2 turns. Be sure to install plastic plug in unused

condensate drain fitting. Two 3/4--in. female threaded pipe

connections are provided in each coil condensate pan.
A trap is not necessary on the condensate line. Consult local codes

for additional restrictions or precautions. If local codes require a
trap then the following guidelines are suggested to assure proper

drainage. Install a trap in condensate line of coil as close to the coil

as possible. Make trap at least 3 in. (76 mm) deep and no higher
than the bottom of unit condensate drain opening (See Fig. 8).

Pitch condensate line 1 in. (25.4 mm) for every 10 ft. of length to
an open drain or sump. Make sure that the outlet of each trap is

below its connection to condensate pan to prevent condensate from

overflowing the drain pan. Prime all traps, test for leaks, and
insulate traps and lines if located above a living area.

3” / 76mm

A08067

Fig. 8 -- Condensate Trap

NOTE

: If unit is located in or above a living space, where damage

may result from condensate overflow, a field--supplied, external
condensate pan should be installed underneath the entire unit, and a
secondary condensate line (with appropriate trap) should be run
from the unit into the pan. Any condensate in this external
condensate pan should be drained to a noticeable place. As an
alternative to using an external condensate pan, some localities
may allow the running of a separate 3/4--in. (19 mm) condensate
line (with appropriate trap) per local code to a place where the
condensate will be noticeable. The owner of the structure must be
informed that when condensate flows from secondary drain or
external condensate pan, the unit requires servicing or water
damage will occur. To further protect against water damage, install
a float switch to shut the unit off if the water in the secondary pan
gets too high.

NOTE

: To avoid drainage problems, test the primary drain line by

slowly pouring water into the pan. Check piping for leaks and
proper condensate drainage. Using the secondary drain as
explained in the previous note provides further protection against
overflow due to a clogged primary drain.

NOTE

:

In applications where return air humidity levels stay at

70% or above for a prolonged period of time, condensation can
form on the bottom of pan and drip.

Summary of Contents for CNPHP

Page 1: ...t serious hazards which will result in severe personal injury or death WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage NOTE is used to highlight suggestions which will result in enhanced installation reliability or operation NOTE Nitrogen can leak out throu...

Page 2: ...ory installed hard shutoff TXV designed only for use with R 410A refrigerant Use only with outdoor units designed for R 410A NOTE All TXV S have preset superheat settings and are not field adjustable Cabinet Sweating If this unit is installed in a garage attic or other unconditioned space special attention needs to be given to the potential of cabinet sweating A 6 in 152 mm wide piece of insulatio...

Page 3: ...plication E Application J Coil Ductwork Airflow Furnace Coil Furnace Ductwork Airflow A13416 Fig 4 Horizontal Installation Applications Table 1 Heat Pump Applications Furnace Width In mm Coil Width In mm 14 356 17 5 445 21 533 24 5 622 14 356 A B C D E D E 17 5 445 A B C D E D E 21 533 A B C D E 24 5 622 A Not permitted Table 2 Air Conditioner Applications Furnace Width In mm Coil Width In mm 14 3...

Page 4: ... work platform using material in platform that will support the weight of an installer or a service person 2 Place work platform in front of discharge end of furnace 3 Secure platform to building joists Install coil To suspend CNPHP 1 Cut metal plumbers strap to desired lengths 2 Attach metal plumbers strap to four corners of coil casing see Fig 7 3 Use a minimum of two screws per corner to attach...

Page 5: ...hten Finger tighten plus 1 1 2 turns Be sure to install plastic plug in unused condensate drain fitting Two 3 4 in female threaded pipe connections are provided in each coil condensate pan A trap is not necessary on the condensate line Consult local codes for additional restrictions or precautions If local codes require a trap then the following guidelines are suggested to assure proper drainage I...

Page 6: ...ARD Failure to follow this warning could result in personal injury or death Provide trap with air gap in drain line when connecting to waste sewer line WARNING Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations E2014 Bryant Heating Cooling Systems D 7310 W Morris St D Indianapolis IN 46231 Edition Date 01 ...

Reviews: