7

AIR DELIVERY -- CFM (CONTINUED)

Unit Size

Cooling Switch Settings

External Static Pressure (ESP)

SW2-8

SW2-7

SW2-6

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

42060

Clg Default:

OFF

OFF

OFF

1330

1295

1260

1220

1190

1150

1110

1075

1045

1005

Cooling (SW2)

OFF

OFF

ON

725

660

600

520

435

See note 4

OFF

ON

OFF

780

725

660

615

540

See note 4

OFF

ON

ON

975

925

875

835

785

750

690

655

610

570

ON

OFF

OFF

1160

1120

1090

1045

1010

970

920

885

840

800

ON

OFF

ON

1330

1295

1260

1220

1190

1150

1110

1075

1045

1005

ON

ON

OFF

1705

1650

1595

1545

1475

1415

1340

1275

1200

1105

ON

ON

ON

1705

1650

1595

1545

1475

1415

1340

1275

1200

1105

Clg SW2:

Maximum Clg Airflow

2

1705

1650

1595

1545

1475

1415

1340

1275

1200

1105

Heating

(SW1)

High Heat Airflow

3

1145

1105

1075

1030

995

955

905

870

825

785

Low Heat Airflow

3

870

820

760

720

655

620

560

525

470

435

48080

Clg Default:

OFF

OFF

OFF

1805

1765

1720

1665

1610

1540

1475

1400

1315

1235

Cooling (SW2)

OFF

OFF

ON

775

635

455

230

See note 8

OFF

ON

OFF

840

740

675

625

555

See note 4

OFF

ON

ON

995

955

910

860

815

770

720

660

620

585

ON

OFF

OFF

1175

1140

1090

1060

1025

980

940

905

855

815

ON

OFF

ON

1325

1280

1245

1210

1180

1140

1105

1070

1025

990

ON

ON

OFF

1545

1515

1480

1445

1410

1380

1350

1315

1245

1175

ON

ON

ON

1805

1765

1720

1665

1610

1540

1475

1400

1315

1235

Clg SW2:

Maximum Clg Airflow

2

1805

1765

1720

1665

1610

1540

1475

1400

1315

1235

Heating

(SW1)

High Heat Airflow

3

1520

1490

1455

1420

1385

1355

1320

1285

1220

1155

Low Heat Airflow

3

1180

1145

1095

1065

1030

985

945

910

860

820

60080

Clg Default:

OFF

OFF

OFF

1905

1870

1825

1785

1750

1700

1665

1625

1560

1460

Cooling (SW2)

OFF

OFF

ON

950

770

620

515

440

365

See note 4

OFF

ON

OFF

1015

935

880

825

765

690

625

580

See note 4

OFF

ON

ON

1155

1105

1040

990

920

875

815

755

710

645

ON

OFF

OFF

1335

1290

1245

1190

1145

1085

1040

990

930

890

ON

OFF

ON

1520

1485

1435

1390

1340

1300

1255

1200

1160

1115

ON

ON

OFF

1905

1870

1825

1785

1750

1700

1665

1625

1560

1460

ON

ON

ON

2290

2230

2160

2085

2005

1915

1820

1730

1640

1525

Clg SW2:

Maximum Clg Airflow

2

2290

2230

2160

2085

2005

1915

1820

1730

1640

1525

Heating

(SW1)

High Heat Airflow

3

1575

1535

1485

1445

1400

1350

1310

1260

1215

1170

Low Heat Airflow

3

1230

1170

1125

1065

1015

955

900

855

795

755

NOTE

: See notes at end of table.

926T

A

Summary of Contents for 926TA

Page 1: ...t Surface Igniter S SmartEvap technology helps control humidity levels in the home when used with a compatible humidity control system S FanOn Plus technology allows control of continuous fan speed fr...

Page 2: ...and continues Bryant s tradition of technology leadership and innovation in providing a reliable and durable product Full Featured Variable Speed Motors Our variable speed ECM Electronically Commutat...

Page 3: ...U 120 120 000 BTU 140 140 000 BTU Not all familes have these models 0 90 AFUE 2 92 AFUE 3 93 AFUE 5 95 AFUE 6 96 AFUE 7 97 AFUE Example of a Model Number A14367 FURNACE COMPONENTS RATING PLATE NOT SHO...

Page 4: ...peed Selections Variable PWM Blower Wheel Dia x Width in 11 x 7 11 x 8 11 x 7 11 x 8 11 x 8 11 x 10 11 x 10 11 x 11 Air Filtration System Optional Media Cabinet Field Supplied Filter Filter Used for C...

Page 5: ...as Orifice Kit 46 Nat Gas LH32DB208 D D D D D D D D Gas Orifice Kit 47 Nat Gas LH32DB078 D D D D D D D D Gas Orifice Kit 48 Nat Gas LH32DB076 D D D D D D D D Gas Orifice Kit 54 LP LH32DB203 D D D D D...

Page 6: ...ON OFF 770 725 685 640 600 560 515 480 See note 4 OFF ON ON 945 910 875 835 800 770 735 695 665 635 ON OFF OFF 1140 1105 1075 1040 1005 970 930 885 835 790 ON OFF ON 1250 1210 1165 1115 1065 1015 965...

Page 7: ...770 720 660 620 585 ON OFF OFF 1175 1140 1090 1060 1025 980 940 905 855 815 ON OFF ON 1325 1280 1245 1210 1180 1140 1105 1070 1025 990 ON ON OFF 1545 1515 1480 1445 1410 1380 1350 1315 1245 1175 ON O...

Page 8: ...1890 1750 1645 1550 Clg SW2 Maximum Clg Airflow 2 note 8 2375 2300 2205 2115 2010 1890 1750 1645 1550 Heating SW1 High Heat Airflow 3 note 8 2375 2300 2205 2115 2010 1890 1750 1645 1550 Low Heat Airfl...

Page 9: ...2 NA NA 60 000 23 7 0 119 36 3 210 64 0 235 71 6 NA 80 000 15 4 6 59 18 0 155 47 2 210 64 0 232 70 7 100 000 NA 19 5 8 98 29 9 211 64 3 236 71 9 120 000 NA NA 8 2 4 86 26 2 224 68 3 140 000 4 NA NA NA...

Page 10: ...ent Vent Length TEVL 112 ft Add all of the above lines Maximum Equivalent Vent Length MEVL 127 ft For 2 pipe from Table 1 Is TEVL less than MEVL YES Therefore 2 pipe may be used Example 2 A direct ven...

Page 11: ...9 8 63 19 2 8001 to 9000 2438 to 2743 40 000 10 3 0 121 36 9 130 39 6 NA NA 60 000 7 2 1 82 25 0 152 46 3 168 51 2 NA 80 000 NA 35 10 7 111 33 8 148 45 1 156 47 5 100 000 NA NA 67 20 4 157 47 9 170 51...

Page 12: ...44 8 0 20 Ft 20 0 32 0 30 0 22 0 11 0 20 0 70 0 104 0 87 0 67 0 20 0 70 0 124 0 104 0 82 0 M 6 1 9 8 9 1 6 7 3 4 6 1 21 3 31 7 26 5 20 4 6 1 21 3 37 8 31 7 25 0 20 30 Ft 20 0 17 0 14 0 6 0 0 0 20 0 7...

Page 13: ...PLY AIR A10490 MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS POSITION CLEARANCE Rear 0 0 mm Front Combustion air openings in furnace and in structure 1 in 25 mm Required for service 24 in 610 mm All Sid...

Page 14: ...5 8 600 2 24 1 2 622 Furnace with or without Cased Coil Assembly or Coil Box 22 1 8 562 19 483 23 3 4 603 20 5 8 600 1 The plenum should be constructed 1 4 in 6 mm smaller in width and depth than the...

Page 15: ...FIELD SUPPLIED DISCONNECT AUXILIARY J BOX 24 V TERMINAL BLOCK THREE WIRE HEATING ONLY FIVE WIRE NOTE 1 NOTE 2 FIELD SUPPLIED DISCONNECT CONDENSING UNIT TWO WIRE FURNACE C O N T R O L R G COM W C R G Y...

Page 16: ...IMENSIONS IN INCH MM 22 2 7 8 7 8 22 2 POWER CONN AIR FLOW SEE NOTE 3 NOTES 1 Doors may vary by model 2 Minimum return air openings at furnace based on metal duct If flex duct is used see flex duct ma...

Page 17: ...Casing Casing shall be of 030 in thickness minimum pre painted steel Draft Inducer Motor Draft inducer motor shall be two speed PSC design Primary Heat Exchangers Primary heat exchangers shall be 3 P...

Page 18: ...e or change at any time specifications or designs without notice and without incurring obligations E2014 Bryant Heating Cooling Systems D 7310 W Morris St D Indianapolis IN 46231 Edition Date 09 14 Re...

Reviews: