PERFORMANCE DATA (CONT)–STANDARD ECM INDOOR MOTOR
COOLING EXTENDED PERFORMANCE TABLE
HEATING EXTENDED PERFORMANCE TABLE
-10–20
HEATING EXTENDED PERFORMANCE TABLE
30–60
*At 75°F entering dry bulb—Tennessee Valley Authority [TVA] rating conditions; all others at 80°F entering dry bulb.
See Legend and Notes on page 17.
604B060 COOLING PERFORMANCE TABLE
Temp (F)
Outdoor Air
Entering
Condenser
Evaporator Air—CFM/BF
1500/0.004
1750/0.007
2000/0.01
Evaporator Air — Ewb (F)
62
63*
67
72
62
63*
67
72
62
63*
67
72
75
TC
57.2
58.2
62.4
68.1
58.8
59.7
64.0
69.8
60.0
60.8
64.9
70.8
SHC
49.4
47.9
41.6
33.8
53.6
51.8
44.5
35.4
57.6
55.4
47.1
36.8
kW
4.1
4.1
4.2
4.2
4.2
4.3
4.3
4.4
4.4
4.4
4.5
4.6
85
TC
54.7
55.6
59.7
65.2
56.2
57.0
61.1
66.6
57.4
58.1
61.9
67.4
SHC
48.2
46.7
40.4
32.6
52.4
50.5
43.2
34.2
56.3
54.2
45.8
35.6
kW
4.5
4.5
4.6
4.7
4.7
4.7
4.8
4.9
4.8
4.9
5.0
5.0
95
TC
52.2
53.0
56.9
62.0
53.5
54.3
58.0
63.2
55.0
55.3
58.7
64.1
SHC
47.0
45.4
39.2
31.4
51.1
49.2
41.9
32.9
55.0
52.9
44.5
34.4
kW
5.0
5.0
5.1
5.2
5.1
5.2
5.3
5.3
5.2
5.3
5.5
5.5
105
TC
49.4
50.2
53.8
58.7
50.7
51.4
54.8
59.6
52.5
52.4
55.4
60.2
SHC
45.7
44.1
37.9
30.1
49.8
47.9
40.6
31.6
52.5
51.6
43.2
33.0
kW
5.5
5.6
5.6
5.7
5.7
5.7
5.8
5.9
5.8
5.8
6.0
6.1
115
TC
46.5
47.2
50.5
55.0
48.1
48.3
51.3
56.8
49.7
49.7
51.8
57.0
SHC
44.3
42.7
36.4
28.7
48.1
46.6
39.2
30.6
49.7
49.7
41.8
31.7
kW
6.1
6.2
6.2
6.3
6.2
6.3
6.4
6.4
6.4
6.4
6.6
6.6
125
TC
43.3
43.9
46.7
52.2
45.2
45.1
47.4
52.5
46.4
46.4
47.9
52.2
SHC
42.8
41.2
34.9
27.8
45.2
45.1
37.6
28.9
46.4
46.4
40.2
29.7
kW
6.7
6.8
6.8
6.8
6.8
6.9
7.0
7.0
7.0
7.0
7.2
7.2
604B060
Return
Air (F db)
CFM (Standard Air)
Air Temperature Entering Outdoor Coil (F db at 70% rh)
-10
0
10
17
20
60
1500
TC
17.89
16.55
22.37
20.58
27.39
25.14
27.90
25.44
33.30
30.20
kW
3.14
3.33
3.56
3.71
3.76
1750
TC
18.44
17.06
22.91
21.08
28.07
25.77
32.32
29.47
34.25
31.06
kW
3.23
3.39
3.60
3.74
3.78
2000
TC
19.03
17.60
23.49
21.62
28.75
26.38
33.08
30.16
35.08
31.81
kW
3.36
3.50
3.70
3.82
3.86
70
1500
TC
16.20
14.98
21.25
19.55
26.32
24.16
30.28
27.61
32.03
29.05
kW
3.36
3.66
3.89
4.09
4.14
1750
TC
16.82
15.56
21.85
20.11
26.96
24.74
31.00
28.26
32.81
29.76
kW
3.48
3.74
3.96
4.12
4.16
2000
TC
17.49
16.17
22.50
20.71
27.85
25.56
31.74
28.94
33.60
30.47
kW
3.62
3.86
4.07
4.21
4.25
80
1500
TC
13.77
12.73
19.62
18.05
25.11
23.05
28.93
26.37
30.64
27.79
kW
3.50
3.94
4.24
4.47
4.54
1750
TC
14.42
13.34
20.32
18.69
25.79
23.67
29.68
27.06
31.43
28.50
kW
3.63
4.04
4.31
4.52
4.57
2000
TC
15.10
13.96
21.01
19.33
26.48
24.31
30.45
27.76
32.22
29.22
kW
3.79
4.19
4.42
4.62
4.67
604B060
Return
Air (F db)
CFM (Standard Air)
Air Temperature Entering Outdoor Coil (F db at 70% rh)
30
40
47
50
60
60
1500
TC
40.88
35.82
49.46
49.46
54.82
54.82
58.83
58.83
63.53
63.53
kW
3.98
4.26
4.47
4.53
4.71
1750
TC
42.02
36.82
50.89
50.89
56.64
56.64
58.34
58.34
61.76
61.76
kW
3.97
4.25
4.33
4.38
4.51
2000
TC
43.05
37.72
52.52
52.52
56.01
56.01
57.04
57.04
60.19
60.19
kW
4.03
4.26
4.30
4.34
4.46
70
1500
TC
39.08
34.24
47.32
47.32
52.27
52.27
53.85
53.85
58.08
58.08
kW
4.36
4.64
4.80
4.86
4.99
1750
TC
40.15
35.18
48.73
48.73
56.00
56.00
58.71
58.71
66.11
66.11
kW
4.35
4.60
4.82
4.88
5.08
2000
TC
41.14
36.05
49.89
49.89
56.89
56.89
58.64
58.64
62.11
62.11
kW
4.40
4.65
4.79
4.84
4.97
80
1500
TC
37.15
32.55
39.76
39.76
41.79
41.79
42.85
42.85
46.59
46.59
kW
4.77
4.80
4.82
4.87
5.01
1750
TC
38.40
33.64
45.36
45.36
47.19
47.19
48.68
48.68
52.98
52.98
kW
4.78
4.95
4.96
5.01
5.15
2000
TC
39.35
34.48
47.88
47.88
52.12
52.12
53.40
53.40
59.14
59.14
kW
4.84
5.06
5.13
5.16
5.32