Bryant 582A Series Installation, Start-Up And Service Instructions Manual Download Page 7

VI. STEP 6 — CONNECT CONDENSATE DRAIN

NOTE:

When installing condensate drain connection be sure

to comply with local codes and restrictions.

Models 582A and 583A dispose of condensate water through
a

3

4

in. NPT fitting which exits through the compressor ac-

cess panel. See Fig. 2 and 3 for location.

Condensate water can be drained directly onto the roof in roof-
top installations (where permitted) or onto a gravel apron in
ground-level installations. Install a field-supplied conden-
sate trap at end of condensate connection to ensure proper
drainage. Make sure that the outlet of the trap is at least
1 in. lower than the drain-pan condensate connection to pre-
vent the pan from overflowing. See Fig. 7. Prime the trap with
water. When using a gravel apron, make sure it slopes away
from the unit.

If the installation requires draining the condensate water away
from the unit, install a 2-in. trap at the condensate connec-
tion to ensure proper drainage. See Fig. 7. Make sure that
the outlet of the trap is at least 1 in. lower than the drain-
pan condensate connection to prevent the pan from overflow-
ing. Prime the trap with water. Connect a drain tube using a
minimum of

3

4

-in. PVC or

3

4

-in. copper pipe (all field-

supplied) at the outlet end of the 2-in. trap. Do not undersize
the tube. Pitch the drain tube downward at a slope of at least
one in. for every 10 ft of horizontal run. Be sure to check the
drain tube for leaks.

VII. STEP 7 — INSTALL FLUE HOOD

The flue hood assembly is shipped screwed to the coil panel
in the indoor blower compartment. Remove the service ac-
cess panel to locate the assembly.

For units being installed in California Air Quality Manage-
ment Districts which require NO

x

emissions of 40 nanograms/

joule or less, a field-installed low NO

x

kit must be installed.

For 40,000 and 60,000 Btuh input models, use kit part num-
ber CPLOWNOX002A00. This kit contains two NO

x

reduc-

tion baffles and one conversion label. For 90,000 115,000 and
130,000 Btuh input models, use kit part number
CPLOWNOX003A00. This kit contains three NO

x

reduction

baffles and one conversion label.

CAUTION:

The venting system is designed to en-

sure proper venting. The flue hood assembly must be
installed as indicated in this section of the unit instal-
lation instructions.

Install the flue hood as follows:

1. This installation must conform with local building codes

and with the National Fuel Gas Code (NFGC), ANSI
Z223.1 (in Canada, CAN/CGA B149.1, and B149.2) or
NFPA (National Fire Protection Association) latest re-
vision. Refer to Provincial and local plumbing or waste-
water codes and other applicable local codes.

2. Remove flue hood from shipping location (inside the blower

compartment). Place vent cap assembly over flue panel.
Orient screw holes in vent cap with holes in the flue panel.

3. Secure flue hood to flue panel by inserting a single screw

on the right side and the left side of the hood.

VIII. STEP 8 — INSTALL GAS PIPING

The gas supply pipe enters the unit through the access hole
provided. The gas connection to the unit is made to the

1

2

-in.

FPT gas inlet on the manual shutoff or gas valve.

Install a gas supply line that runs to the heating section. Re-
fer to Table 3 and the NFGC for gas pipe sizing. Do not use
cast-iron pipe. 
It is recommended that a black iron pipe is
used. Check the local utility for recommendations concern-
ing existing lines. Size gas supply piping for 0.5 in. wg maxi-
mum pressure drop. Never use pipe smaller than the

1

2

-in.

FPT gas inlet on the unit gas valve.

For natural gas applications, the gas pressure at unit gas con-
nection must not be less than 4.0 in. wg or greater than
13 in. wg while the unit is operating. For propane applica-
tions, the gas pressure must not be less than 4.0 in. wg or
greater than 13 in. wg at the unit connection.

An

1

8

-in. NPT plugged tapping accessible for test gage con-

nection must be installed immediately upstream of the gas
supply connection to the gas valve.

When installing the gas supply line, observe local codes per-
taining to gas pipe installations. Refer to the NFGC ANSI
Z223.1-1988 NFPA latest edition (in Canada, CAN/CGA B149.1,
(2)-M86). In the absence of local building codes, adhere to the
following pertinent recommendations:

1. Avoid low spots in long runs of pipe. Grade all pipe

1

4

inch in every 15 ft to prevent traps. Grade all hori-

zontal runs downward to risers. Use risers to connect to
heating section and to meter.

2. Protect all segments of piping system against physical

and thermal damage. Support all piping with appropri-
ate straps, hangers, etc. Use a minimum of one hanger
every 6 ft. For pipe sizes larger than

1

2

in., follow rec-

ommendations of national codes.

3. Apply joint compound (pipe dope) sparingly and only to

male threads of joint when making pipe connections. Use
only pipe dope that is resistant to action of liquefied
petroleum gases as specified by local and/or national codes.
Never use Teflon tape.

4. Install sediment trap in riser leading to heating section

per Fig. 8. This drip leg functions as a trap for dirt and
condensate.

5. Install an accessible, external, manual main shutoff valve

in gas supply pipe within 6 ft of heating section.

6. Install ground-joint union close to heating section be-

tween unit manual shutoff and external manual main
shutoff valve.

7. Pressure-test all gas piping in accordance with local and

national plumbing and gas codes before connecting pip-
ing to unit.

NOTE:

Pressure test the gas supply system after the gas sup-

ply piping is connected to the gas valve. The supply piping
must be disconnected from the gas valve during the test-
ing of the piping systems when test pressure is in excess of
0.5 psig. Pressure test the gas supply piping system at pres-
sures equal to or less than 0.5 psig. The unit heating section
must be isolated from the gas piping system by closing the
external main manual shutoff valve and slightly opening the
ground-joint union.

Fig. 7 — Condensate Trap

—7—

Summary of Contents for 582A Series

Page 1: ...rained personnel can perform basic maintenance func tions of cleaning coils and filters All other operations should be performed by trained service personnel When working on air conditioning equipment observe precautions in the lit erature tags and labels attached to the unit and other safety precautions that may apply Follow all safety codes Wear safety glasses and work gloves Use quenching cloth...

Page 2: ... 249 0 113 2 35 02 889 5 20 0 508 0 14 0 355 6 15 0 381 0 582A024040 060 208 230 1 60 280 0 127 3 35 02 889 5 22 5 571 5 13 0 330 2 15 0 381 0 582A030040 060 208 230 1 60 208 230 3 60 280 0 127 3 35 02 889 5 21 5 546 1 13 75 349 3 15 0 381 0 582A036060 090 208 230 1 60 208 230 3 60 460 3 60 314 0 142 7 35 02 889 5 22 5 571 5 14 0 355 6 13 0 330 2 582A042060 090 208 230 1 60 208 230 3 60 460 3 60 3...

Page 3: ... CG Center of Gravity COND Condenser EVAP Evaporator NEC National Electrical Code REQ D Required NOTE Dimensions are in mm in UNIT ELECTRICAL CHARACTERISTICS UNIT WEIGHT UNIT HEIGHT in mm CENTER OF GRAVITY in mm lb kg A X Y Z 582A048090 115 130 208 230 1 60 208 230 3 60 460 3 60 415 188 6 38 98 990 2 22 558 5 16 406 4 17 432 0 582A060090 115 130 208 230 1 60 208 230 3 60 460 3 60 450 204 5 38 98 9...

Page 4: ...d weatherproof all external ductwork joints and roof openings with counter flashing and mastic in accordance with applicable codes Ducts passing through an unconditioned space must be in sulated and covered with a vapor barrier If a plenum return is used on a vertical unit the return should be ducted through the roof deck to comply with applicable fire codes A minimum clearance is not required aro...

Page 5: ... applied as required to unit being installed 3 Dimensions in are in millimeters 4 Roof curb is made of 16 gage steel 5 Table lists only the dimensions per part number that have changed 6 Attach ductwork to curb flanges of duct rest on curb 7 Insulated panels 1 in thick fiberglass 1 lb density 8 Dimensions are in inches 3 0 4 0 BASE PAN BOTTOM SUPPLY 0 75 SIDE PANEL SUPPORT RIB S COUNTER FLASHING F...

Page 6: ... 14 0 355 6 042 377 171 4 21 5 546 1 13 5 342 9 048 437 198 6 22 0 558 5 17 0 432 0 060 472 214 5 22 0 558 5 17 0 432 0 UNIT 583A MAXIMUM WEIGHT A B Size lb kg in mm in mm 024 312 688 0 22 0 558 5 14 5 368 3 030 335 738 7 22 0 558 5 15 3 388 6 036 343 756 4 22 0 558 5 15 3 388 6 042 404 890 9 23 0 584 2 16 3 414 0 048 443 976 9 21 5 546 1 16 3 414 0 060 490 1080 5 23 5 596 9 16 3 414 3 Fig 6 Sugge...

Page 7: ...ide and the left side of the hood VIII STEP 8 INSTALL GAS PIPING The gas supply pipe enters the unit through the access hole provided The gas connection to the unit is made to the 1 2 in FPT gas inlet on the manual shutoff or gas valve Install a gas supply line that runs to the heating section Re fer to Table 3 and the NFGC for gas pipe sizing Do not use cast iron pipe It is recommended that a bla...

Page 8: ...owaway 20 x 20 20 x 20 20 x 20 20 x 20 20 x 20 20 x 24 20 x 24 20 x 24 20 x 24 UNIT SIZE 582A 048090 048115 048130 060090 060115 060130 NOMINAL CAPACITY ton 4 4 4 5 5 5 OPERATING WEIGHT lb 415 415 415 450 450 450 COMPRESSORS Scroll Reciprocating Quantity 1 1 REFRIGERANT R 22 Quantity lbs 6 0 6 0 6 0 8 0 8 0 8 0 REFRIGERANT METERING DEVICE Acutrol Device Orifice ID in 032 032 032 030 030 030 CONDEN...

Page 9: ...x 24 20 x 24 24 x 30 24 x 30 UNIT SIZE 583A 048090 048115 048130 060090 060115 060130 NOMINAL CAPACITY ton 4 4 4 5 5 5 OPERATING WEIGHT lb 421 421 421 468 468 468 COMPRESSORS Scroll Quantity 1 REFRIGERANT R 22 Quantity lb 7 2 7 2 7 2 8 1 8 1 8 1 REFRIGERANT METERING DEVICE Acutrol Device Orifice ID in 034 034 034 032 032 032 CONDENSER COIL Rows Fins in 2 17 2 17 2 17 2 17 2 17 2 17 Face Area sq ft...

Page 10: ...ommended that the basepan insulation around the perimeter of the vertical return air opening be secured to the basepan with aluminum tape Applicable local codes may require aluminum tape to prevent exposed fiberglass 6 Cover both horizontal duct openings with the duct cov ers from the accessory duct cover kit Ensure opening is air and watertight 7 After completing unit conversion perform all safet...

Page 11: ...recautions could result in damage to the unit being installed 1 Make all electrical connections in accordance with NEC ANSI NFPA latest edition and local electrical codes gov erning such wiring In Canada all electrical connec tions must be in accordance with CSA standard C22 1 Canadian Electrical Code Part 1 and applicable local codes Refer to unit wiring diagram 2 Use only copper conductor for co...

Page 12: ...3 8 27 5 45 208 230 3 60 187 253 10 7 85 0 1 6 3 8 18 8 25 460 3 60 414 506 5 3 42 0 0 9 2 0 9 5 15 048 208 230 1 60 197 253 25 3 131 0 1 6 3 8 37 0 60 208 230 3 60 187 253 13 5 108 0 1 6 3 8 22 3 35 460 3 60 414 506 6 7 47 5 0 9 2 0 11 3 15 060 208 230 1 60 187 253 28 9 147 0 1 6 6 2 43 9 60 208 230 3 60 187 253 18 6 125 0 1 6 6 2 31 1 45 460 3 60 414 506 8 5 66 5 0 9 3 2 14 7 20 LEGEND FLA Full ...

Page 13: ... Load Amps Fuse or HACR Breaker NOTES 1 In compliance with NEC National Electrical Code requirements for multimotor and combination load equipment refer to NEC Articles 430 and 440 the overcurrent protective device for the unit shall be fuse or HACR breaker The CGA Canadian Gas Association units may be fuse or circuit breaker 2 Minimum wire size is based on 60 C copper wire If other than 60 C wire...

Page 14: ...zed safety practices and wear protec tive goggles when checking or servicing refrigerant system 2 Do not operate compressor or provide any electric power to unit unless compressor terminal cover is in place and secured 3 Do not remove compressor terminal cover until all electrical sources are disconnected 4 Relieve and recover all refrigerant from system be fore touching or disturbing anything ins...

Page 15: ... sure that burner orifices are properly aligned Un stable operation may occur when the burner orifices in the manifold are misaligned Follow the lighting instructions on the heating section opera tion label located inside the burner or blower access door to start the heating section NOTE Make sure that gas supply has been purged and that all gas piping has been checked for leaks A Check Heating Co...

Page 16: ...pply to unit 2 Remove pipe plug on manifold see Fig 13 then con nect manometer at this point Turn on gas to unit 3 Record number of seconds for gas meter test dial to make one revolution 4 Divide number of seconds in Step 3 into 3600 number of seconds in one hour 5 Multiply result of Step 4 by the number of cu ft shown for one revolution of test dial to obtain cu ft of gas flow per hour 6 Multiply...

Page 17: ...at the flames are approxi mately the same for each burner Propane will have blue flame with yellow tips See Fig 14 Refer to Maintenance section for information on burner removal E Airflow and Temperature Rise The heating section for each size unit is designed and ap proved for heating operation within the temperature rise range stamped on the unit rating plate Table 7 shows the approved temperatur...

Page 18: ...he function of the switch is to close the main gas valve in the event of flame rollout The switch is located above the main burners When the temperature at the auxiliary switch reaches the maximum allowable temperature the R control circuit trips closing the gas valve and stopping gas flow to the burners The indoor evaporator fan motor IFM and in duced draft motor continue to run until switch is r...

Page 19: ...r Field Splice Terminal Marked Terminal Unmarked Splice Splice Marked Factory Wiring Field Control Wiring Field Power Wiring Accessory or Optional Wiring To Indicate Common Potential Only Not to Represent Wiring NOTES 1 If any of the original wires furnished are replaced they must be replaced with type 90 degree C wire or its equivalent 2 See price pages for thermostat and subbases 3 Use 75 degree...

Page 20: ...S Rollout Switch SEN Sensor SW Switch TRAN Transformer Field Splice Terminal Marked Terminal Unmarked Splice Splice Marked Factory Wiring Field Control Wiring Field Power Wiring Accessory or Optional Wiring To Indicate Common Potential Only Not to Represent Wiring NOTES 1 If any of the original wires furnished are replaced they must be replaced with type 90 de gree C wire or its equivalent 2 See p...

Page 21: ... Sensor SW Switch TRAN Transformer Field Splice Terminal Marked Terminal Unmarked Splice Splice Marked Factory Wiring Field Control Wiring Field Power Wiring Accessory or Optional Wiring To Indicate Common Potential Only Not to Represent Wiring NOTES 1 If any of the original wires furnished are replaced they must be replaced with type 90 de gree C wire or its equivalent 2 See price pages for therm...

Page 22: ... section on page 15 C Indoor Airflow and Airflow Adjustments CAUTION For cooling operation the recommended airflow is 350 to 450 cfm for each 12 000 Btuh of rated cooling capacity For heating operation the airflow must produce a temperature rise that falls within the range stamped on the unit rating plate Table 7 shows the temperature rise at various airflow rates Tables 9 and 10 show both heating...

Page 23: ...Fig 18 Cooling Charging Chart 582A018 Units Fig 19 Cooling Charging Chart 582A024 Units Fig 20 Cooling Charging Chart 582A030 Units Fig 21 Cooling Charging Chart 582A036 Units 23 ...

Page 24: ...Fig 21 Cooling Charging Chart 582A042 Units Fig 24 Cooling Charging Chart 582A060 Units Fig 23 Cooling Charging Chart 582A048 Units 24 ...

Page 25: ...Fig 25 Cooling Charging Chart 583A024 Units Fig 26 Cooling Charging Chart 583A030 Units Fig 27 Cooling Charging Chart 583A036 Units Fig 28 Cooling Charging Chart 583A042 Units 25 ...

Page 26: ...Fig 29 Cooling Charging Chart 583A048 Units Fig 30 Cooling Charging Chart 583A060 Units 26 ...

Page 27: ...126 1018 858 781 High Watts 810 800 790 782 766 742 723 709 688 661 627 Cfm 1800 1745 1660 1600 1547 1465 1360 1270 1163 967 876 042 Low Watts 675 660 650 640 630 620 610 595 580 Cfm 1454 1327 1326 1275 1204 1142 1081 995 918 Med Watts 886 855 825 795 778 765 750 735 718 700 Cfm 1515 1458 1406 1350 1285 1224 1163 1091 1013 932 High Watts 1000 950 925 910 890 875 855 833 Cfm 1551 1488 1424 1360 129...

Page 28: ...5 593 574 549 518 485 454 Cfm 1626 1614 1579 1532 1478 1421 1361 1295 1218 1120 Med Watts 726 695 661 625 591 561 540 Cfm 1731 1672 1610 1541 1456 1345 1193 High Watts 790 766 742 713 Cfm 1699 1602 1494 1367 048 Low Watts 614 588 577 572 566 556 539 517 491 Cfm 1591 1549 1518 1490 1460 1421 1372 1312 1242 Med Watts 778 756 738 719 699 676 650 623 596 572 555 Cfm 1854 1837 1804 1759 1705 1643 1577 ...

Page 29: ...op After a 30 second delay the blower motor stops The unit is in a standby condition waiting for the next call for cool ing from the room thermostat MAINTENANCE To ensure continuing high performance and to minimize the possibility of premature equipment failure periodic mainte nance must be performed on this equipment This combina tion heating cooling unit should be inspected at least once each ye...

Page 30: ... handling and or clean ing blower wheel be sure not to disturb balance weights clips on blower wheel vanes c Remove caked on dirt from wheel and housing with a brush Remove lint and or dirt accumulations from wheel and housing with vacuum cleaner using soft brush attachment Remove grease and oil with mild solvent d Reassemble wheel into housing e Reassemble motor into housing Be sure setscrews are...

Page 31: ...s piping at unit gas valve 5 Remove wires connected to gas valve Mark each wire 6 Remove ignitor and sensor wires at the ignitor module 7 Remove the mounting screw that attaches the burner rack to the basepan See Fig 31 8 Slide the burner rack out of the unit See Fig 31 and 34 9 To reinstall reverse the procedure outlined above VIII CONDENSER COIL EVAPORATOR COIL AND CONDENSATE DRAIN PAN Inspect t...

Page 32: ...connections are noticed disassemble the connection clean all the parts restrip the wire end and reassemble the connection properly and securely After inspecting the electrical controls and wiring replace the access panel Start the unit and observe at least one com plete heating cycle and one complete cooling cycle to ensure proper operation If discrepancies are observed in either or both operating...

Page 33: ...e and correct Defective run start capacitor overload or start relay Determine cause and replace Defective thermostat Replace thermostat Faulty condenser fan motor or capacitor Replace Restriction in refrigerant system Locate restriction and remove Compressor operates continuously Dirty air filter Replace filter Unit undersized for load Decrease load or increase unit size Thermostat set too low Res...

Page 34: ...east 5 minutes for any gas to dissipate before attempt ing to light unit 2 Check gas valve Inadequate heating Dirty air filter Clean or replace filter as necessary Gas input to furnace too low Check gas pressure at manifold Match with that on unit nameplate Unit undersized for application Replace with proper unit or add additional unit Restricted airflow Clean or replace filter Remove any restrict...

Page 35: ...g gaps etc Ensure that flame sense and ignition wires are properly terminated Verify that unit is obtaining proper amount of gas Induced draft motor fault LED 6 flashes IGC does not sense that induced draft motor is operating Check for proper voltage If motor is operating check the speed sensor plug IGC Terminal J2 connection Proper connection PIN 1 White PIN 2 Red PIN 3 Black Rollout switch fault...

Page 36: ......

Page 37: ......

Page 38: ...ing popular video based formats and materials All include video and or slides plus companion book Classroom Service Training which includes hands on experience with the products in our labs can mean increased confidence that really pays dividends in faster troubleshooting and fewer callbacks Course descriptions and schedules are in our catalog CALL FOR FREE CATALOG 1 800 962 9212 Packaged Service ...

Page 39: ......

Page 40: ...ORIFICE AND SETSCREW TIGHTNESS III START UP ELECTRICAL SUPPLY VOLTAGE L1 L2 L2 L3 L3 L1 COMPRESSOR AMPS L1 L2 L3 COMPRESSOR AMPS L1 L2 L3 INDOOR EVAPORATOR FAN AMPS TEMPERATURES OUTDOOR CONDENSER AIR TEMPERATURE DB RETURN AIR TEMPERATURE DB WB COOLING SUPPLY AIR DB WB GAS HEAT SUPPLY AIR PRESSURES GAS INLET PRESSURE IN WG GAS MANIFOLD PRESSURE IN WG REFRIGERANT SUCTION PSIG SUCTION LINE TEMP REFRI...

Reviews: