Bryant 598A Series D Installation And Start-Up Instructions Manual Download Page 15

J.

Compressor PTC Overload Protection

The control senses the resistance of the compressor internal
positive temperature coefficient (PTC) overloads. If PTC resis-
tance is out of range, control shuts off the unit until resistance
range is acceptable. See Table 8 for compressor PTC ranges.

When the control turns outdoor unit off due to out of range PTCs,
the unit remains off for 15 minutes with outdoor fan running. After
15 minutes, the control checks resistance every 5 minutes until it
reaches the reset range. During this time, a malfunction signal
appears at control board. If a PTC trip occurs 3 times, the control
locks out outdoor unit operation and provides a malfunction signal
at control and indoor thermostat.

K.

Pressure Switch Protection

The outdoor unit is equipped with high- and low-pressure
switches, wired in series. If the control senses the opening of a
pressure switch, it provides a 5-minute time delay in outdoor unit
operation with outdoor fan running. A malfunction signal appears
on control when pressure switch opens. If pressure switch remains
open for 1 hr or longer, a malfunction signal is provided at L
terminal on indoor thermostat.

WARNING:

Interlocked contactor coils are 240v, high

voltage. Electrical shock can cause personal injury or
death.

CAUTION:

Do not bypass interlocks of contactors, as

compressor damage will occur.

L.

Major Components

2-SPEED CONTROL

The 2-speed control board controls the following functions:
- High- and low-compressor contactor operation
- Outdoor fan motor operation
- Crankcase heater operation
- Compressor protection
- Pressure switch monitoring
- Second-stage latching
- Time delays
- 5-minute time delay speed-up (bypass)
Refer to the System Functions section for individual function
information.

HEADER PIN HOUSING

The header pin housing is the plastic assembly which holds the
stripped lead ends for field connections. The 2-speed control
receives 24-vac low-voltage control system inputs through the
housing/pins. The housing also contains jumpers which the control
uses for system configuration, such as heat pump versus air
conditioner. Refer to Fig. 11 for header pin housing configuration.

2-SPEED COMPRESSOR

The 2-speed compressor contains motor windings that provide
low-speed, 4 pole (1750 RPM) and high-speed, 2-pole (3500
RPM) operation. Refer to Table 9 for appropriate winding resis-
tances. Refer to unit wiring label for winding configurations.
The 2-speed compressor is protected by an internal pressure relief
(IPR) which relieves discharge gas into compressor shell when
differential between suction and discharge pressures exceeds 500
psi.
The compressor is also protected by 3 PTC devices attached to
motor windings. The PTC resistance is sensed by the 2-speed
control. See Table 8 for resistance ranges.

Fig. 9—LED and Potentiometer Location

A91503

HIGH VOLTAGE

LOW VOLTAGE

L2

LO

HI

CCH

ODF

O

C

LM1 LM2

DFT1 DFT2 T1

T2

S2

S1

PW2 PW1

P1

1

18

SPEED-UP

STAGE 2

LATCH

DEFROST

TIME

BALANCE

POINT

K7

K6

K5

K4

K3

K2

K1

LED 1

Fig. 10—Typical Cooling Balance Points

A91282

10

20

30

40

50

60

70

50

60

70

80

90

100

110

120

BTU (1000'S)

HIGH SPEED CAPACITY

 

HIGH SPEED
BALANCE POINT

LOW SPEED
BALANCE POINT

LOW SPEED CAPACITY

TEMPERATURE (°F)

STRUCTURE
BALANCE POINT

TABLE 8—COMPRESSOR PTC RANGES

COMPRESSOR INTERNAL PTC RESISTANCE

Safe range (77°F)

1.5k to 7.8k ohms

To trip

26k to 34k ohms

To reset

8.4k to 10k ohms

Fig. 11—Header Pin Housing Configuration

A93565

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

C - TRANSFORMER COMMON

R - TRANSFORMER LINE

Y2 - SECOND STAGE COOLING

L - MALFUNCTION LIGHT

Y1 - FIRST STAGE COOLING

—15—

Summary of Contents for 598A Series D

Page 1: ...om improper installation of equipment 1 Locate unit away from windows patios decks etc where unit operation sound may disturb customer 2 Ensure that vapor and liquid tube diameters are appropriate to capacity of unit 3 Run refrigerant tubes as directly as possible by avoiding unnecessary turns and bends 4 Leave some slack between structure and unit to absorb vibration 5 When passing refrigerant tu...

Page 2: ...ient in cooling mode is 125 F V REMOVE INDOOR CHECK FLO RATER PISTON AND REPLACE WITH TXV CAUTION For proper unit operation and reliability the outdoor unit must be installed with the factory supplied balance port hard shutoff TXV Do not install with evaporator coils having capillary tube metering devices After removing existing Check Flo Rater from indoor coil install factory supplied thermostati...

Page 3: ...oved Be sure field wiring complies with local and national fire safety and electrical codes and voltage to system is within limits shown on unit rating plate Contact local power company for correction of improper voltage See unit rating plate for recommended circuit protection device NOTE Operation of unit on improper line voltage constitutes abuse and could affect unit reliability See unit rating...

Page 4: ... a Bryant Thermidistat which controls temperature and humidity level without the need for an additional humidistat and relay LCC OPERATION FOR TYPICAL PSC FURNACES The standard blower operation of systems with typical PSC furnaces is covered in Fig 7J K M N P or R The blower runs in high or low speed in conjunction with compressor high or low speed operation When the LCC is wired according to Fig ...

Page 5: ...AC COMM N A OUTDOOR SENSOR CONNECTION C B S1 S2 C Y2 C BRYANT PROGRAMMABLE THERMOSTAT MODEL 2S TYPICAL FAN COIL TWO SPEED AIR CONDITIONER See notes 6 and 8 W2 Y E R W3 Y1 L H R1 D A97458 R C C Y1 TYPICAL FAN COIL TWO SPEED AIR CONDITIONER See note 8 Y G W2 R Y2 E W3 L H R1 24 VAC HOT 24 VAC COM HEAT STAGE 1 COOL STAGE 2 FAN R C G W Y2 Y1 OTHER BRAND TWO SPEED THERMOSTATS COOL STAGE 1 B A97453 24 V...

Page 6: ...PROGRAMMABLE THERMOSTAT MODEL 2S FK4C FAN COIL J1 JUMPER REMOVE J2 JUMPER FOR HEAT STAGING TWO SPEED AIR CONDITIONER See notes 6 8 and 19 DH Y1 Y1 W W1 O W2 Y1 W2 W1 Y Y2 Y2 Y Y2 O W2 H A97459 R Y2 R Y2 C C C R L Y1 OTHER BRAND TWO SPEED THERMOSTATS FK4C FAN COIL TWO SPEED AIR CONDITIONER J1 JUMPER REMOVE J2 JUMPER FOR HEAT STAGING G G Y Y2 DH W W1 Y1 W2 Y1 O W2 24 VAC HOT 24 VAC COM FAN COOL STAG...

Page 7: ... W2 G 24 VAC COMM N A OUTDOOR SENSOR CONNECTION C B S1 S2 C Y2 C BRYANT PROGRAMMABLE THERMOSTAT MODEL 2S SINGLE STAGE FURNACE TWO SPEED AIR CONDITIONER See note 6 W R Y1 R G L Y H R1 M A97455 24 VAC HOT 24 VAC COM HEAT STAGE 1 COOL STAGE 2 FAN R C G W Y2 R C Y1 C OTHER BRAND TWO SPEED THERMOSTATS SINGLE STAGE FURNACE TWO SPEED AIR CONDITIONER G W R Y Y2 L Y1 H R1 COOL STAGE 1 K A97450 24 VAC HOT 2...

Page 8: ... 1 FAN HEAT STAGE 1 COOL STAGE 2 HEAT STAGE 2 24 VAC HOT R W W1 Y Y2 O W2 Y1 W2 24 VAC COMM N A OUTDOOR SENSOR CONNECTION C B S1 S2 BRYANT PROGRAMMABLE THERMOSTAT MODEL 2S G H R1 A97457 24 VAC HOT 24 VAC COM HEAT STAGE 1 COOL STAGE 2 FAN R C G W Y2 R C Y1 C OTHER BRAND TWO SPEED THERMOSTATS TWO STAGE FURNACE WITH PSC BLOWER MOTOR TWO SPEED AIR CONDITIONER See notes 7 and 17 G R Y2 L W W1 Y Y2 W2 Y...

Page 9: ...W1 Y Y2 O W2 Y1 W2 G 24 VAC COMM N A OUTDOOR SENSOR CONNECTION C B S1 S2 C Y2 C BRYANT PROGRAMMABLE THERMOSTAT MODEL 2S TWO STAGE VARIABLE SPEED FURNACE WITH ICM BLOWER MOTOR TWO SPEED AIR CONDITIONER See notes 6 7 16 and 17 R Y1 R G L W W1 Y Y2 W2 Y1 24 VAC HOT 24 VAC COMM HEAT STAGE 1 COOL STAGE 2 FAN R C G W W1 Y Y2 R C HEAT STAGE 2 COOL STAGE 1 N A OUTDOOR SENSOR CONNECTION Y1 B S1 S2 C BRYANT...

Page 10: ... FAN 24 VAC HOT 24 VAC COM DEHUMIDIFY HUMIDIFY N A OUTDOOR SENSOR CONNECTIONS Y Y2 HUMIDIFIER 24 VAC OUTDOOR SENSOR See notes 11 12 13 15 16 and 17 O W2 W W1 Y1 W2 G R BRYANT THERMIDISTAT CONTROL VARIABLE SPEED CONDENSING FURNACE TWO SPEED AIR CONDITIONER W W1 G Y Y2 C Y2 R Y1 C DHUM HUM B S1 S2 W2 R C HEAT STAGE 1 COOL STAGE 1 COOL STAGE 2 HEAT STAGE 2 FAN 24 VAC HOT 24 VAC COMM DEHUMIDIFY HUMIDI...

Page 11: ...DIFY FUNCTION ON FK4C REMOVE J1 JUMPER AT FAN COIL CONTROL BOARD 11 THERMIDISTAT DIP SWITCH 1 SHOULD BE SET IN THE OFF POSITION FOR AIR CONDITIONER INSTALLA TIONS THIS IS THE FACTORY DEFAULT 12 THERMIDISTAT DIP SWITCH 2 SHOULD BE SET IN THE ON POSITION FOR 2 SPEED COMPRESSOR OPERATION 13 REFER TO INDOOR EQUIPMENT INSTALLATION INSTRUCTIONS FOR PROPER SETUP 14 TO ACTIVATE DEHUMIDIFY FEATURE ON CURRE...

Page 12: ...ASY SELECT control board that allows the installing technician to select proper airflows For adjustments to control board and recommended A C SIZE and CFM ADJUST selections refer to Table 5 This fan coil has an adjustable blower off delay factory set at 90 sec for high and low speed blower operation TABLE 3 AIRFLOW SELECTION FOR 333 B J AV FURNACES CFM 598A UNIT SIZE FURNACE MODEL HEATING SIZE FUR...

Page 13: ...TO or ON as desired Wait for appropriate time delay s and 2 minute minimum low speed run time Operate unit for 15 minutes Check refrigerant charge XI CHECK CHARGE WARNING Service valve gage ports are not equipped with Schrader valves To prevent personal injury make sure gage manifold is connected to the valve gage ports before moving valves off fully back seated position Wear safety glasses and gl...

Page 14: ...delay and if a pressure switch or compressor PTC overload should trip I Second Stage Latching Mechanical thermostats operate with a staging differential of 2 F droop Bryant electronic thermostats are droopless meaning that they maintain room temperature at set point without latching second stage If system is installed with a mechanical thermostat or second stage latching is desired the following i...

Page 15: ...ystem Functions section for individual function information HEADER PIN HOUSING The header pin housing is the plastic assembly which holds the stripped lead ends for field connections The 2 speed control receives 24 vac low voltage control system inputs through the housing pins The housing also contains jumpers which the control uses for system configuration such as heat pump versus air conditioner...

Page 16: ...MAINTENANCE For continuing high performance and to minimize possible equip ment failure periodic maintenance must be performed on this equipment Frequency of maintenance may vary depending upon geographic areas such as coastal applications TABLE 9 TWO SPEED COMPRESSOR WINDING RESISTANCE AT 70 F 20 WINDING 3 TON 4 TON 5 TON T1 T2 0 80 0 70 0 60 T1 T3 3 20 2 20 1 80 T1 T7 1 30 1 00 1 00 T1 T8 3 10 2...

Reviews: