Bryant ASPAS1BBA Owner'S Manual Download Page 9

Bryant

7

1.6

SYSTEM SET LED

The “System Set” LED is lit when all of the following

conditions are true:
1. The AUTO/OFF/MANUAL switch is set to the AUTO

position.

2. The utility voltage being supplied to the unit is being

sensed by the PCB. If the utility sense voltage is not

connected to the unit or if it is below 168 volts AC,

then the system set light will flash rapidly. This

indicates that if the AUTO/OFF/ MANUAL switch is

placed in the Auto position, the generator will start.

3. The “Not In Auto” dip switch is set to the OFF position

on the control board.

4. No alarms are present, for example, low oil pressure,

high temperature, etc.

1.7

FUEL REQUIREMENTS 
AND RECOMMENDATIONS

With LP gas, use only the vapor withdrawal 

system.

This type of system uses the vapors formed

above the liquid fuel in the storage tank.
The engine has been fitted with a fuel carburetion system

that meets the specifications of the 1997 California Air

Resources Board for tamper-proof dual fuel systems.

The unit will run on natural gas or LP gas, but it has been

factory set to run on natural gas. Should the primary fuel

need to be changed to LP gas, the fuel system needs to

be reconfigured. See Section 1.9 for instructions on

reconfiguration of the fuel system.
Recommended fuels should have a Btu content of at

least 1,000 Btus per cubic foot for natural gas; or at least

2,520 Btus per cubic foot for LP gas. Ask the fuel supplier

for the Btu content of the fuel.
Required fuel pressure for 

natural gas is 5 inches to 7

inches water colum (0.18 to 0.25 psi); and for liquid

propane, 11 inches to 14 inches of water column (0.4

to 0.5 psi).

NOTE:

Any piping used to connect the generator to the fuel

supply should be of adequate size to ensure the fuel

pressure NEVER drops below 4 inches water colum

for natural gas or 10 inches water column for liquid

propane for all load ranges.

1.8

FUEL CONSUMPTION

*Natural gas is in cubic feet per hour.

**LP is in gallons per hour/cubic feet per hour.

*** Values given are approximate.

Gaseous fuels such as natural gas and liquid
propane (LP) gas are highly explosive. Even the
slightest spark can ignite such fuels and cause
an explosion. No leakage of fuel is permitted.
Natural gas, which is lighter than air, tends to
collect in high areas. LP gas is heavier than air
and tends to settle in low areas.

1.9

LOCATION

1.9.1 GENERATOR

Install the generator set, in its protective enclosure,

outdoors, where adequate cooling and ventilating air is

always available. Consider these factors:
• Install the unit where air inlet and outlet openings will

not become obstructed by leaves, grass, snow, etc. If

prevailing winds will cause blowing or drifting, consider

using a windbreak to protect the unit.

• Install the generator on high ground where water

levels will not rise and endanger it.

• Allow sufficient room on all sides of the generator for

maintenance and servicing. A good rule is to allow

three feet of space on all sides.

• Where strong prevailing winds blow from one direction,

face the generator air inlet openings to the prevailing

winds.

• Install the generator as close as possible to the fuel

supply, to reduce the length of piping.

• Install the generator as close as possible to the

transfer switch. HOWEVER, REMEMBER THAT

LAWS OR CODES MAY REGULATE THE

DISTANCE.

The genset must be installed on a level surface. The

base frame must be level within two (2) inches all around.

1.9.2 TRANSFER SWITCH

1.9.2.1   7 kW, 12 kW and 15 kW Units

The transfer switch shipped with this generator is

enclosed in a NEMA 1 enclosure. 

This type of

enclosure is intended for indoor use only

. Follow

these rules:
• Install the transfer switch indoors on a firm, sturdy

supporting structure.

• To prevent switch distortion, level the switch if

necessary. This can be done by placing washers

between the switch enclosure and mounting surface.

• Never install the switch where water or any corrosive

substance might drip onto the enclosure.

• Protect the switch at all times against excessive

moisture, dust, dirt, lint, construction grit and corrosive

vapors.

DANGER

Section 1 — General Information

Bryant Air-cooled 7 kW, 12 kW and 15 kW Generators

Model #

Nat. Gas (*)

LP Vapor (**)

1/2 Load

Full Load

1/2 Load

Full Load

6/7 kW

66

119

0.82/30

1.47/54

12 kW

152

215

1.53/56

2.08/76

13/15 kW

156

220

1.58/58

2.40/88

Summary of Contents for ASPAS1BBA

Page 1: ...ic Standby Generators Models ASPAS1BBA007 6 kW NG 7 kW LP ASPAS1BBA012 12 kW NG 12 kW LP ASPAS1BBA015 13 kW NG 15 kW LP DEADLY EXHAUST FUMES OUTDOOR INSTALLATION ONLY DANGER Not intended for use as Pr...

Page 2: ...d or property of others This symbol points out potential explosion hazard This symbol points out potential fire hazard This symbol points out potential electrical shock hazard The operator is responsi...

Page 3: ...ery Installation 8 1 11 The Battery 8 Section 2 Operation 9 2 1 Break in Procedure 9 2 2 Using the Auto Off Manual Switch 9 2 3 Automatic Transfer Operation 10 2 4 Sequence of Automatic Operation 10 2...

Page 4: ...mpliance with applicable codes and standards Following installation do nothing that might render the system unsafe or in noncompliance with such codes and standards Keep hands feet clothing etc away f...

Page 5: ...ed in accordance with the manufacturer s instructions and recommendations Following proper installation do nothing that might alter a safe installation and render the unit in noncompliance with the af...

Page 6: ...the control panel to notify personnel that one of these faults has occurred There is also a System Set LED that is lit when all of the conditions describe in Section 1 3 are true 1 3 NEC REQUIREMENT F...

Page 7: ...ck Data Decal Control Panel Fuel Regulator Fuel Inlet GFCI Outlet Oil Filter Battery Compartment Exhaust Enclosure Oil Filter Battery Compartment Fuel Inlet GFCI Outlet Control Panel Data Decal Oil Di...

Page 8: ...as fuel Btu content ambient temperature altitude engine power and condition etc Maximum power decreases about 3 5 percent for each 1 000 feet above sea level and also will decrease about 1 percent for...

Page 9: ...liquid propane LP gas are highly explosive Even the slightest spark can ignite such fuels and cause an explosion No leakage of fuel is permitted Natural gas which is lighter than air tends to collect...

Page 10: ...hock and high short circuit current The following precautions are to be observed when working on batteries Remove the 7 5A and 15A fuses from the generator control panel Remove watches rings or other...

Page 11: ...unit will continue to run for one minute and then shut down 9 Allow the unit to cool 10 Set the generator s main circuit breaker to its OFF or OPEN position 11 Set the generator s AUTO OFF MANUAL swi...

Page 12: ...tor is not running This outlet is protected by a 15 amp circuit breaker located in the generator control panel Figure 3 1 2 4 SEQUENCE OF AUTOMATIC OPERATION The generator s control panel houses a con...

Page 13: ...e should shut down 4 Check that utility power supply to the transfer switch is turned OFF Do not attempt to activate the transfer switch manually until all power voltage supplies to the switch have be...

Page 14: ...light indicating an over crank failure The AUTO OFF MANUAL switch will need to be set to OFF and then back to AUTO to reset the generator control board NOTE If the fault is not repaired the over cran...

Page 15: ...kW Figure 3 3 Oil Dipstick and Fill 12 kW and 15 kW 3 3 CHANGING THE ENGINE OIL 3 3 1 ENGINE OIL RECOMMENDATIONS Use oil of American Petroleum Institute API Service Class SG SH or SJ Use all season S...

Page 16: ...side of the air box and around edges 4 Install the new air cleaner into the air box 5 Install the cover Turn the two cover screws clockwise to tighten See the Service Schedule Section 4 1 for air clea...

Page 17: ...trolyte contacts the eyes flush thoroughly and immediately with water and seek medical attention and Spilled electrolyte is to be washed down with an acid neutralizing agent A common practice is to us...

Page 18: ...completely Refill the crankcase with oil See Engine Oil Recommendations Section 3 3 1 7 Attach a tag to the engine indicating the viscosity and classification of the oil in the crankcase 8 Remove the...

Page 19: ...Repair is Needed FUEL Fuel lines and connections X M LUBRICATION Oil level X M Oil X AFTER BREAK IN AND Y Oil filter X AFTER BREAK IN AND Y COOLING Enclosure louvers X X W BATTERY Remove corrosion X X...

Page 20: ...and runs rough or damaged 2 Defective spark plug s 2 Clean re gap or replace plug s 3 Fuel Regulator not set 3 Set Fuel Regulator 4 Fuel Pressure incorrect 4 Confirm fuel pressure to regulator is 11...

Page 21: ...misuse abuse negligence or improper installation As with all mechanical devices the Bryant engines need periodic part s service and replacement to perform well Failures caused by any external cause or...

Page 22: ...ngine or a part component thereof has failed due to abuse neglect improper maintenance or unapproved modifications or the use of counterfeit and or grey market parts not made supplied or approved by G...

Page 23: ...elow Any such emissions related part repaired or replaced under the ECS Warranty shall be warranted for the remainder of the ECS Warranty Period prior to the first scheduled replacement point for such...

Page 24: ...PART NO 0F4108 13AS PA1 REV A 12 17 04 FORM OM18 1 PRINTED IN U S A...

Reviews: