background image

9

Venting System Length Calculations

The Total Equivalent Vent Length (TEVL) for

EACH

combustion air or vent pipe equals the length of the venting system, plus the equivalent

length of elbows used in the venting system from Table 3.
Standard vent terminations or factory accessory concentric vent terminations count for zero deduction.
See vent system manufacturer’s data for equivalent lengths of flexible vent pipe or other termination systems.

DO NOT ASSUME

that one

foot of flexible vent pipe equals one foot of straight PVC/ABS DWV vent pipe.
Compare the Total Equivalent Vent Length to the Maximum Equivalent Vent Lengths in Table 2.

Example 1

A direct--vent 60,000 Btuh furnace installed at 2100 ft. (640 M). Venting system includes,

FOR EACH PIPE

, 100 feet (30 M) of vent pipe,

95 feet (28 M) of combustion air inlet pipe, (3) 90

_

long radius elbows, (2) 45

_

long radius elbows and a factory accessory concentric vent

kit.
Can this application use 2--in. (50 mm ND) PVC/ABS DWV vent piping?

Measure the required linear length of air inlet and vent pipe; insert the

longest of the two here:

100 ft

Use length of the longer of the vent

or air inlet piping system

Add equiv length of (3) 90º long-radius elbows

(use the highest number of elbows for either the

vent or inlet pipe)

3

x

3 ft

=

9 ft.

From Table 3

Add equiv length of (2) 45º long-radius elbows

(use the highest number of elbows for either the

vent or inlet pipe)

2

x

1.5 ft

=

3 ft.

From Table 3

Add equiv length of vent termination

0 ft.

From Table 3

Add correction for flexible vent pipe, if any

0 ft.

From Vent Manufacturer’s instructions;

zero for PVC/ABS DWV

Total Equivalent Vent Length (TEVL)

112 ft.

Add all of the above lines

Maximum Equivalent Vent Length (MEVL)

127 ft.

For 2” pipe from Table 2

Is TEVL less than MEVL?

YES

Therefore, 2” pipe may be used

Example 2

A direct--vent 60,000 Btuh furnace installed at 2100 ft. (640 M) Venting system includes,

FOR EACH PIPE

, 100 feet (30 M) of vent pipe,

95 feet (28 M) of combustion air inlet pipe, (3) 90

_

long radius elbows, and a polypropylene concentric vent kit. Also includes 20 feet (6 M)

of flexible polypropylene vent pipe, included within the 100 feet (30 M) of vent pipe.
Assume that one meter of flexible 60 mm or 80 mm polypropylene pipe equals 2 Meters of PVC/ABS pipe.

VERIFY FROM VENT

MANUFACTURER’S INSTRUCTIONS.

Can this application use 60 mm (O.D.) polypropylene vent piping? If not what size piping can be used?

Measure the required linear length of air inlet and vent pipe; insert the

longest of the two here:

100 ft

Use length of the longer of the vent

or air inlet piping system

Add equiv length of (3) 90º long-radius elbows

(use the highest number of elbows for either the

vent or inlet pipe)

3

x

3 ft

=

9 ft.

From Vent Manufacturer’s instructions

Add equiv length of (2) 45º long-radius elbows

(use the highest number of elbows for either the

vent or inlet pipe)

0

x

=

0 ft.

From Vent Manufacturer’s instructions

Add equiv length of vent termination

9 M

x

3 ft/M

=

18 ft.

From Vent Manufacturer’s instructions

Add correction for flexible vent pipe, if any

1.8

x

20 ft

=

36 ft.

From Vent Manufacturer’s instructions

Total Equivalent Vent Length (TEVL)

163 ft.

Add all of the above lines

Maximum Equivalent Vent Length (MEVL)

127 ft.

For 2” pipe from Table 2

Is TEVL less than MEVL?

NO

Therefore, 60mm pipe may NOT be used;

try 80 mm

Maximum Equivalent Vent Length (MEVL)

250 ft.

For 3” pipe from Table 2

Is TEVL less than MEVL?

YES

Therefore, 80 mm pipe may be used

NOTES

:

1. Use only the smallest diameter pipe possible for venting. Over---sizing may cause flame disturbance or excessive vent terminal icing or freeze---up.
2. NA --- Not allowed. Pressure switch will not close, or flame disturbance may result.
3. Total equivalent vent lengths under 10’ for 40,000 BTUH furnaces from 0 to 2000 ft. (0 to 610 M) above sea level require use of an outlet choke plate .

Failure to use an outlet choke when required may result in flame disturbance or flame sense lockout.

4. Not all furnace families include 140,000 BTUH input models.
5. Vent sizing for Canadian installations over 4500 ft (1370 M) above sea level are subject to acceptance by local authorities having jurisdiction.
6. Size both the combustion air and vent pipe independently, then use the larger size for both pipes.
7. Assume the two 45

_

elbows equal one 90

_

elbow. Wide radius elbows are desirable and may be required in some cases.

8. Elbow and pipe sections within the furnace casing and at the vent termination should not be included in vent length or elbow count.
9. The minimum pipe length is 5 ft. (2 M) linear feet (meters) for all applications.

10. Use 3---in. (76 mm) diameter vent termination kit for installations requiring 4---in. (102 mm) diameter pipe.

912SC

Summary of Contents for 912SC

Page 1: ...eight 35 cabinet short enough for taller coils but still allows enough room for service S Silicon Nitride Perfect Lightt Hot Surface Igniter S Aluminized steel primary heat exchanger S Stainless steel...

Page 2: ...product a design with more than ten years of field proven performance and success These innovations paired with the continuation of a crimped no weld seam create an efficient robust design for this e...

Page 3: ...970 2050 Cooling Capacity tons 400 CFM ton 2 5 2 5 2 5 3 5 4 4 5 3 5 5 5 350 CFM ton 2 5 3 3 4 4 5 5 0 4 0 5 5 5 5 Direct Drive Motor Type Permanent Split Capacitor PSC Direct Drive Motor HP 0 3 0 5 0...

Page 4: ...U 120 120 000 BTU 140 140 000 BTU Not all familes have these models 0 90 AFUE 2 92 AFUE 3 93 AFUE 5 95 AFUE 6 96 AFUE 7 97 AFUE Example of a Model Number A12374 FURNACE COMPONENTS RATING PLATE NOT SHO...

Page 5: ...Nat Gas LH32DB202 D D D D D D D D D Gas Orifice Kit 44 Nat Gas LH32DB200 D D D D D D D D D Gas Orifice Kit 45 Nat Gas LH32DB205 D D D D D D D D D Gas Orifice Kit 46 Nat Gas LH32DB208 D D D D D D D D...

Page 6: ...nge 3 5 397 1485 1470 1455 1430 1390 1340 1280 1205 1120 1035 Blue 3 2 5 426 1120 1110 1100 1090 1065 1035 990 935 870 805 Red 3 2 0 433 940 920 910 890 865 830 790 745 690 625 048100 SIDE BOTTOM Blac...

Page 7: ...Temp C Unit Size 40 000 BTUH 60 000 BTUH Uninsulated 3 8 in Insulation 1 2 in Insulation Uninsulated 3 8 in Insulation 1 2 in Insulation Pipe Dia mm 38 51 64 38 51 64 38 51 64 38 51 64 76 38 51 64 76...

Page 8: ...ize 40 000 Outlet choke required under 10 ft TEVL 60 000 80 000 100 000 120 000 140 000 Altitude meters Pipe Dia mm 38 51 64 38 5 64 76 38 51 64 76 102 51 64 76 102 64 76 102 64 76 102 0 610 6 26 57 6...

Page 9: ...eters of PVC ABS pipe VERIFY FROM VENT MANUFACTURER S INSTRUCTIONS Can this application use 60 mm O D polypropylene vent piping If not what size piping can be used Measure the required linear length o...

Page 10: ...PLY AIR A10490 MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS POSITION CLEARANCE Rear 0 0 mm Front Combustion air openings in furnace and in structure 1 in 25 mm Required for service 24 in 610 mm All Sid...

Page 11: ...1 2 YES YES NO YES 60 000 14 3 16 YES YES NO YES 17 1 2 YES NO NO YES 80 000 17 1 2 YES YES NO YES 21 YES YES NO YES 100 000 21 YES YES NO YES 120 000 24 1 2 YES YES NO YES INPUT CASING WIDTH INCHES...

Page 12: ...5 8 600 2 24 1 2 622 Furnace with or without Cased Coil Assembly or Coil Box 22 1 8 562 19 483 23 3 4 603 20 5 8 600 1 The plenum should be constructed 1 4 in 6 mm smaller in width and depth than the...

Page 13: ...SUPPLIED DISCONNECT AUXILIARY J BOX 24 V TERMINAL BLOCK THREE WIRE HEATING ONLY FIVE WIRE NOTE 1 NOTE 2 FIELD SUPPLIED DISCONNECT CONDENSING UNIT TWO WIRE FURNACE C O N T R O L R G COM W C R G Y GND...

Page 14: ...S IN INCH MM 22 2 7 8 7 8 22 2 POWER CONN AIR FLOW SEE NOTE 3 NOTES 1 Doors may vary by model 2 Minimum return air openings at furnace based on metal duct If flex duct is used see flex duct manufactur...

Page 15: ...accessory highly efficient Media Filter is available as an option _____________ Media Filter Casing Casing shall be of 030 in thickness minimum pre painted steel Draft Inducer Motor Draft inducer mot...

Page 16: ...e or change at any time specifications or designs without notice and without incurring obligations E2014 Bryant Heating Cooling Systems D 7310 W Morris St D Indianapolis IN 46231 Edition Date 10 14 Re...

Reviews: