NOTE:

Read the entire instruction manual before starting the

installation.

This symbol

indicates a change since the last issue.

SAFETY CONSIDERATIONS

Improper installation, adjustment, alteration, service, maintenance,
or use can cause explosion, fire, electrical shock, or other
conditions which may cause death, personal injury, or property
damage. Consult a qualified installer, service agency, or your
distributor or branch for information or assistance. The qualified
installer or agency must use factory-authorized kits or accessories
when modifying this product. Refer to the individual instructions
packaged with the kits or accessories when installing.

Follow all safety codes. Wear safety glasses, protective clothing,
and work gloves. Use quenching cloth for brazing operations.
Have fire extinguisher available. Read these instructions thor-
oughly and follow all warnings or cautions included in literature
and attached to the unit. Consult local building codes and National
Electrical Code (NEC) for special requirements.

Recognize safety information. This is the safety-alert symbol

.

When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury.

Understand these signal words; DANGER, WARNING, and
CAUTION. These words are used with the safety-alert symbol.
DANGER identifies the most serious hazards which will result in
severe personal injury or death. WARNING signifies hazards
which could result in personal injury or death. CAUTION is used
to identify unsafe practices which would result in minor personal
injury or product and property damage.

WARNING:

Before installing, modifying, or servicing

system, main electrical disconnect switch must be in the
OFF position. There may be more than 1 disconnect
switch. Lock out and tag switch with a suitable warning
label. Electrical shock can cause personal injury or death.

INSTALLATION RECOMMENDATIONS

NOTE:

In some cases noise in the living area has been traced to

gas pulsations from improper installation of equipment.

1. Locate unit away from windows, patios, decks, etc. where

unit operation sound may disturb customer.

2. Ensure that vapor and liquid tube diameters are appropriate

to capacity of unit.

3. Run refrigerant tubes as directly as possible by avoiding

unnecessary turns and bends.

4. Leave some slack between structure and unit to absorb

vibration.

5. When passing refrigerant tubes through the wall, seal

opening with RTV or other pliable silicon-based caulk. (See
Fig. 2.)

6. Avoid direct tubing contact with water pipes, duct work,

floor joists, wall studs, floors, and walls.

7. Do not suspend refrigerant tubing from joists and studs with

a rigid wire or strap which comes in direct contact with
tubing. (See Fig. 2.)

8. Ensure that tubing insulation is pliable and completely

surrounds vapor tube.

9. When necessary, use hanger straps which are 1 in. wide and

conform to shape of tubing insulation. (See Fig. 2.)

10. Isolate hanger straps from insulation by using metal sleeves

bent to conform to shape of insulation.

When outdoor unit is connected to factory-approved indoor unit,
outdoor unit contains system refrigerant charge for operation with
indoor unit of the same size when connected by 15 ft of
field-supplied or factory accessory tubing. For proper unit opera-
tion, check refrigerant charge using charging information located
on control box cover.

IMPORTANT:

Maximum liquid-line size is 3/8-in. O.D. for all

residential applications.

IMPORTANT:

Always install a liquid-line filter drier. Refer to

Product Data Sheet for appropriate part number. Obtain filter
driers from your local dealer or branch.

INSTALLATION

I.

CHECK EQUIPMENT AND JOB SITE

A.

Unpack Unit

Move to final location. Remove carton taking care not to damage
unit.

B.

Inspect Equipment

File claim with shipping company prior to installation if shipment
is damaged or incomplete. Locate unit rating plate on unit corner
panel. It contains information needed to properly install unit.
Check rating plate to be sure unit matches job specifications.

Fig. 1—Model 598A

A98538

installation and
start-up instructions

TWO-SPEED
SPLIT-SYSTEM
AIR CONDITIONER

Cancels:

II 598A-36-6

II 598A-36-7

10-98

598A

Series D

—1—

Summary of Contents for 598A Series D

Page 1: ...om improper installation of equipment 1 Locate unit away from windows patios decks etc where unit operation sound may disturb customer 2 Ensure that vapor and liquid tube diameters are appropriate to capacity of unit 3 Run refrigerant tubes as directly as possible by avoiding unnecessary turns and bends 4 Leave some slack between structure and unit to absorb vibration 5 When passing refrigerant tu...

Page 2: ...ient in cooling mode is 125 F V REMOVE INDOOR CHECK FLO RATER PISTON AND REPLACE WITH TXV CAUTION For proper unit operation and reliability the outdoor unit must be installed with the factory supplied balance port hard shutoff TXV Do not install with evaporator coils having capillary tube metering devices After removing existing Check Flo Rater from indoor coil install factory supplied thermostati...

Page 3: ...oved Be sure field wiring complies with local and national fire safety and electrical codes and voltage to system is within limits shown on unit rating plate Contact local power company for correction of improper voltage See unit rating plate for recommended circuit protection device NOTE Operation of unit on improper line voltage constitutes abuse and could affect unit reliability See unit rating...

Page 4: ... a Bryant Thermidistat which controls temperature and humidity level without the need for an additional humidistat and relay LCC OPERATION FOR TYPICAL PSC FURNACES The standard blower operation of systems with typical PSC furnaces is covered in Fig 7J K M N P or R The blower runs in high or low speed in conjunction with compressor high or low speed operation When the LCC is wired according to Fig ...

Page 5: ...AC COMM N A OUTDOOR SENSOR CONNECTION C B S1 S2 C Y2 C BRYANT PROGRAMMABLE THERMOSTAT MODEL 2S TYPICAL FAN COIL TWO SPEED AIR CONDITIONER See notes 6 and 8 W2 Y E R W3 Y1 L H R1 D A97458 R C C Y1 TYPICAL FAN COIL TWO SPEED AIR CONDITIONER See note 8 Y G W2 R Y2 E W3 L H R1 24 VAC HOT 24 VAC COM HEAT STAGE 1 COOL STAGE 2 FAN R C G W Y2 Y1 OTHER BRAND TWO SPEED THERMOSTATS COOL STAGE 1 B A97453 24 V...

Page 6: ...PROGRAMMABLE THERMOSTAT MODEL 2S FK4C FAN COIL J1 JUMPER REMOVE J2 JUMPER FOR HEAT STAGING TWO SPEED AIR CONDITIONER See notes 6 8 and 19 DH Y1 Y1 W W1 O W2 Y1 W2 W1 Y Y2 Y2 Y Y2 O W2 H A97459 R Y2 R Y2 C C C R L Y1 OTHER BRAND TWO SPEED THERMOSTATS FK4C FAN COIL TWO SPEED AIR CONDITIONER J1 JUMPER REMOVE J2 JUMPER FOR HEAT STAGING G G Y Y2 DH W W1 Y1 W2 Y1 O W2 24 VAC HOT 24 VAC COM FAN COOL STAG...

Page 7: ... W2 G 24 VAC COMM N A OUTDOOR SENSOR CONNECTION C B S1 S2 C Y2 C BRYANT PROGRAMMABLE THERMOSTAT MODEL 2S SINGLE STAGE FURNACE TWO SPEED AIR CONDITIONER See note 6 W R Y1 R G L Y H R1 M A97455 24 VAC HOT 24 VAC COM HEAT STAGE 1 COOL STAGE 2 FAN R C G W Y2 R C Y1 C OTHER BRAND TWO SPEED THERMOSTATS SINGLE STAGE FURNACE TWO SPEED AIR CONDITIONER G W R Y Y2 L Y1 H R1 COOL STAGE 1 K A97450 24 VAC HOT 2...

Page 8: ... 1 FAN HEAT STAGE 1 COOL STAGE 2 HEAT STAGE 2 24 VAC HOT R W W1 Y Y2 O W2 Y1 W2 24 VAC COMM N A OUTDOOR SENSOR CONNECTION C B S1 S2 BRYANT PROGRAMMABLE THERMOSTAT MODEL 2S G H R1 A97457 24 VAC HOT 24 VAC COM HEAT STAGE 1 COOL STAGE 2 FAN R C G W Y2 R C Y1 C OTHER BRAND TWO SPEED THERMOSTATS TWO STAGE FURNACE WITH PSC BLOWER MOTOR TWO SPEED AIR CONDITIONER See notes 7 and 17 G R Y2 L W W1 Y Y2 W2 Y...

Page 9: ...W1 Y Y2 O W2 Y1 W2 G 24 VAC COMM N A OUTDOOR SENSOR CONNECTION C B S1 S2 C Y2 C BRYANT PROGRAMMABLE THERMOSTAT MODEL 2S TWO STAGE VARIABLE SPEED FURNACE WITH ICM BLOWER MOTOR TWO SPEED AIR CONDITIONER See notes 6 7 16 and 17 R Y1 R G L W W1 Y Y2 W2 Y1 24 VAC HOT 24 VAC COMM HEAT STAGE 1 COOL STAGE 2 FAN R C G W W1 Y Y2 R C HEAT STAGE 2 COOL STAGE 1 N A OUTDOOR SENSOR CONNECTION Y1 B S1 S2 C BRYANT...

Page 10: ... FAN 24 VAC HOT 24 VAC COM DEHUMIDIFY HUMIDIFY N A OUTDOOR SENSOR CONNECTIONS Y Y2 HUMIDIFIER 24 VAC OUTDOOR SENSOR See notes 11 12 13 15 16 and 17 O W2 W W1 Y1 W2 G R BRYANT THERMIDISTAT CONTROL VARIABLE SPEED CONDENSING FURNACE TWO SPEED AIR CONDITIONER W W1 G Y Y2 C Y2 R Y1 C DHUM HUM B S1 S2 W2 R C HEAT STAGE 1 COOL STAGE 1 COOL STAGE 2 HEAT STAGE 2 FAN 24 VAC HOT 24 VAC COMM DEHUMIDIFY HUMIDI...

Page 11: ...DIFY FUNCTION ON FK4C REMOVE J1 JUMPER AT FAN COIL CONTROL BOARD 11 THERMIDISTAT DIP SWITCH 1 SHOULD BE SET IN THE OFF POSITION FOR AIR CONDITIONER INSTALLA TIONS THIS IS THE FACTORY DEFAULT 12 THERMIDISTAT DIP SWITCH 2 SHOULD BE SET IN THE ON POSITION FOR 2 SPEED COMPRESSOR OPERATION 13 REFER TO INDOOR EQUIPMENT INSTALLATION INSTRUCTIONS FOR PROPER SETUP 14 TO ACTIVATE DEHUMIDIFY FEATURE ON CURRE...

Page 12: ...ASY SELECT control board that allows the installing technician to select proper airflows For adjustments to control board and recommended A C SIZE and CFM ADJUST selections refer to Table 5 This fan coil has an adjustable blower off delay factory set at 90 sec for high and low speed blower operation TABLE 3 AIRFLOW SELECTION FOR 333 B J AV FURNACES CFM 598A UNIT SIZE FURNACE MODEL HEATING SIZE FUR...

Page 13: ...TO or ON as desired Wait for appropriate time delay s and 2 minute minimum low speed run time Operate unit for 15 minutes Check refrigerant charge XI CHECK CHARGE WARNING Service valve gage ports are not equipped with Schrader valves To prevent personal injury make sure gage manifold is connected to the valve gage ports before moving valves off fully back seated position Wear safety glasses and gl...

Page 14: ...delay and if a pressure switch or compressor PTC overload should trip I Second Stage Latching Mechanical thermostats operate with a staging differential of 2 F droop Bryant electronic thermostats are droopless meaning that they maintain room temperature at set point without latching second stage If system is installed with a mechanical thermostat or second stage latching is desired the following i...

Page 15: ...ystem Functions section for individual function information HEADER PIN HOUSING The header pin housing is the plastic assembly which holds the stripped lead ends for field connections The 2 speed control receives 24 vac low voltage control system inputs through the housing pins The housing also contains jumpers which the control uses for system configuration such as heat pump versus air conditioner...

Page 16: ...MAINTENANCE For continuing high performance and to minimize possible equip ment failure periodic maintenance must be performed on this equipment Frequency of maintenance may vary depending upon geographic areas such as coastal applications TABLE 9 TWO SPEED COMPRESSOR WINDING RESISTANCE AT 70 F 20 WINDING 3 TON 4 TON 5 TON T1 T2 0 80 0 70 0 60 T1 T3 3 20 2 20 1 80 T1 T7 1 30 1 00 1 00 T1 T8 3 10 2...