f. Loosen set-screw that secures wheel to motor shaft,

remove screws that secure motor mount brackets to
blower housing, and slide motor and motor mount out of
blower housing.

2. Remove and clean blower wheel as follows:

a. Ensure proper reassembly by marking wheel orientation.

b. Lift wheel from housing. When handling and/or cleaning

blower wheel, be sure not to disturb balance weights
(clips) on blower wheel vanes.

c. Remove caked-on dirt from wheel and housing with a

brush. Remove lint and/or dirt accumulations from wheel
and housing with vacuum cleaner, using soft brush
attachment. Remove grease and oil with mild solvent.

d. Reassemble wheel into housing.

e. Reassemble motor into housing. Be sure set-screw(s) are

tightened on motor shaft flats and not on round part of
shaft.

f. Pivot blower access panel back into place. Adjust wire

assemblies so that wiring follows proper pathways.

g. Reinstall unit access panel.

3. Restore electrical power, then gas supply to unit. Start unit

and check for proper blower rotation and motor speeds
during heating and cooling cycles.

TROUBLESHOOTING

START-UP CHECKLIST

TABLE 2—ICM FIOP PHYSICAL DATA—UNIT 583B (CONTINUED)

THIS DATA APPLIES TO 583B UNITS WITH THE ICM INDOOR MOTOR FIOP

UNIT SIZE 583B

048090

048115

048130

060090

060115

060130

NOMINAL CAPACITY (ton)

4

4

4

5

5

5

OPERATING WEIGHT (lb.)

421

421

421

468

468

468

COMPRESSORS

Quantity

Scroll

1

REFRIGERANT (R-410A)

Quantity (lb.)

9.5

9.5

9.5

10.0

10.0

10.0

REFRIGERANT METERING DEVICE

Orifice ID (in.)

Check-Flo-Rater™ Piston

.073

.073

.073

.086

.086

.086

CONDENSER COIL

Rows...Fins/in.

Face Area (sq ft)

2...17

12.3

2...17

12.3

2...17

12.3

2...17

16.4

2...17

16.4

2...17

16.4

CONDENSER FAN

Nominal Cfm

Diameter (in.)

Motor Hp (Rpm)

3300

22

1/4 (1100)

3300

22

1/4 (1100)

3300

22

1/4 (1100)

3300

22

1/4 (1100)

3300

22

1/4 (1100)

3300

22

1/4 (1100)

EVAPORATOR COIL

Rows...Fins/in.

Face Area (sq ft)

4...15

4.7

4...15

4.7

4...15

4.7

4...15

4.7

4...15

4.7

4...15

4.7

EVAPORATOR BLOWER

Nominal Airflow (Cfm)

Size (in.)

Motor (HP)

1600

11 X 10

3/4

1600

11 X 10

3/4

1600

11 X 10

3/4

2000

11 X 10

1.0

2000

11 X 10

1.0

2000

11 X 10

1.0

FURNACE SECTION*

Burner Orifice No. (Qty...Drill Size)

Natural Gas

Burner Orifice No. (Qty...Drill Size)

Propane Gas

3...38
3...46

3...33
3...42

3...31
3...41

3...38
3...46

3...33
3...42

3...31
3...41

HIGH-PRESSURE SWITCH (psig)

Cutout

Reset (Auto)

610 ± 15
420 ± 25

LOSS-OF-CHARGE/LOW-PRESSURE SWITCH

(Liquid Line) (psig)

Cutout

Reset (Auto)

20 ± 5

45 ± 10

RETURN-AIR FILTERS (in.)

Throwaway

24 X 30 X 1

24 X 30 X 1

24 X 30 X 1

24 X 30 X 1

24 X 30 X 1

24 X 30 X 1

* Based on altitude of 0 to 2000 ft.

TABLE 3—583B WITH ICM FIOP ELECTRICAL DATA

UNIT

SIZE 583B

V-PH-HZ

VOLTAGE

RANGE

COMPRESSOR

OUTDOOR FAN

MOTOR

INDOOR FAN

MOTOR

POWER SUPPLY

MIN

MAX

RLA

LRA

FLA

FLA

MCA

MAX FUSE

OR CKT. BKR.

024

208/230–1–60

187

253

13.5

61.0

0.9

4.3

22.1

30

030

208/230–1–60

187

253

14.7

73.0

0.9

4.3

23.6

30

036

208/230–1–60

187

253

15.4

83.0

0.9

6.8

27.0

35

042

208/230–1–60

187

253

18.6

105.0

0.9

6.8

31.0

40

048

208/230–1–60

187

253

20.5

109.0

1.6

6.8

34.0

40

060

208/230–1–60

187

253

27.6

158.0

1.6

9.2

45.2

60

—13—

Summary of Contents for 602B

Page 1: ...or all brazing operations WARNING Improper installation adjustment alter ation service maintenance or use can cause explosion fire electric shock or other occurrences which could cause serious injury...

Page 2: ...from the installer s packet included with unit and install grommet in the knockout opening Provide a drip loop before running wire through panel Run the low voltage leads from the thermostat through...

Page 3: ...t is desirable to allow system coils time to cool down in conjunction with the airflow in heating mode 3 A no delay option used for servicing unit or when a thermostat is utilized to perform delay fun...

Page 4: ...energized If the installation includes the use of this operating mode do not use these terminals to control accessories See Electronic Air Cleaner and Humidifier sections for further information b EL...

Page 5: ...onents used See Fig 8 a GAS HEAT CFM SELECT GAS HEAT INPUT SIZE Factory selected gas heat size should correspond to unit label b AC HP SIZE SELECT SYSTEM SIZE INSTALLED Factory selected air conditione...

Page 6: ...stem size please verify 3 SYSTEM TYPE Factory selected on 683B system for HP EFF 4 AC HP CFM ADJUST Select NOM Lo for 060 5 ON OFF DELAY Select ENH profile 6 CONTINUOUS FAN Select desired fan speed wh...

Page 7: ...Occurs if outdoor temperature is above outdoor temperature change over setpoint 1 Thermidistat closes circuit R to G and R to Y Y2 The unit delivers selected heat pump heating airflow g HEATING MODE...

Page 8: ...rt This will minimize cold blow in heat pump operation 602B only and could enhance system efficiency f CONTINUOUS FAN SELECT DESIRED FAN SPEED WHEN THERMOSTAT IS SET ON CONTINUOUS FAN 1 LO speed Facto...

Page 9: ...it board provides connection terminals for use of a standard humidistat The unit will detect the humidistat contacts opening on increasing humidity and reduce its airflow to approximately 80 percent o...

Page 10: ...y minimal If a substantial adjustment is indicated an abnormal condition exists somewhere in the cooling system such as insuf ficient airflow across either one or both coils I 583B START UP ICM FIOP C...

Page 11: ...switches in AUTO positions Observe that unit operates in heating mode when tempera ture control is set to call for heating above room temperature and operates in cooling mode when tempera ture contro...

Page 12: ...ide assembly out Be careful not to tear insulation in blower compartment e Ensure proper reassembly by marking blower wheel and motor in relation to blower housing before disassembly TABLE 1 ICM FIOP...

Page 13: ...Quantity lb 9 5 9 5 9 5 10 0 10 0 10 0 REFRIGERANT METERING DEVICE Orifice ID in Check Flo Rater Piston 073 073 073 086 086 086 CONDENSER COIL Rows Fins in Face Area sq ft 2 17 12 3 2 17 12 3 2 17 12...

Page 14: ...Fig 14 ICM FIOP Electric Schematic Unit 583B C01035 14...

Page 15: ...OUTDOOR FAN Nominal Cfm Diameter in Motor Hp Rpm 2350 22 1 8 825 2350 22 1 8 825 2350 22 1 8 825 2500 22 1 4 1100 2500 22 1 4 1100 2350 22 1 8 825 2350 22 1 8 825 INDOOR COIL Rows Fins in Face Area sq...

Page 16: ...7 INDOOR BLOWER Nominal Airflow Cfm Size in Motor HP 1600 11 X 10 3 4 1600 11 X 10 3 4 1600 11 X 10 3 4 1750 11 X 10 1 0 1750 11 X 10 1 0 1750 11 X 10 1 0 FURNACE SECTION Burner Orifice No Qty Drill S...

Page 17: ...Fig 15 ICM FIOP Electric Schematic Unit 683B C01101 17...

Page 18: ...7 12 3 2 17 12 3 2 17 16 4 CONDENSER FAN Nominal Cfm Diameter in Motor Hp Rpm 2350 22 1 8 825 2350 22 1 8 825 2350 22 1 8 825 2350 22 1 8 825 3300 22 1 4 1100 3300 22 1 4 1100 EVAPORATOR COIL Rows Fin...

Page 19: ...50 50 60 70 80 90 042 208 230 1 60 187 253 18 6 105 0 0 9 6 8 3 8 5 0 5 4 7 2 7 5 10 0 11 3 15 0 15 0 20 0 18 1 20 8 25 9 30 0 36 1 41 7 54 2 62 5 72 2 83 3 31 0 31 0 31 1 34 5 40 9 46 0 53 6 60 6 76...

Page 20: ...Fig 16 ICM FIOP Electrical Schematic 702B C01037 20...

Page 21: ...IL Rows Fins in face area sq ft 2 17 8 5 2 17 10 3 2 17 10 3 2 17 13 5 2 17 13 5 2 17 15 4 OUTDOOR FAN Nominal Airflow CFM Diameter Motor HP RPM 2350 22 1 8 825 2350 22 1 8 825 2800 22 1 4 1100 2500 2...

Page 22: ...40 40 60 60 70 80 80 90 100 110 042 208 230 1 60 187 253 22 4 105 0 0 9 6 8 3 8 5 0 5 4 7 2 7 5 10 0 11 3 15 0 15 0 20 0 18 1 20 8 25 9 30 0 36 1 41 7 54 2 62 5 72 2 83 3 35 7 35 7 58 3 61 7 68 1 73 2...

Page 23: ...Fig 17 ICM FIOP Electrical Schematic 602B c01036 23...

Page 24: ...n selections deliver equal airflow TABLE 12 583B 683B COOLING AND HEAT PUMP HEATING 683B ONLY DRY COIL ICM AIRFLOW LARGE CABINET UNIT SIZE CFM ADJUST PIN SELECT LO PIN NOM PIN HI PIN EXTERNAL STATIC P...

Page 25: ...1600 53 35 65 170 130 1750 54 40 70 175 060 90 1600 41 25 55 155 115 1600 53 35 65 170 130 1800 53 40 70 175 TABLE 16 702B 602B COOLING HEATING DRY COIL ICM AIRFLOW SMALL CABINET UNIT SIZE CFM ADJUST...

Page 26: ...N WG SMALL CABINET STATIC CFM 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 5 kW 0 00 0 00 0 00 0 00 0 00 0 00 0 00 0 00 0 02 0 04 0 06 0 07 7 5 kW 0 00 0 00 0 00 0 00 0 00 0 00 0 02 0 03 0 0...

Page 27: ...60 0 029 0 032 0 036 0 040 0 045 0 049 0 053 TABLE 22 FILTER PRESSURE DROP TABLE IN WG FILTER SIZE CFM 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 20 X 20...

Page 28: ...Super Dehumidify set to ON Option 12 Heaters during Defrost setting 2 is suggested for all heaters Option 16 Heat pump systems set to ON for warmer heat below 40 F Option 17 Select programmable or no...

Page 29: ...TDOOR CONDENSER AIR TEMPERATURE ___________DB RETURN AIR TEMPERATURE ___________DB ___________WB COOLING SUPPLY AIR ___________DB ___________WB HEAT PUMP SUPPLY AIR ___________ GAS HEAT SUPPLY AIR ___...

Page 30: ...2001 Bryant Heating Cooling Systems 7310 W Morris St Indianapolis IN 46231 30 Printed in U S A ii583b243 Catalog No 5358 308...

Reviews: