
Table 3 — Maximum Gas Flow Capacity*
NOMINAL
IRON PIPE,
SIZE
(in.)
INTERNAL
DIAMETER
(in.)
LENGTH OF PIPE, FT†
10
20
30
40
50
60
70
80
90
100
125
150
175
200
1
⁄
2
.622
175
120
97
82
73
66
61
57
53
50
44
40
—
—
3
⁄
4
.824
360
250
200
170
151
138
125
118
110
103
93
84
77
72
1
1.049
680
465
375
320
285
260
240
220
205
195
175
160
145
135
1
1
⁄
4
1.380
1400
950
770
600
580
530
490
460
430
400
360
325
300
280
1
1
⁄
2
1.610
2100
1460
1180
990
900
810
750
690
650
620
550
500
460
430
*Capacity of pipe in cu ft of gas per hr for gas pressure of 0.5 psig or less. Pressure drop of 0.5-in. wg (based on
a 0.60 specific gravity gas). Refer to Table C-4, National Fire Protection Association NFPA 54.
†This length includes an ordinary number of fittings.
X. STEP 10 — INSTALL ELECTRICAL CONNECTIONS
WARNING:
The unit cabinet must have an uninter-
rupted, unbroken electrical ground to minimize the pos-
sibility of personal injury if an electrical fault should
occur. This ground may consist of an electrical wire con-
nected to the unit ground lug in the control compart-
ment, or conduit approved for electrical ground when
installed in accordance with NEC (National Electrical
Code) ANSI/NFPA (latest edition) (in Canada, Cana-
dian Electrical Code CSA [Canadian Standards Asso-
ciation] C22.1) and local electrical codes. Do not use gas
piping as an electrical ground. Failure to adhere to this
warning could result in personal injury or death.
CAUTION:
Failure to follow these precautions could
result in damage to the unit being installed:
1. Make all electrical connections in accordance with NEC
ANSI/NFPA (latest edition) and local electrical codes gov-
erning such wiring. In Canada, all electrical connec-
tions must be in accordance with CSA standard C22.1
Canadian Electrical Code Part 1 and applicable local codes.
Refer to unit wiring diagram.
2. Use only copper conductor for connections between field-
supplied electrical disconnect switch and unit. DO NOT
USE ALUMINUM WIRE.
3. Be sure that high-voltage power to unit is within oper-
ating voltage range indicated on unit rating plate.
4. Do not damage internal components when drilling through
any panel to mount electrical hardware, conduit, etc. On
3-phase units, ensure phases are balanced within 2%.
Consult local power company for correction of improper
voltage and/or phase imbalance.
A. High-Voltage Connections
The unit must have a separate electrical service with a field-
supplied, waterproof, disconnect switch mounted at, or within
sight from, the unit. Refer to the unit rating plate for maxi-
mum fuse/circuit breaker size and minimum circuit amps (am-
pacity) for wire sizing. See Tables 4 and 5 for electrical data.
The field-supplied disconnect switch box may be mounted on
the unit over the high-voltage inlet hole when the standard
power and low-voltage entry points are used. See Fig. 2 and
3 for acceptable location.
See unit wiring label and Fig. 11 for reference when making
high voltage connections. Proceed as follows to complete the
high-voltage connections to the unit.
Fig. 9 — Supply and Return Duct Openings
Fig. 10 — Vertical Duct Cover Removed
—11—
Summary of Contents for 582A Series
Page 26: ...Fig 29 Cooling Charging Chart 583A048 Units Fig 30 Cooling Charging Chart 583A060 Units 26 ...
Page 36: ......
Page 37: ......
Page 39: ......