background image

pre-programmed table of airflows.
The unit must be configured to operate properly with system
components with which it is installed. To successfully configure a
basic system (see information printed on circuit board label located
next to select pins), move the 6 select wires to the pins which
match the components used (See Fig. 8).

a. GAS HEAT/CFM—SELECT GAS HEAT INPUT SIZE

Factory selected gas heat size should correspond to unit label.

b. AC/HP SIZE—SELECT SYSTEM SIZE INSTALLED

Factory selected air conditioner size should correspond to
capacity of unit installed. Installer should verify air conditioner
size to ensure that airflow delivered falls within proper range
for the size unit installed. This applies to all operational modes.

c. SYSTEM TYPE—SELECT SYSTEM TYPE INSTALLED

Factory selected on 583B for AC-Air conditioner.
For Gas Heat/Electric Cool Unit–AC must be selected.

d. AC/HP CFM ADJUST—SELECT NOMINAL, LOW, OR

HIGH AIRFLOW

The AC/HP CFM Adjust select is factory set to the High-HI
(NOM for 060) tap. The CFM Adjust selections NOM/LO will
regulate airflow supplied for all operational modes, except
non-heat pump heating modes. HI provides 15 percent airflow
over nominal unit size selected and LO provides 10 percent
airflow below nominal unit size selected. Adjust selection
options are provided to adjust airflow supplied to meet indi-
vidual installation needs for such things as noise, comfort, and
humidity removal (See Fig. 8, D as indicated).

e. ON/OFF DELAY—SELECT DESIRED

TIME DELAY PROFILE

Four motor operation delay profiles are provided to customize
and enhance system operation (See Fig. 8, E as indicated).
Selection options are:
(1.) The standard 90 sec off delay (Factory Setting) at 100

percent airflow in cooling mode. In heating mode, IGC
will control 45 sec on delay with no airflow and 45 sec off
delay.

(2.) A 30 sec cooling delay with no airflow/ 90 sec off delay at

100 percent airflow profile is used when it is desirable to
allow system coils time to cool-down in conjunction with
the airflow in heating mode.

(3.) A no delay option used for servicing unit or when a

thermostat is utilized to perform delay functions in cooling
mode. In heating mode IGC will control 45 sec on delay
with no airflow and 45 sec off delay.

(4.) Not recommended for 583B

f. CONTINUOUS FAN—SELECT DESIRED FAN SPEED

WHEN THERMOSTAT IS SET ON CONTINUOUS FAN

(1.) LO speed—Factory setting, 50 percent cooling mode

airflow.

(2.) MED speed—Move connector to MED, 65 percent cooling

mode airflow.

(3.) HI speed—Move connector to HI, 100 percent cooling

mode airflow (See Fig. 8, F as indicated).

g. LOW-VOLTAGE CIRCUIT FUSING AND REFERENCE

The low-voltage circuit is fused by a board-mounted 5–amp
automotive fuse placed in series with the transformer SEC2 and
the R circuit. The C circuit of the transformer is referenced to
chassis ground through a printed circuit run at SEC1 connected
to metal standoff marked with ground symbol.

h. BASIC UNIT CONFIGURATION

The following basic configuration of the indoor motor will
provide ARI rated performance of the 583B. This BASIC
CONFIGURATION should be used when the rated ARI perfor-
mance is required, or if system enhancements such as super
dehumidify are not needed.
(1.) HEAT-Factory selected to match heat input size.

(2.) AC/HP Size-Factory selected to match system size, please

verify.

Fig. 4—702B High- and Control-Voltage

Connections

C01027

POWER
SUPPLY

FIELD-SUPPLIED
FUSED DISCONNECT

HIGH VOLTAGE
POWER LEADS
(SEE UNIT WIRING
LABEL)

GND

CONTROL BOX

SPLICE BOX

LOW-VOLTAGE
POWER LEADS
(SEE UNIT
WIRING LABEL)

YEL(Y)

GRN(G)

RED(R)

BRN(C)

THERMOSTAT
(TYPICAL)

LEGEND

Field Control-Voltage Wiring
Field High-Voltage Wiring

BLK(DH)

DHUM

Y

G

R

C

W1

WHI(W1)

GRA(W2)

W2

Fig. 5—602B High- and Control-Voltage

Connections

C01028

POWER
SUPPLY

FIELD-SUPPLIED
FUSED DISCONNECT

HIGH VOLTAGE
POWER LEADS
(SEE UNIT WIRING
LABEL)

GND

CONTROL BOX

SPLICE BOX

LOW-VOLTAGE
POWER LEADS
(SEE UNIT
WIRING LABEL)

YEL(Y)

GRN(G)

RED(R)

BRN(C)

THERMOSTAT
(TYPICAL)

LEGEND

Field Control-Voltage Wiring
Field High-Voltage Wiring

BLK(DH)

DHUM

Y

G

R

C

W1

WHI(W1)

GRA(W2)

W2

ORN(0)

O

—3—

Summary of Contents for 602B

Page 1: ...or all brazing operations WARNING Improper installation adjustment alter ation service maintenance or use can cause explosion fire electric shock or other occurrences which could cause serious injury...

Page 2: ...from the installer s packet included with unit and install grommet in the knockout opening Provide a drip loop before running wire through panel Run the low voltage leads from the thermostat through...

Page 3: ...t is desirable to allow system coils time to cool down in conjunction with the airflow in heating mode 3 A no delay option used for servicing unit or when a thermostat is utilized to perform delay fun...

Page 4: ...energized If the installation includes the use of this operating mode do not use these terminals to control accessories See Electronic Air Cleaner and Humidifier sections for further information b EL...

Page 5: ...onents used See Fig 8 a GAS HEAT CFM SELECT GAS HEAT INPUT SIZE Factory selected gas heat size should correspond to unit label b AC HP SIZE SELECT SYSTEM SIZE INSTALLED Factory selected air conditione...

Page 6: ...stem size please verify 3 SYSTEM TYPE Factory selected on 683B system for HP EFF 4 AC HP CFM ADJUST Select NOM Lo for 060 5 ON OFF DELAY Select ENH profile 6 CONTINUOUS FAN Select desired fan speed wh...

Page 7: ...Occurs if outdoor temperature is above outdoor temperature change over setpoint 1 Thermidistat closes circuit R to G and R to Y Y2 The unit delivers selected heat pump heating airflow g HEATING MODE...

Page 8: ...rt This will minimize cold blow in heat pump operation 602B only and could enhance system efficiency f CONTINUOUS FAN SELECT DESIRED FAN SPEED WHEN THERMOSTAT IS SET ON CONTINUOUS FAN 1 LO speed Facto...

Page 9: ...it board provides connection terminals for use of a standard humidistat The unit will detect the humidistat contacts opening on increasing humidity and reduce its airflow to approximately 80 percent o...

Page 10: ...y minimal If a substantial adjustment is indicated an abnormal condition exists somewhere in the cooling system such as insuf ficient airflow across either one or both coils I 583B START UP ICM FIOP C...

Page 11: ...switches in AUTO positions Observe that unit operates in heating mode when tempera ture control is set to call for heating above room temperature and operates in cooling mode when tempera ture contro...

Page 12: ...ide assembly out Be careful not to tear insulation in blower compartment e Ensure proper reassembly by marking blower wheel and motor in relation to blower housing before disassembly TABLE 1 ICM FIOP...

Page 13: ...Quantity lb 9 5 9 5 9 5 10 0 10 0 10 0 REFRIGERANT METERING DEVICE Orifice ID in Check Flo Rater Piston 073 073 073 086 086 086 CONDENSER COIL Rows Fins in Face Area sq ft 2 17 12 3 2 17 12 3 2 17 12...

Page 14: ...Fig 14 ICM FIOP Electric Schematic Unit 583B C01035 14...

Page 15: ...OUTDOOR FAN Nominal Cfm Diameter in Motor Hp Rpm 2350 22 1 8 825 2350 22 1 8 825 2350 22 1 8 825 2500 22 1 4 1100 2500 22 1 4 1100 2350 22 1 8 825 2350 22 1 8 825 INDOOR COIL Rows Fins in Face Area sq...

Page 16: ...7 INDOOR BLOWER Nominal Airflow Cfm Size in Motor HP 1600 11 X 10 3 4 1600 11 X 10 3 4 1600 11 X 10 3 4 1750 11 X 10 1 0 1750 11 X 10 1 0 1750 11 X 10 1 0 FURNACE SECTION Burner Orifice No Qty Drill S...

Page 17: ...Fig 15 ICM FIOP Electric Schematic Unit 683B C01101 17...

Page 18: ...7 12 3 2 17 12 3 2 17 16 4 CONDENSER FAN Nominal Cfm Diameter in Motor Hp Rpm 2350 22 1 8 825 2350 22 1 8 825 2350 22 1 8 825 2350 22 1 8 825 3300 22 1 4 1100 3300 22 1 4 1100 EVAPORATOR COIL Rows Fin...

Page 19: ...50 50 60 70 80 90 042 208 230 1 60 187 253 18 6 105 0 0 9 6 8 3 8 5 0 5 4 7 2 7 5 10 0 11 3 15 0 15 0 20 0 18 1 20 8 25 9 30 0 36 1 41 7 54 2 62 5 72 2 83 3 31 0 31 0 31 1 34 5 40 9 46 0 53 6 60 6 76...

Page 20: ...Fig 16 ICM FIOP Electrical Schematic 702B C01037 20...

Page 21: ...IL Rows Fins in face area sq ft 2 17 8 5 2 17 10 3 2 17 10 3 2 17 13 5 2 17 13 5 2 17 15 4 OUTDOOR FAN Nominal Airflow CFM Diameter Motor HP RPM 2350 22 1 8 825 2350 22 1 8 825 2800 22 1 4 1100 2500 2...

Page 22: ...40 40 60 60 70 80 80 90 100 110 042 208 230 1 60 187 253 22 4 105 0 0 9 6 8 3 8 5 0 5 4 7 2 7 5 10 0 11 3 15 0 15 0 20 0 18 1 20 8 25 9 30 0 36 1 41 7 54 2 62 5 72 2 83 3 35 7 35 7 58 3 61 7 68 1 73 2...

Page 23: ...Fig 17 ICM FIOP Electrical Schematic 602B c01036 23...

Page 24: ...n selections deliver equal airflow TABLE 12 583B 683B COOLING AND HEAT PUMP HEATING 683B ONLY DRY COIL ICM AIRFLOW LARGE CABINET UNIT SIZE CFM ADJUST PIN SELECT LO PIN NOM PIN HI PIN EXTERNAL STATIC P...

Page 25: ...1600 53 35 65 170 130 1750 54 40 70 175 060 90 1600 41 25 55 155 115 1600 53 35 65 170 130 1800 53 40 70 175 TABLE 16 702B 602B COOLING HEATING DRY COIL ICM AIRFLOW SMALL CABINET UNIT SIZE CFM ADJUST...

Page 26: ...N WG SMALL CABINET STATIC CFM 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 5 kW 0 00 0 00 0 00 0 00 0 00 0 00 0 00 0 00 0 02 0 04 0 06 0 07 7 5 kW 0 00 0 00 0 00 0 00 0 00 0 00 0 02 0 03 0 0...

Page 27: ...60 0 029 0 032 0 036 0 040 0 045 0 049 0 053 TABLE 22 FILTER PRESSURE DROP TABLE IN WG FILTER SIZE CFM 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 20 X 20...

Page 28: ...Super Dehumidify set to ON Option 12 Heaters during Defrost setting 2 is suggested for all heaters Option 16 Heat pump systems set to ON for warmer heat below 40 F Option 17 Select programmable or no...

Page 29: ...TDOOR CONDENSER AIR TEMPERATURE ___________DB RETURN AIR TEMPERATURE ___________DB ___________WB COOLING SUPPLY AIR ___________DB ___________WB HEAT PUMP SUPPLY AIR ___________ GAS HEAT SUPPLY AIR ___...

Page 30: ...2001 Bryant Heating Cooling Systems 7310 W Morris St Indianapolis IN 46231 30 Printed in U S A ii583b243 Catalog No 5358 308...

Reviews: