5
The coil can be connected to outdoor units using accessory
refrigerant line sets or field--supplied lines of refrigerant grade.
See Table 3 for coil connection tube size.
Table 3 – Coil Connection Tube Size
MODEL NUMBER
COIL CONNECTION TUBE SIZE
in (mm)
Liquid
Suction
CNPHP2417A
3/8 (10)
5/8 (16)
CNPHP3017A
3/8 (10)
3/4 (19)
CNPHP3617A
3/8 (10)
3/4 (19)
CNPHP4221A
3/8 (10)
7/8 (22)
CNPHP4821A
3/8 (10)
7/8 (22)
CNPHP6024A
3/8 (10)
7/8 (22)
CNPHP6124A
3/8 (10)
7/8 (22)
UNIT DAMAGE HAZARD
Failure to follow this caution may result in product damage.
To avoid valve damage to the refrigerant control device while
brazing, valves must be wrapped with a heat--sinking material
such as a wet cloth.
CAUTION
!
1. Remove cabinet access door.
2. Remove rubber plugs from coil stubs using a pulling and
twisting motion. Hold coil stubs steady to avoid bending or
distorting.
3. Wrap TXV and nearby tubing with a heat--sinking material
such as a wet cloth.
4. Fit refrigerant lines into coil stubs. Wrap a heat sinking
material such as a wet cloth behind braze joints.
5. Use 1/2 psig Nitrogen purge in the suction and out the
liquid line.
6. Braze using a Sil--Fos or Phos--copper alloy. Do not use soft
solder.
7. After brazing, allow joints to cool. Slide rubber grommets
over joints. Position tubing at center of each grommet to
ensure an air seal around the tube.
8. Always evacuate lines and reclaim refrigerant when making
connections or flaring refrigerant lines. Leak check
connections before insulating entire suction line.
9. If outdoor equipment will not be installed until a later date,
braze liquid and suction lines closed outside. Add a
Schraeder port test fitting to the suction line outside.
CONDENSATE DRAIN LINE CONNECTION
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in property damage.
When installing over a finished ceiling and/or living area,
install a field--fabricated secondary condensate pan under the
entire unit.
CAUTION
!
The coil is designed to dispose of accumulated water through
built--in condensate drain fittings. It is recommended that PVC
fittings be used on the condensate pan. Do not over--tighten. Finger
tighten plus 1--1/2 turns. Be sure to install plastic plug in unused
condensate drain fitting. Two 3/4--in. female threaded pipe
connections are provided in each coil condensate pan.
A trap is not necessary on the condensate line. Consult local codes
for additional restrictions or precautions. If local codes require a
trap then the following guidelines are suggested to assure proper
drainage. Install a trap in condensate line of coil as close to the coil
as possible. Make trap at least 3 in. (76 mm) deep and no higher
than the bottom of unit condensate drain opening (See Fig. 8).
Pitch condensate line 1 in. (25.4 mm) for every 10 ft. of length to
an open drain or sump. Make sure that the outlet of each trap is
below its connection to condensate pan to prevent condensate from
overflowing the drain pan. Prime all traps, test for leaks, and
insulate traps and lines if located above a living area.
3” / 76mm
A08067
Fig. 8 -- Condensate Trap
NOTE
: If unit is located in or above a living space, where damage
may result from condensate overflow, a field--supplied, external
condensate pan should be installed underneath the entire unit, and a
secondary condensate line (with appropriate trap) should be run
from the unit into the pan. Any condensate in this external
condensate pan should be drained to a noticeable place. As an
alternative to using an external condensate pan, some localities
may allow the running of a separate 3/4--in. (19 mm) condensate
line (with appropriate trap) per local code to a place where the
condensate will be noticeable. The owner of the structure must be
informed that when condensate flows from secondary drain or
external condensate pan, the unit requires servicing or water
damage will occur. To further protect against water damage, install
a float switch to shut the unit off if the water in the secondary pan
gets too high.
NOTE
: To avoid drainage problems, test the primary drain line by
slowly pouring water into the pan. Check piping for leaks and
proper condensate drainage. Using the secondary drain as
explained in the previous note provides further protection against
overflow due to a clogged primary drain.
NOTE
:
In applications where return air humidity levels stay at
70% or above for a prolonged period of time, condensation can
form on the bottom of pan and drip.