Bryant ASPAS1BBA Owner'S Manual Download Page 13

Bryant

11

2.5

MANUAL TRANSFER OPERATION

2.5.1 TRANSFER TO GENERATOR 

POWER SOURCE

To start the generator and activate the transfer switch

manually, proceed as follows:
1. Set the generator’s AUTO/OFF/MANUAL switch 

to OFF.

2. Set the generator’s main circuit breaker to its OFF (or

open) position.

3. Turn OFF the utility power supply to the transfer

switch using the means provided (such as a 

utility main line circuit breaker).

Do not attempt to activate the transfer switch
manually until all power voltage supplies to
the switch have been positively turned off.
Failure to turn off all power voltage supplies
may result in extremely hazardous and possibly
fatal electrical shock.

4. Use the manual transfer handle inside the transfer

switch to move the main contacts to their “Standby”

position, i.e., loads connected to the standby power

source (Figure 2.2).

Figure 2.2 – Manual Transfer Switch Operation

5. To crank and start the engine, set the

AUTO/OFF/MANUAL switch to MANUAL.

6. Let the engine stabilize and warm up for a few

minutes.

7. Set the generator’s main circuit breaker to its ON (or

closed) position. The standby power source now

powers the loads.

2.5.2 TRANSFER BACK TO UTILITY POWER

SOURCE

When utility power has been restored, transfer back to

that source and shut down the generator. This can be

accomplished as follows:
1. Set the generator’s main circuit breaker to its OFF (or

open) position.

2. Let the engine run for a minute or two at no-load to

stabilize the internal temperatures.

3. Set the generator’s AUTO/OFF/MANUAL switch to 

its OFF (or open) position. The engine should 

shut down.

4. Check that utility power supply to the transfer switch

is turned OFF.

Do not attempt to activate the transfer switch
manually until all power voltage supplies 
to the switch have been positively turned off.
Failure to turn off all power voltage supplies
may result in extremely hazardous and possibly
fatal electrical shock.

5. Use the manual transfer handle inside the transfer

switch to move the main contacts back to their

UTILITY position, i.e., loads connected to the utility

power source (Figure 2.2).

6. Turn ON the utility power supply to the transfer

switch using the means provided.

7. Set the system to automatic operation as outlined in

“Automatic Transfer Operation,” Section 2.3.

2.6

SETTING THE EXERCISE TIMER

This generator is equipped with an exercise timer. Once

it is set, the generator will start and exercise once every

seven days, on the day of the week and at the time of day

the following sequence is completed. During this

exercise period, the unit runs for approximately 12

minutes and then shuts down. Transfer of loads to the

generator output does not occur during the exercise

cycle.
A switch on the control panel (see Figure 2.1) permits

selection of the day and time for the system to exercise.

At the chosen time, perform the following sequence to

select the desired day and time of day the system will

exercise.
1. Verify that the AUTO/OFF/MANUAL switch is set 

to AUTO.

2. Hold down the “Set Exercise Time” switch until the

generator starts (approximately 10 seconds) and

then release.

3. The generator will start and run for approximately 12

minutes and then shut down on its own. The

exerciser will then be set to run at that time of day

every week.

DANGER

‹

DANGER

‹

Section 2 — Operation

Bryant Air-cooled 7 kW, 12 kW and 15 kW Generators

Summary of Contents for ASPAS1BBA

Page 1: ...ic Standby Generators Models ASPAS1BBA007 6 kW NG 7 kW LP ASPAS1BBA012 12 kW NG 12 kW LP ASPAS1BBA015 13 kW NG 15 kW LP DEADLY EXHAUST FUMES OUTDOOR INSTALLATION ONLY DANGER Not intended for use as Pr...

Page 2: ...d or property of others This symbol points out potential explosion hazard This symbol points out potential fire hazard This symbol points out potential electrical shock hazard The operator is responsi...

Page 3: ...ery Installation 8 1 11 The Battery 8 Section 2 Operation 9 2 1 Break in Procedure 9 2 2 Using the Auto Off Manual Switch 9 2 3 Automatic Transfer Operation 10 2 4 Sequence of Automatic Operation 10 2...

Page 4: ...mpliance with applicable codes and standards Following installation do nothing that might render the system unsafe or in noncompliance with such codes and standards Keep hands feet clothing etc away f...

Page 5: ...ed in accordance with the manufacturer s instructions and recommendations Following proper installation do nothing that might alter a safe installation and render the unit in noncompliance with the af...

Page 6: ...the control panel to notify personnel that one of these faults has occurred There is also a System Set LED that is lit when all of the conditions describe in Section 1 3 are true 1 3 NEC REQUIREMENT F...

Page 7: ...ck Data Decal Control Panel Fuel Regulator Fuel Inlet GFCI Outlet Oil Filter Battery Compartment Exhaust Enclosure Oil Filter Battery Compartment Fuel Inlet GFCI Outlet Control Panel Data Decal Oil Di...

Page 8: ...as fuel Btu content ambient temperature altitude engine power and condition etc Maximum power decreases about 3 5 percent for each 1 000 feet above sea level and also will decrease about 1 percent for...

Page 9: ...liquid propane LP gas are highly explosive Even the slightest spark can ignite such fuels and cause an explosion No leakage of fuel is permitted Natural gas which is lighter than air tends to collect...

Page 10: ...hock and high short circuit current The following precautions are to be observed when working on batteries Remove the 7 5A and 15A fuses from the generator control panel Remove watches rings or other...

Page 11: ...unit will continue to run for one minute and then shut down 9 Allow the unit to cool 10 Set the generator s main circuit breaker to its OFF or OPEN position 11 Set the generator s AUTO OFF MANUAL swi...

Page 12: ...tor is not running This outlet is protected by a 15 amp circuit breaker located in the generator control panel Figure 3 1 2 4 SEQUENCE OF AUTOMATIC OPERATION The generator s control panel houses a con...

Page 13: ...e should shut down 4 Check that utility power supply to the transfer switch is turned OFF Do not attempt to activate the transfer switch manually until all power voltage supplies to the switch have be...

Page 14: ...light indicating an over crank failure The AUTO OFF MANUAL switch will need to be set to OFF and then back to AUTO to reset the generator control board NOTE If the fault is not repaired the over cran...

Page 15: ...kW Figure 3 3 Oil Dipstick and Fill 12 kW and 15 kW 3 3 CHANGING THE ENGINE OIL 3 3 1 ENGINE OIL RECOMMENDATIONS Use oil of American Petroleum Institute API Service Class SG SH or SJ Use all season S...

Page 16: ...side of the air box and around edges 4 Install the new air cleaner into the air box 5 Install the cover Turn the two cover screws clockwise to tighten See the Service Schedule Section 4 1 for air clea...

Page 17: ...trolyte contacts the eyes flush thoroughly and immediately with water and seek medical attention and Spilled electrolyte is to be washed down with an acid neutralizing agent A common practice is to us...

Page 18: ...completely Refill the crankcase with oil See Engine Oil Recommendations Section 3 3 1 7 Attach a tag to the engine indicating the viscosity and classification of the oil in the crankcase 8 Remove the...

Page 19: ...Repair is Needed FUEL Fuel lines and connections X M LUBRICATION Oil level X M Oil X AFTER BREAK IN AND Y Oil filter X AFTER BREAK IN AND Y COOLING Enclosure louvers X X W BATTERY Remove corrosion X X...

Page 20: ...and runs rough or damaged 2 Defective spark plug s 2 Clean re gap or replace plug s 3 Fuel Regulator not set 3 Set Fuel Regulator 4 Fuel Pressure incorrect 4 Confirm fuel pressure to regulator is 11...

Page 21: ...misuse abuse negligence or improper installation As with all mechanical devices the Bryant engines need periodic part s service and replacement to perform well Failures caused by any external cause or...

Page 22: ...ngine or a part component thereof has failed due to abuse neglect improper maintenance or unapproved modifications or the use of counterfeit and or grey market parts not made supplied or approved by G...

Page 23: ...elow Any such emissions related part repaired or replaced under the ECS Warranty shall be warranted for the remainder of the ECS Warranty Period prior to the first scheduled replacement point for such...

Page 24: ...PART NO 0F4108 13AS PA1 REV A 12 17 04 FORM OM18 1 PRINTED IN U S A...

Reviews: