Bryant 602B Installation, Start-Up, And Operating Instructions Manual Download Page 11

remains on for 4 minutes. Observe that compressor,
outdoor fan and indoor blower motors start after the call
for Cooling. At the end of 4 minutes, the cooling cycle
stops and the MODE reverts back to OFF. The Indoor
Blower continues to run for the time selected on the Easy
Select™ board after OFF icon is displayed.

(3.) HEAT PUMP HEATING—

Press MODE button on the Thermidistat™ until HEAT
icon is displayed. Heat pump heating begins within 10 sec.
and remains on for 4 minutes. Observe that the compres-
sor, outdoor fan and indoor blower come on. At the end of
the 4 minutes, heating cycle stops and the MODE reverts
back to OFF. The indoor blower continues to run for the
time selected on the Easy Select™ Board after the OFF
icon is displayed. Heating maybe turned off anytime
during the 4 minute cycle by pressing MODE button until
OFF is displayed.

(4.) GAS HEAT MODE—

Press MODE button until E-HEAT(Emergency Heat or
Back-Up Heat) icon is displayed. Gas heating begins
within 10 sec. and remains on for 4 minutes. The induced
draft motor should start immediately. The burners should
light within 5 sec. of E-HEAT call. The indoor blower will
turn on 45 sec. after the flame has been established. Gas
heating stops at the end of 4 minutes and MODE reverts
back to OFF. The indoor blower continues to run for the
time selected on the Easy Select™ Board after the OFF
icon is displayed.

NOTE:

If the burners do not light, this lighting sequence is

repeated for 15 minutes from the initial call for E-HEAT. If after
15 minutes the burners do not light, there will be a lockout. To
reset the burner lockout control, break the 24-v. power to “W”.

(5.) AUTOMATIC CHANGE-OVER—

To test AUTO CHANGE-OVER function between COOL
and HEAT:
Enable the AUTO CHANGE-OVER mode during Thermi-
distat™ set-up. Refer to the Thermidistat™ literature for
details. Observe that the unit operates in cooling when in
COOL MODE (when setting is below room temperature)
and HEAT MODE (when setting is above room tempera-
ture).

AIRFLOW AND TEMPERATURE RISE-The heating section for
each size unit is designed and approved for heating operation
within the temperature rise range stamped on the unit rating plate.
Table 15 shows the approved temperature rise range for each
heating input, and the air delivery (CFM) at various temperature
rise ranges.
The heating operation airflow must produce a temperature rise that
falls with in the approved range.
Refer to Indoor Airflow and Airflow Tables on the following
pages to adjust heating airflow when required.

III.

702B: START-UP (ICM FIOP)

CHECKING COOLING CONTROL OPERATION–Start and
check the unit for proper cooling control operation as follows:

(1.) Place room thermostat SYSTEM switch in OFF position.

Observe that blower motor starts when FAN switch is
placed in ON position and shuts down when FAN switch
is placed in AUTO position.

(2.) Place SYSTEM switch in COOL position and FAN switch

in AUTO position. Set cooling control below room tem-
perature. Observe that compressor, condenser fan, and
evaporator blower motors start. Observe that cooling cycle
shuts down when control setting is satisfied. The evapo-
rator fan will continue to run for the selected off delay.

(3.) When using an auto-changeover room thermostat, place

both SYSTEM and FAN switches in AUTO positions.
Observe that unit operates in heating mode when tempera-
ture control is set to ‘‘call for heating’’ (above room
temperature) and operates in cooling mode when tempera-
ture control is set to ‘‘call for cooling’’ (below room
temperature).

NOTE: Once the compressor has started and then has stopped, it
will not start again until 5 minutes have elapsed. (The cooling
cycle remains ‘‘on’’ until the room temperature drops to point that
is slightly below the cooling control setting of the room thermostat.
At this point, the thermostat ‘‘breaks’’ the circuit between ther-
mostat terminal R to terminals Y and G.) These open circuits
de-energize contactor coil C and ICM board. The condenser and
compressor motors stop. After the time delay setting selected on
the Easy Select™ board (See Easy Select Section) , the blower
motor stops. The unit is in a ‘‘standby’’ condition, waiting for the
next ‘‘call for cooling’’ from the room thermostat.

IV.

602B: START-UP (ICM FIOP)

CHECKING COOLING AND HEATING CONTROL OPERA-
TION– Start and check the unit for proper control operation as
follows:

(1.) Place room thermostat SYSTEM switch or MODE control

in OFF position. Observe that blower motor starts when
FAN mode is placed in FAN ON position and shuts down
according to time delay selected on the Easy Select™
board (See Easy Select Section) when FAN MODE switch
is placed in AUTO position.

(2.) Thermostat:

When the room temperature rises to a point that is slightly
above the cooling control setting of the thermostat, the
thermostat completes the circuit between thermostat ter-
minal R to terminals Y, O and G. These completed circuits
through the thermostat connect contactor coil (C) (through
unit wire Y) and ICM board (through unit wire G) across
the 24-v. secondary of transformer (TRAN).
Thermidistat™ or Thermostat and Humidistat:
When the room temperature rises to a point that is slightly
above the cooling control setting of the thermostat, the
thermostat completes the circuit between thermostat ter-
minal R to terminals Y, O, DH, and G. These completed
circuits through the thermostat connect contactor coil (C)
(through unit wire Y) and ICM board (though unit wire G)
across the 24-v. secondary of transformer (TRANS).

(3.) Place system switch or MODE control in HEAT position.

Set control above room temperature. Observe that com-
pressor, outdoor fan, and indoor blower motors start.
Observe that heating cycle shuts down according to time
delay selected on the Easy Select™ board (See Easy Select
Section) when control setting is satisfied.

(4.) When using an automatic changeover room thermostat,

place both SYSTEM or MODE control and FAN mode
switches in AUTO positions. Observe that unit operates in
Cooling mode when temperature control is set to “call for
Cooling” (below room temperature), and unit operates in
Heating mode when temperature control is set to “call for
Heating” (above room temperature).

NOTE: Once the compressor has started and then has stopped, it
should not be started again until 5 minutes have elapsed. The
cooling cycle remains ‘‘on’’ until the room temperature drops to
point that is slightly below the cooling control setting of the room
thermostat. At this point, the thermostat ‘‘breaks’’ the circuit
between thermostat terminal R to terminals Y and G. These open
circuits de-energize contactor coil C and ICM board. The con-
denser and compressor motors stop. After the time delay setting
selected on the Easy Select™ board (See Easy Select Section) , the

—11—

Summary of Contents for 602B

Page 1: ...or all brazing operations WARNING Improper installation adjustment alter ation service maintenance or use can cause explosion fire electric shock or other occurrences which could cause serious injury...

Page 2: ...from the installer s packet included with unit and install grommet in the knockout opening Provide a drip loop before running wire through panel Run the low voltage leads from the thermostat through...

Page 3: ...t is desirable to allow system coils time to cool down in conjunction with the airflow in heating mode 3 A no delay option used for servicing unit or when a thermostat is utilized to perform delay fun...

Page 4: ...energized If the installation includes the use of this operating mode do not use these terminals to control accessories See Electronic Air Cleaner and Humidifier sections for further information b EL...

Page 5: ...onents used See Fig 8 a GAS HEAT CFM SELECT GAS HEAT INPUT SIZE Factory selected gas heat size should correspond to unit label b AC HP SIZE SELECT SYSTEM SIZE INSTALLED Factory selected air conditione...

Page 6: ...stem size please verify 3 SYSTEM TYPE Factory selected on 683B system for HP EFF 4 AC HP CFM ADJUST Select NOM Lo for 060 5 ON OFF DELAY Select ENH profile 6 CONTINUOUS FAN Select desired fan speed wh...

Page 7: ...Occurs if outdoor temperature is above outdoor temperature change over setpoint 1 Thermidistat closes circuit R to G and R to Y Y2 The unit delivers selected heat pump heating airflow g HEATING MODE...

Page 8: ...rt This will minimize cold blow in heat pump operation 602B only and could enhance system efficiency f CONTINUOUS FAN SELECT DESIRED FAN SPEED WHEN THERMOSTAT IS SET ON CONTINUOUS FAN 1 LO speed Facto...

Page 9: ...it board provides connection terminals for use of a standard humidistat The unit will detect the humidistat contacts opening on increasing humidity and reduce its airflow to approximately 80 percent o...

Page 10: ...y minimal If a substantial adjustment is indicated an abnormal condition exists somewhere in the cooling system such as insuf ficient airflow across either one or both coils I 583B START UP ICM FIOP C...

Page 11: ...switches in AUTO positions Observe that unit operates in heating mode when tempera ture control is set to call for heating above room temperature and operates in cooling mode when tempera ture contro...

Page 12: ...ide assembly out Be careful not to tear insulation in blower compartment e Ensure proper reassembly by marking blower wheel and motor in relation to blower housing before disassembly TABLE 1 ICM FIOP...

Page 13: ...Quantity lb 9 5 9 5 9 5 10 0 10 0 10 0 REFRIGERANT METERING DEVICE Orifice ID in Check Flo Rater Piston 073 073 073 086 086 086 CONDENSER COIL Rows Fins in Face Area sq ft 2 17 12 3 2 17 12 3 2 17 12...

Page 14: ...Fig 14 ICM FIOP Electric Schematic Unit 583B C01035 14...

Page 15: ...OUTDOOR FAN Nominal Cfm Diameter in Motor Hp Rpm 2350 22 1 8 825 2350 22 1 8 825 2350 22 1 8 825 2500 22 1 4 1100 2500 22 1 4 1100 2350 22 1 8 825 2350 22 1 8 825 INDOOR COIL Rows Fins in Face Area sq...

Page 16: ...7 INDOOR BLOWER Nominal Airflow Cfm Size in Motor HP 1600 11 X 10 3 4 1600 11 X 10 3 4 1600 11 X 10 3 4 1750 11 X 10 1 0 1750 11 X 10 1 0 1750 11 X 10 1 0 FURNACE SECTION Burner Orifice No Qty Drill S...

Page 17: ...Fig 15 ICM FIOP Electric Schematic Unit 683B C01101 17...

Page 18: ...7 12 3 2 17 12 3 2 17 16 4 CONDENSER FAN Nominal Cfm Diameter in Motor Hp Rpm 2350 22 1 8 825 2350 22 1 8 825 2350 22 1 8 825 2350 22 1 8 825 3300 22 1 4 1100 3300 22 1 4 1100 EVAPORATOR COIL Rows Fin...

Page 19: ...50 50 60 70 80 90 042 208 230 1 60 187 253 18 6 105 0 0 9 6 8 3 8 5 0 5 4 7 2 7 5 10 0 11 3 15 0 15 0 20 0 18 1 20 8 25 9 30 0 36 1 41 7 54 2 62 5 72 2 83 3 31 0 31 0 31 1 34 5 40 9 46 0 53 6 60 6 76...

Page 20: ...Fig 16 ICM FIOP Electrical Schematic 702B C01037 20...

Page 21: ...IL Rows Fins in face area sq ft 2 17 8 5 2 17 10 3 2 17 10 3 2 17 13 5 2 17 13 5 2 17 15 4 OUTDOOR FAN Nominal Airflow CFM Diameter Motor HP RPM 2350 22 1 8 825 2350 22 1 8 825 2800 22 1 4 1100 2500 2...

Page 22: ...40 40 60 60 70 80 80 90 100 110 042 208 230 1 60 187 253 22 4 105 0 0 9 6 8 3 8 5 0 5 4 7 2 7 5 10 0 11 3 15 0 15 0 20 0 18 1 20 8 25 9 30 0 36 1 41 7 54 2 62 5 72 2 83 3 35 7 35 7 58 3 61 7 68 1 73 2...

Page 23: ...Fig 17 ICM FIOP Electrical Schematic 602B c01036 23...

Page 24: ...n selections deliver equal airflow TABLE 12 583B 683B COOLING AND HEAT PUMP HEATING 683B ONLY DRY COIL ICM AIRFLOW LARGE CABINET UNIT SIZE CFM ADJUST PIN SELECT LO PIN NOM PIN HI PIN EXTERNAL STATIC P...

Page 25: ...1600 53 35 65 170 130 1750 54 40 70 175 060 90 1600 41 25 55 155 115 1600 53 35 65 170 130 1800 53 40 70 175 TABLE 16 702B 602B COOLING HEATING DRY COIL ICM AIRFLOW SMALL CABINET UNIT SIZE CFM ADJUST...

Page 26: ...N WG SMALL CABINET STATIC CFM 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 5 kW 0 00 0 00 0 00 0 00 0 00 0 00 0 00 0 00 0 02 0 04 0 06 0 07 7 5 kW 0 00 0 00 0 00 0 00 0 00 0 00 0 02 0 03 0 0...

Page 27: ...60 0 029 0 032 0 036 0 040 0 045 0 049 0 053 TABLE 22 FILTER PRESSURE DROP TABLE IN WG FILTER SIZE CFM 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 20 X 20...

Page 28: ...Super Dehumidify set to ON Option 12 Heaters during Defrost setting 2 is suggested for all heaters Option 16 Heat pump systems set to ON for warmer heat below 40 F Option 17 Select programmable or no...

Page 29: ...TDOOR CONDENSER AIR TEMPERATURE ___________DB RETURN AIR TEMPERATURE ___________DB ___________WB COOLING SUPPLY AIR ___________DB ___________WB HEAT PUMP SUPPLY AIR ___________ GAS HEAT SUPPLY AIR ___...

Page 30: ...2001 Bryant Heating Cooling Systems 7310 W Morris St Indianapolis IN 46231 30 Printed in U S A ii583b243 Catalog No 5358 308...

Reviews: